(6) Jumper explanation
a) EEV operation manually(CN27, CN29)
CN27: short circuit CN27 2 seconds continuously, EEV is opened fully.
CN29: short circuit CN29 2 seconds continuously, EEV is closed fully.
b) time-short and self-check (CN28)
Short circuit CN28 2 seconds after power ON, process into time-short
Short circuit CN28 before power ON, process into self-check.
Code setting of wired controller
Function switches
Code Switch
status
Function description
Default
setting
Remarks
SW1
ON
Sub wired controller
OFF
OFF
main wired controller
SW2
ON
Common wired controller
ON
OFF
New fan-only has refrigerating,
heating, and air supplying modes
SW3
ON
Display ambient temperature
OFF
OFF
Do not display ambient temperature
SW4
ON
26 lock disabled
ON
OFF
26 lock enabled
SW5
ON
Collect ambient temperature of
wired controller
ON
OFF
Collect ambient temperature of PCB
SW6
ON
Power failure memory disabled
OFF
OFF
Power failure memory enabled
SW7
ON
Temperature sensor 4k7 enabled
ON
Between SW7
and SW8,one
and only one
must be ON
for any given
period
OFF
Temperature sensor 4k7 disabled
SW8
ON
Temperature sensor 5k1 enabled
OFF
OFF
Temperature sensor 5k1 disabled
Note: ON indicates short circuit; OFF indicates disconnection.
The difference between main and
sub wired controller
Topic
main
controller
sub controller
Function all function ON/OFF, Mode,
Fan speed,
Temp, Swing
function only.
20
EN
G
LI
SH
Summary of Contents for XCT Series
Page 33: ...The manufacturer reserves the right to change any product specifications without notice ...
Page 88: ...Le fabricant se réserve le droit de modifier les spécifications du produit sans préavis ...
Page 116: ...DerHerstellerbehältsichdasRechtvor ProduktspezifikationenohneVorankündigungzuändern ...
Page 144: ...Elfabricantesereservaelderechodecambiarcualesquieraespecificacionesdeproductosinprevioaviso ...
Page 172: ...O fabricante reserva se o direito de alterar as especificações do produto sem aviso prévio ...