background image

PHD4 Series K and WPH4 Series K: Installation Instruction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

21

Pre-Start-Up

Use the Start-Up Checklist supplied at the end of this book and proceed

as follows to inspect and prepare the unit for initial start-up:

1. Remove all access panels (see 

Fig. 25

).

2. Read  and  follow  instructions  on  all  DANGER,  WARNING,

CAUTION,  and  INFORMATION  labels  attached  to,  or  shipped

with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as broken lines, 

loose parts, disconnected wires, etc.

b. Inspect all field and factory-wiring connections. Be sure that 

connections are completed and tight. Ensure wires do not touch 

refrigerant tubing or sharp sheet metal edges.

c. Inspect coil fins. If damaged during shipping and handling, 

carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor-fan blade is correctly positioned in fan 

orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled with 

water to ensure proper drainage. 

d. Make sure that all tools and miscellaneous loose parts have been 

removed. 

5. Each unit system has 2 Schrader-type ports, one low-side Schrader

fitting  located  on  the  suction  line,  and  one  high-side  Schrader

fitting located on the compressor discharge line. Be sure that caps

on the ports are tight.

Start-Up

Checking Cooling and Heating Control Operation

Start and check the unit for proper control operation as follows:

(1.) Place room thermostat SYSTEM switch or MODE control 

in OFF position. Observe that blower motor starts when 

FAN mode is placed in FAN ON position and shuts down 

when FAN MODE switch is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is slightly 

above the cooling control setting of the thermostat, the 

thermostat completes the circuit between thermostat 

terminal R to terminals Y, O and G.These completed circuits 

through the thermostat connect contactor coil (C) (through 

unit wire Y) and Indoor Fan board (through unit wire G) 

across the 24-v. secondary of transformer (TRAN).

(3.) Place system switch or MODE control in HEAT position. 

Set control above room temperature. Observe that 

compressor, outdoor fan, and indoor blower motors start. 

Observe that heating cycle shuts down when control setting 

is satisfied.

(4.) When using an automatic changeover room thermostat  

place both SYSTEM or MODE control and FAN mode 

switches in AUTO positions. Observe that unit operates in 

Cooling mode when temperature control is set to “call for 

Cooling” (below room temperature), and unit operates in 

Heating mode when temperature control is set to “call for 

Heating” (above room temperature).

NOTE: 

Once the compressor has started and then has stopped, it should

not be started again until 5 minutes have elapsed. The defrost board has a

built-in 5 minute delay between cycles. The 5 minute compressor delay

also applies to heat pump heating mode.

Step 1 –  Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to charge

the unit: 

1. Locate leak and make sure that refrigerant system pressure has been

relieved and reclaimed from both high- and low-pressure ports. 

2. Repair leak following Refrigerant Service procedures. 

NOTE: 

Install  a  bi-flow  filter  drier  whenever  the  system  has  been

opened for repair.

3. Add  a  small  charge  of  R-410A  refrigerant  vapor  to  system  and

leak-test unit. 

4. Recover  refrigerant  from  refrigerant  system  and  evacuate  to  500

microns if no additional leaks are not found. 

5. Charge  unit  with  R-410A  refrigerant,  using  an  electronic  scale.

Refer to unit rating plate for required charge. 

Step 2 – Start-Up Adjustments

Complete  the  required  procedures  given  in  the  Pre-Start-Up  section

before  starting  the  unit.  Do  not  jumper  any  safety  devices  when

operating the unit. Do not operate the unit in Cooling mode when the

outdoor temperature is below 40°F (4°C) (unless accessory low-ambient

kit is installed).

IMPORTANT: 

Three-phase, scroll compressors are direction oriented.

Unit must be checked to ensure proper compressor 3-phase power lead

orientation. If not corrected within 5 minutes, the internal protector will

shut off the compressor. The 3-phase  power leads  to the unit must be

WARNING

!

FIRE, EXPLOSION, ELECTRICAL SHOCK AND 

ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury, death or

property damage. 

1. Follow  recognized  safety  practices  and  wear  protective  goggles

when checking or servicing refrigerant system. 

2. Relieve and recover all refrigerant from system before touching or

disturbing compressor plug if refrigerant leak is suspected around

compressor terminals. 

3. Do  not  remove  compressor  plug  until  all  electrical  sources  are

disconnected and tagged. 

4. Never  attempt  to  repair  soldered  connection  while  refrigerant

system is under pressure.

5. Do not use torch to remove any component. System contains oil

and refrigerant under pressure.

To remove a component, wear protective goggles and proceed as

follows:

a. Shut off electrical power to unit and install lockout tag.

b. Relieve and reclaim all refrigerant from system using both high- 

and low-pressure ports. 

c. Cut component connecting tubing with tubing cutter and 

remove component from unit. 

d. Carefully unsweat remaining tubing stubs when necessary. Oil 

can ignite when exposed to torch flame.

WARNING

!

EXPLOSION HAZARD

Failure to follow this warning could result in

death,  serious  personal  injury,  and/or

property damage.

Never use air or gases containing oxygen for

leak  testing  or  operating  refrigerant

compressors.  Pressurized  mixtures  of  air  or

gases  containing  oxygen  can  lead  to  an

explosion.

Summary of Contents for WPH4 Series

Page 1: ...and Defrost Mode 24 Maintenance 27 Indoor Blower and Motor 27 Refrigerant 30 Compressor Oil 30 Servicing Systems on Roofs with Synthetic Materials 31 Liquid Line Filter Drier 31 R 410A Refrigerant Cha...

Page 2: ...on on older G series roof curbs Two accessory kits are available to aid in installing a new G series unit on an old G roof curb 1 Accessory kit number CPADCURB001A00 small chassis and accessory kit nu...

Page 3: ...partial overhang such as a normal house overhang is 48 in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict out...

Page 4: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221484 Fig 2 PHD4 24 30 Unit D...

Page 5: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 A221486 Fig 3 WPH4 24 30 Unit D...

Page 6: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A221485 Fig 4 PHD4 36 60 Unit D...

Page 7: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 7 A221487 Fig 5 WPH4 36 60 Unit D...

Page 8: ...4 Attach ductwork to curb flanges of duct rest on curb 5 Insulated panels 1 in 25 mm thick fiberglass 1 lb density UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm Part Number CPRCURB011B00...

Page 9: ...al use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Particular attention should be...

Page 10: ...ing Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to...

Page 11: ...n accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tu...

Page 12: ...24 volt splice box See Fig 12 for connection diagram Run the low voltage leads from the thermostat through the control wiring inlet hole grommet see Fig 2 Fig 5 and into the low voltage splice box Pr...

Page 13: ...r Dual Accuraters Orifice ID in mm N A 0 080 1 2 03 1 N A Orifice OD in mm 0 032 2 0 81 2 0 035 2 0 89 2 0 040 2 1 02 2 0 046 2 1 17 2 0 046 2 1 17 2 0 046 2 1 17 2 Outdoor Coil Rows Fins in face area...

Page 14: ...ries K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 14 A09098 Fig 13 Typical Insta...

Page 15: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 15 A221468 Fig 14 Connection Wiring Schem...

Page 16: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 A221469 Fig 15 Ladder Wiring Schemat...

Page 17: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 17 A221470 Fig 16 Connection Wiring Schem...

Page 18: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221471 Fig 17 Ladder Wiring Schemat...

Page 19: ...nd WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221472 Fig 18 Connection Wiring Di...

Page 20: ...and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221473 Fig 19 Ladder Wiring Diag...

Page 21: ...temperature NOTE Once the compressor has started and then has stopped it should not be started again until 5 minutes have elapsed The defrost board has a built in 5 minute delay between cycles The 5 m...

Page 22: ...r than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments NO...

Page 23: ...able range for the speed tap to be used for dehumidification cooling 7 Use any spare vinyl plugs to cap any unused speed tap wires Single Speed Cooling With Higher Electric Heat Speed This unit can al...

Page 24: ...tive defrost cycles the control will lengthen the defrost interval by 15 minutes up to a maximum of 120 minutes or 30 minutes greater than the original setpoint whichever comes first If the previous d...

Page 25: ...0 41 0 41 High Black CFM 1505 1464 1423 1380 1336 1292 1242 1199 1145 1096 BHP 0 38 0 39 0 40 0 42 0 43 0 43 0 44 0 45 0 46 0 47 42 Low Blue CFM 956 899 843 786 729 676 621 558 504 435 BHP 0 13 0 13 0...

Page 26: ...4x24x1 406x610x25 356x610x25 3 0 3 5 4 0 0 09 0 09 0 10 0 12 0 13 0 15 0 17 0 17 0 19 0 21 1500 2200CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 8 Electr...

Page 27: ...slide assembly out Be careful not to tear insulation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscr...

Page 28: ...wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check...

Page 29: ...pect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 25 to locate all the electrical controls and wiring Check a...

Page 30: ...e interchanged The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves...

Page 31: ...polyethylene plastic drip cloth or tarp Cover an approximate 10x10 ft 3x3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent ru...

Page 32: ...ng vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil see Fig 27 The thermostat closes at 32_F...

Page 33: ...nt line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace...

Page 34: ...LECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOU...

Reviews: