background image

PHD4 Series K and WPH4 Series K: Installation Instruction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

27

Maintenance

To ensure continuing high performance, and to minimize the possibility

of  premature  equipment  failure,  periodic  maintenance  must  be

performed on this equipment. This heat pump unit should be inspected at

least once each year by a qualified service person. To troubleshoot unit,

refer to 

Table 9

.

NOTE: 

TO EQUIPMENT OWNER: Consult your local dealer about the

availability of a maintenance contract.

The  minimum  maintenance  requirements  for  this  equipment  are  as

follows: 

1. Inspect air filter(s) each month. Clean or replace when necessary. 
2. Inspect indoor coil, drain pan, and condensate drain each cooling

season for cleanliness. Clean when necessary.

3. Inspect  blower  motor  and  wheel  for  cleanliness  each  cooling

season. Clean when necessary.

4. Check electrical connections for tightness and controls for proper

operation each cooling season. Service when necessary.

Step 1 – Air Filter

IMPORTANT: 

Never operate the unit without a suitable air filter in the

return-air  duct  system.  Always  replace  the  filter  with  the  same

dimensional  size  and  type  as  originally  installed.  See 

Table 1

  for

recommended filter sizes. 
Inspect  air  filter(s)  at  least  once  each  month  and  replace

(throwaway-type)  or  clean  (cleanable-type)  at  least  twice  during  each

cooling  season  and  twice  during  the  heating  season,  or  whenever  the

filter becomes clogged with dust and lint. 

Indoor Blower and Motor

NOTE: 

 All motors are pre-lubricated. Do not attempt to lubricate these

motors.

NOTE: 

460  volt  units  have  a  stepdown autotransformer  that  supplies

approximately 230 volts to a nominal 230 volt indoor blower motor.
For  longer  life,  operating  economy,  and  continuing  efficiency,  clean

accumulated dirt and grease from the blower wheel and motor annually.

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove blower access panel (see 

Fig. 25

).

b. Disconnect 5 pin plug and 4 pin plug from indoor blower motor. 

Remove capacitor if required.

c. On all units remove blower assembly from unit. Remove screws 

securing blower to blower partition and slide assembly out. Be 

careful not to tear insulation in blower compartment.

d. Ensure proper reassembly by marking blower wheel and motor in 

relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft, remove 

screws that secure motor mount brackets to housing, and slide 

motor and motor mount out of housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning blower 

wheel, be sure not to disturb balance weights (clips) on blower 

wheel vanes.

c. Remove caked-on dirt from wheel and housing with a brush. 

Remove lint and/or dirt accumulations from wheel and housing 

with vacuum cleaner, using soft brush attachment. Remove 

grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are tightened 

on motor shaft flats and not on round part of shaft. Reinstall 

blower into unit. Reinstall capacitor.

f. Connect 5 pin plug and 4 pin plug to indoor blower motor.

g. Reinstall blower access panel (see 

Fig. 25

).

3. Restore  electrical  power  to  unit.  Start  unit  and  check  for  proper

blower rotation and motor speeds during cooling cycles.

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury or death

and unit component damage.

The ability to properly perform maintenance on this equipment requires

certain expertise, mechanical skills, tools and equipment. If you do not

possess  these,  do  not  attempt  to  perform  any  maintenance  on  this

equipment, other than those procedures recommended in the Owner’s

Manual.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure  to  follow  these  warnings  could  result  in  personal  injury  or

death:

1. Turn  off  electrical  power  to  the  unit    and  install  a  lockout  tag

before performing any maintenance or service on this unit.

2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact with the

unit.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in improper operation.

Errors  made  when  reconnecting  wires  may  cause  improper  and

dangerous  operation.  Label  all  wires  prior  to  disconnecting  when

servicing.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect  and  tag  electrical  power  to  the  unit  before  cleaning  the

blower motor and wheel.

Summary of Contents for WPH4 Series

Page 1: ...and Defrost Mode 24 Maintenance 27 Indoor Blower and Motor 27 Refrigerant 30 Compressor Oil 30 Servicing Systems on Roofs with Synthetic Materials 31 Liquid Line Filter Drier 31 R 410A Refrigerant Cha...

Page 2: ...on on older G series roof curbs Two accessory kits are available to aid in installing a new G series unit on an old G roof curb 1 Accessory kit number CPADCURB001A00 small chassis and accessory kit nu...

Page 3: ...partial overhang such as a normal house overhang is 48 in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict out...

Page 4: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221484 Fig 2 PHD4 24 30 Unit D...

Page 5: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 A221486 Fig 3 WPH4 24 30 Unit D...

Page 6: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A221485 Fig 4 PHD4 36 60 Unit D...

Page 7: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 7 A221487 Fig 5 WPH4 36 60 Unit D...

Page 8: ...4 Attach ductwork to curb flanges of duct rest on curb 5 Insulated panels 1 in 25 mm thick fiberglass 1 lb density UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm Part Number CPRCURB011B00...

Page 9: ...al use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Particular attention should be...

Page 10: ...ing Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to...

Page 11: ...n accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tu...

Page 12: ...24 volt splice box See Fig 12 for connection diagram Run the low voltage leads from the thermostat through the control wiring inlet hole grommet see Fig 2 Fig 5 and into the low voltage splice box Pr...

Page 13: ...r Dual Accuraters Orifice ID in mm N A 0 080 1 2 03 1 N A Orifice OD in mm 0 032 2 0 81 2 0 035 2 0 89 2 0 040 2 1 02 2 0 046 2 1 17 2 0 046 2 1 17 2 0 046 2 1 17 2 Outdoor Coil Rows Fins in face area...

Page 14: ...ries K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 14 A09098 Fig 13 Typical Insta...

Page 15: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 15 A221468 Fig 14 Connection Wiring Schem...

Page 16: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 A221469 Fig 15 Ladder Wiring Schemat...

Page 17: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 17 A221470 Fig 16 Connection Wiring Schem...

Page 18: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221471 Fig 17 Ladder Wiring Schemat...

Page 19: ...nd WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221472 Fig 18 Connection Wiring Di...

Page 20: ...and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221473 Fig 19 Ladder Wiring Diag...

Page 21: ...temperature NOTE Once the compressor has started and then has stopped it should not be started again until 5 minutes have elapsed The defrost board has a built in 5 minute delay between cycles The 5 m...

Page 22: ...r than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments NO...

Page 23: ...able range for the speed tap to be used for dehumidification cooling 7 Use any spare vinyl plugs to cap any unused speed tap wires Single Speed Cooling With Higher Electric Heat Speed This unit can al...

Page 24: ...tive defrost cycles the control will lengthen the defrost interval by 15 minutes up to a maximum of 120 minutes or 30 minutes greater than the original setpoint whichever comes first If the previous d...

Page 25: ...0 41 0 41 High Black CFM 1505 1464 1423 1380 1336 1292 1242 1199 1145 1096 BHP 0 38 0 39 0 40 0 42 0 43 0 43 0 44 0 45 0 46 0 47 42 Low Blue CFM 956 899 843 786 729 676 621 558 504 435 BHP 0 13 0 13 0...

Page 26: ...4x24x1 406x610x25 356x610x25 3 0 3 5 4 0 0 09 0 09 0 10 0 12 0 13 0 15 0 17 0 17 0 19 0 21 1500 2200CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 8 Electr...

Page 27: ...slide assembly out Be careful not to tear insulation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscr...

Page 28: ...wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check...

Page 29: ...pect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 25 to locate all the electrical controls and wiring Check a...

Page 30: ...e interchanged The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves...

Page 31: ...polyethylene plastic drip cloth or tarp Cover an approximate 10x10 ft 3x3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent ru...

Page 32: ...ng vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil see Fig 27 The thermostat closes at 32_F...

Page 33: ...nt line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace...

Page 34: ...LECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOU...

Reviews: