background image

PHD4 Series K and WPH4 Series K: Installation Instruction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

12

High-Voltage Connections 

The unit must have  a  separate  electrical service  with  a  field-supplied,

waterproof disconnect switch mounted at, or within sight from the unit.

Refer  to  the  unit  rating  plate,  NEC  and  local  codes  for  maximum

fuse/circuit breaker size and minimum circuit amps (ampacity) for wire

sizing. 
The  field-supplied  disconnect  may  be  mounted  on  the  unit  over  the

high-voltage inlet hole when the standard power and low-voltage entry

points are used. See 

Fig. 2

 

Fig. 5

 for acceptable location. Remove high

voltage knockout.
See unit wiring label (

Fig. 14

 

Fig. 19

) and 

Fig. 12

 for reference when

making  high voltage  connections.  Proceed  as  follows to complete  the

high-voltage connections to the unit.

A09071

Fig. 12 – High- and Control-Voltage Connections

Single phase units:

1. Run the high-voltage (L1, L2) and ground lead into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the

contactor.

4. Connect field L1 to black wire on connection 11 of the compressor

contactor.

5. Connect  field  wire  L2  to  yellow  wire  on  connection  23  of  the

compressor contactor.

Three-phase units:

1. Run the high-voltage (L1, L2, L3) and ground lead into the control

box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the

contactor.

4. Connect field L1 to black wire on connection 11 of the compressor

contactor.

5. Connect  field  wire  L3  to  yellow  wire  on  connection  13  of  the

compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

Special Procedures for 208-V Operation 

Control Voltage Connections

NOTE: 

Do not use any type of power-stealing thermostat. Unit control

problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C

minimum)  wires to make the control voltage connections between the

thermostat  and  the  unit.  If  the  thermostat  is  located more  than  100  ft

(30.5 m) from the unit (as measured along the control voltage wires), use

no. 16 AWG color-coded, insulated (35° C minimum) wires.

Standard Connections

Locate the eight (nine on 3-phase) low voltage thermostat leads in 24

volt splice box. See 

Fig. 12

 for connection diagram. Run the low-voltage

leads from the thermostat, through the control wiring inlet hole grommet

(see 

Fig. 2

 

Fig. 5

), and into the low-voltage splice box. Provide a drip

loop  before  running  wires  through  panel.  Secure  and  strain  relief  all

wires so that they do not interfere with operation of unit. A gray wire is

standard on 3-phase units for connection to an economizer.
If an accessory electric heater is installed, low voltage leads from heater

must  be  connected  to  factory  supplied  control  leads  from  Indoor  Fan

Board P4 connector. 

NOTE: 

If the unit 24V wires do not have a matching receptacle, cut the

24V  wires  from  the  electric  heater  plug,  strip  the  ends,  and  wire  nut

together to match the schematic connections. If the electric heater 24V

wires  do  not  have  a  matching  plug,  cut  the  24V  wires  from  the  unit

receptacle, strip the ends, and wire nut together to match the schematic

connections.
Factory wires are provided for electric heat staging W1 and W2 (W2 and

W3 on IFB). If room thermostat has only one stage of supplemental heat,

connect white and  violet wires  shown  in 

Fig. 12

 to  second  stage heat

field wire. 
Some  electric  heaters  have  four  control  wires  (plus  common  wire).

Consult  unit  wiring  diagram  and  electric  heater  wiring  diagram  for

additional details.

Transformer Protection

The transformer is of the energy-limiting type. It is set to withstand a

30-second  overload  or  shorted  secondary  condition.  If  an  overload  or

short is present, correct overload condition and check for blown fuse on

Interface  Fan  Board.  Replace  fuse  as  required  with  correct  size  and

rating.

Accessory Electric Heaters Installation

Electric heaters may be installed with the unit per instructions supplied

with electric heater package. See unit rating plate for factory-approved

electric heater kits.

Sequence of Operation

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G energizing the blower 

motor for continuous fan.

b. COOLING MODE

(1.) If indoor temperature is above temperature set point, 

thermostat closes circuits R to G, R to Y and R to O-The 

unit delivers cooling airflow.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing  or servicing  system, always turn off main  power to

system. Tag the disconnect switch with a suitable warning label. With

disconnect switch open, move black wire from transformer (3/16 in.)

terminal marked 230 to terminal marked 208. This retaps transformer to

primary voltage of 208 vac.

Summary of Contents for WPH4 Series

Page 1: ...and Defrost Mode 24 Maintenance 27 Indoor Blower and Motor 27 Refrigerant 30 Compressor Oil 30 Servicing Systems on Roofs with Synthetic Materials 31 Liquid Line Filter Drier 31 R 410A Refrigerant Cha...

Page 2: ...on on older G series roof curbs Two accessory kits are available to aid in installing a new G series unit on an old G roof curb 1 Accessory kit number CPADCURB001A00 small chassis and accessory kit nu...

Page 3: ...partial overhang such as a normal house overhang is 48 in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict out...

Page 4: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221484 Fig 2 PHD4 24 30 Unit D...

Page 5: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 A221486 Fig 3 WPH4 24 30 Unit D...

Page 6: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A221485 Fig 4 PHD4 36 60 Unit D...

Page 7: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 7 A221487 Fig 5 WPH4 36 60 Unit D...

Page 8: ...4 Attach ductwork to curb flanges of duct rest on curb 5 Insulated panels 1 in 25 mm thick fiberglass 1 lb density UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm Part Number CPRCURB011B00...

Page 9: ...al use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Particular attention should be...

Page 10: ...ing Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to...

Page 11: ...n accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tu...

Page 12: ...24 volt splice box See Fig 12 for connection diagram Run the low voltage leads from the thermostat through the control wiring inlet hole grommet see Fig 2 Fig 5 and into the low voltage splice box Pr...

Page 13: ...r Dual Accuraters Orifice ID in mm N A 0 080 1 2 03 1 N A Orifice OD in mm 0 032 2 0 81 2 0 035 2 0 89 2 0 040 2 1 02 2 0 046 2 1 17 2 0 046 2 1 17 2 0 046 2 1 17 2 Outdoor Coil Rows Fins in face area...

Page 14: ...ries K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 14 A09098 Fig 13 Typical Insta...

Page 15: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 15 A221468 Fig 14 Connection Wiring Schem...

Page 16: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 A221469 Fig 15 Ladder Wiring Schemat...

Page 17: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 17 A221470 Fig 16 Connection Wiring Schem...

Page 18: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221471 Fig 17 Ladder Wiring Schemat...

Page 19: ...nd WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221472 Fig 18 Connection Wiring Di...

Page 20: ...and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221473 Fig 19 Ladder Wiring Diag...

Page 21: ...temperature NOTE Once the compressor has started and then has stopped it should not be started again until 5 minutes have elapsed The defrost board has a built in 5 minute delay between cycles The 5 m...

Page 22: ...r than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments NO...

Page 23: ...able range for the speed tap to be used for dehumidification cooling 7 Use any spare vinyl plugs to cap any unused speed tap wires Single Speed Cooling With Higher Electric Heat Speed This unit can al...

Page 24: ...tive defrost cycles the control will lengthen the defrost interval by 15 minutes up to a maximum of 120 minutes or 30 minutes greater than the original setpoint whichever comes first If the previous d...

Page 25: ...0 41 0 41 High Black CFM 1505 1464 1423 1380 1336 1292 1242 1199 1145 1096 BHP 0 38 0 39 0 40 0 42 0 43 0 43 0 44 0 45 0 46 0 47 42 Low Blue CFM 956 899 843 786 729 676 621 558 504 435 BHP 0 13 0 13 0...

Page 26: ...4x24x1 406x610x25 356x610x25 3 0 3 5 4 0 0 09 0 09 0 10 0 12 0 13 0 15 0 17 0 17 0 19 0 21 1500 2200CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 8 Electr...

Page 27: ...slide assembly out Be careful not to tear insulation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscr...

Page 28: ...wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check...

Page 29: ...pect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 25 to locate all the electrical controls and wiring Check a...

Page 30: ...e interchanged The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves...

Page 31: ...polyethylene plastic drip cloth or tarp Cover an approximate 10x10 ft 3x3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent ru...

Page 32: ...ng vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil see Fig 27 The thermostat closes at 32_F...

Page 33: ...nt line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace...

Page 34: ...LECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOU...

Reviews: