Electrical Wiring
(5) Description of jump wire:SW08 (1:ON, 2:OFF)
J1
fix air volume
1
normal mode(default)
0
Air volume is fixed at high speed(for duct type)
J2
Run at Mid speed
when Hi Speed is selected
1
normal mode(default)
0
Run at Mid speed when Hi Speed is selected
J3
Quiet running mode
1
normal mode(default)
0
Quiet running mode
J4
This Indoor has highest priority
1
normal mode(default)
0
This Indoor has highest priority(the target degree of superheat
reduce 1 degree when Tao is between 10 and 43 degree)
J5
Indoor and outdoor 90 meters
drop selection
1
normal mode(default)
0
high drop
J6
reserved
--
--
J7
indoor installation
height selection
1
normal mode(default)
0
Above 2.7m, uses next higher fan speed (indoor fan speed improve
1 grade)
J8
twin energy source
1
normal mode-TES is unavailable (default)
0
TES is available
Note: 0 indicates disconnection, 1 indicates short circuit.
Default position:
SW01: depend on unit capacity CN41, CN42, CN43: open circuit.
CN44: open circuit except of floor ceiling unit SW07: all ON J1-J8: all ON.
19
Summary of Contents for XCT Series
Page 33: ...The manufacturer reserves the right to change any product specifications without notice ...
Page 88: ...Le fabricant se réserve le droit de modifier les spécifications du produit sans préavis ...
Page 116: ...DerHerstellerbehältsichdasRechtvor ProduktspezifikationenohneVorankündigungzuändern ...
Page 144: ...Elfabricantesereservaelderechodecambiarcualesquieraespecificacionesdeproductosinprevioaviso ...
Page 172: ...O fabricante reserva se o direito de alterar as especificações do produto sem aviso prévio ...