Electrical Wiring
(1) Description of SW01
SW01 1
SW01 2
SW01 3
SW01 4
wired
control
address
[1] [2] [3] [4] wired control address
0
0
0
0
main unit in
group control
0
0
0
1
sub unit 1 in
group control
0
0
1
0
sub unit 2 in
group control
0
0
1
1
sub unit 3 in
group control
1
1
1
1
sub unit 15 in
group control
SW01 5
SW01 6
SW01 7
SW01 8
indoor
unit
capacity
[5] [6] [7] [8]
indoor unit
capacity
0
0
0
0
0.6HP
0
0
0
1
0.8HP
0
0
1
0
1.0HP
0
0
1
1
1.2HP
0
1
0
0
1.5HP
0
1
0
1
1.7HP
0
1
1
0
2.0HP
0
1
1
1
2.5HP
1
0
0
0
3.0HP
1
0
0
1
3.2HP
1
0
1
0
4.0HP
1
0
1
1
5.0HP
1
1
0
0
6.0HP
1
1
0
1
8.0HP
1
1
1
0
10.0HP
1
1
1
1
15.0HP
(2) CN41,CN42,CN43,CN44 plug explanation
CN41
Set
address
by wired
controller
0
set the address with
wired controller is
unavailable(default)
1
set the address
with wired controller
is available (When
SW03 1 is off)
CN42
CN43
CN44
indoor
type
CN
44
CN
42
CN
43
indoor type
0
0
0
normal indoor (default)
0
0
1
wall mounted
0
1
0
Fresh air unit
0
1
1
OEM(HRV)
1
0
0
Ceiling floor
1
0
1
reserve (general
indoor unit)
1
1
0
reserve (general
indoor unit)
1
1
1
reserve (general
indoor unit)
*Note1*
1. 0 stands for open circuit,1 stands for socket
2. CN41 must be in short circuit, and SW03 1 at OFF when
addressing by wired controller
3. Using wired controller modifying physical address or
central control address, the other corresponding address
can change automatically, meeting as follows:
Central control address equals to physical address
plus 0 or 64.
17
Summary of Contents for XCT Series
Page 33: ...The manufacturer reserves the right to change any product specifications without notice ...
Page 88: ...Le fabricant se réserve le droit de modifier les spécifications du produit sans préavis ...
Page 116: ...DerHerstellerbehältsichdasRechtvor ProduktspezifikationenohneVorankündigungzuändern ...
Page 144: ...Elfabricantesereservaelderechodecambiarcualesquieraespecificacionesdeproductosinprevioaviso ...