background image

PHD4 Series K and WPH4 Series K: Installation Instruction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

10

Rigging/Lifting of Unit (See 

Fig. 7

)

Lifting holes are provided in base rails as shown.

1. Attach shackles, clevis pins, and straps to the base rails of the unit.

Be  sure  materials  are  rated  to  hold  the  weight  of  the  unit  (See

Fig. 7

).

2. Attach a  clevis  of  sufficient  strength in the  middle  of  the  straps.

Adjust  the  clevis  location  to  ensure  unit  is  lifted  level  with  the

ground.

After the unit is placed on the roof curb or mounting pad, remove the top

skid. 

Step 5 – Select and Install Ductwork

The  design  and installation of the duct system  must be in  accordance

with the standards of the NFPA for installation of non-residence type air

conditioning  and  ventilating  systems,  NFPA  90A  or  residence-type,

NFPA 90B and/or local codes and ordinances. 
Select  and  size  ductwork,  supply-air  registers,  and  return  air  grilles

according  to ASHRAE  (American  Society  of  Heating,  Refrigeration,

and Air Conditioning Engineers) recommendations. 
The unit has duct flanges on the supply- and return-air openings on the

side of the unit. 

When designing and installing ductwork, consider the following: 

1. All units should have field-supplied filters or accessory filter rack

installed in the return-air side of the unit. Recommended sizes for

filters are shown in 

Table 1

. 

2. Avoid abrupt duct size increases and reductions. Abrupt change in

duct size adversely affects air performance. 

IMPORTANT: 

Use flexible connectors between ductwork and unit to

prevent transmission of vibration. Use suitable gaskets to ensure weather

tight  and  airtight  seal.  When  electric  heat  is  installed,  use  fireproof

canvas (or similar heat resistant material) connector between ductwork

and  unit  discharge  connection.  If  flexible  duct  is  used,  insert  a  sheet

metal sleeve inside duct. Heat resistant duct connector (or sheet metal

sleeve) must extend 24-in. (610 mm) from electric heater element. 

3. Size  ductwork  for  cooling  air  quantity  (cfm).  The  minimum  air

quantity  for  proper  electric  heater  operation  is  listed  in 

Table 2

.

Heater  limit  switches  may  trip  at  air  quantities  below  those

recommended. 

4. Seal,  insulate,  and  weatherproof  all  external  ductwork.  Seal,

insulate  and  cover  with  a  vapor  barrier  all  ductwork  passing

through  conditioned  spaces.  Follow  latest  Sheet  Metal  and  Air

Conditioning  Contractors  National  Association  (SMACNA)  and

Air  Conditioning  Contractors  Association  (ACCA)  minimum

installation  standards  for  residential  heating  and  air  conditioning

systems.

5. Secure  all  ducts  to  building  structure.  Flash,  weatherproof,  and

vibration-isolate  duct openings  in wall or roof according to good

construction practices. 

Configuring Units for Downflow (Vertical) Discharge

1. Open  all  electrical  disconnects  and  install  lockout  tag  before

starting any service work.

2. Remove  horizontal  (metal)  ductcovers  to  access  vertical

(downflow) discharge duct knockouts in unit basepan. (See 

Fig. 8

.)

3. To  remove  downflow  return  and  supply  knockout  covers,  break

front and right side connecting tabs with a screwdriver and hammer.

Push cover down to break rear and left side tabs.

A09061

A09088

Fig. 8 – Supply and Return Duct Opening

NOTE: 

These panels are held in place with tabs similar to an electrical

knockout. Reinstall horizontal duct covers (

Fig. 8

) shipped on unit from

factory. Insure openings are air and watertight.

NOTE: 

The  design  and  installation  of  the  duct  system  must  be  in

accordance  with  the  standards  of  the  NFPA  for  installation  of

nonresidence-type air conditioning and ventilating systems, NFPA 90A

or residence-type, NFPA 90B; and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the

duct system:

1. Units are shipped for side shot installation.
2. Select and size ductwork, supply-air registers, and return-air grilles

according  to American  Society  of  Heating,  Refrigeration  and Air

Conditioning Engineers (ASHRAE) recommendations.

3. Use flexible transition between rigid ductwork and unit to prevent

transmission of vibration. The transition may be screwed or bolted

WARNING

!

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury or death.

For  vertical  supply  and  return  units,  tools  or  parts  could  drop  into

ductwork. Install a 90 degree turn in the return ductwork between the

unit and the conditioned space. If a 90 degree elbow cannot be installed,

then  a  grille  of  sufficient  strength  and  density  should  be  installed  to

prevent  objects  from  falling  into  the  conditioned  space.  Units  with

electric heaters require 90 degree elbow in supply duct.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before  performing  service  or  maintenance  operations  on  the  system,

turn off main power to unit and install lockout tag. There may be more

than one disconnect switch.

Horizontal Duct Covers

Basepan
Downflow
(Vertical)
Supply
Knockout 

Basepan
Downflow 
(Vertical)
Return
Knockout 

Summary of Contents for WPH4 Series

Page 1: ...and Defrost Mode 24 Maintenance 27 Indoor Blower and Motor 27 Refrigerant 30 Compressor Oil 30 Servicing Systems on Roofs with Synthetic Materials 31 Liquid Line Filter Drier 31 R 410A Refrigerant Cha...

Page 2: ...on on older G series roof curbs Two accessory kits are available to aid in installing a new G series unit on an old G roof curb 1 Accessory kit number CPADCURB001A00 small chassis and accessory kit nu...

Page 3: ...partial overhang such as a normal house overhang is 48 in 1219 mm above the unit top The maximum horizontal extension of a partial overhang must not exceed 48 in 1219 mm IMPORTANT Do not restrict out...

Page 4: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A221484 Fig 2 PHD4 24 30 Unit D...

Page 5: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 A221486 Fig 3 WPH4 24 30 Unit D...

Page 6: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 A221485 Fig 4 PHD4 36 60 Unit D...

Page 7: ...s K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 7 A221487 Fig 5 WPH4 36 60 Unit D...

Page 8: ...4 Attach ductwork to curb flanges of duct rest on curb 5 Insulated panels 1 in 25 mm thick fiberglass 1 lb density UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm Part Number CPRCURB011B00...

Page 9: ...al use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Particular attention should be...

Page 10: ...ing Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to...

Page 11: ...n accessory or is field supplied Make sure that the outlet of the trap is at least 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tu...

Page 12: ...24 volt splice box See Fig 12 for connection diagram Run the low voltage leads from the thermostat through the control wiring inlet hole grommet see Fig 2 Fig 5 and into the low voltage splice box Pr...

Page 13: ...r Dual Accuraters Orifice ID in mm N A 0 080 1 2 03 1 N A Orifice OD in mm 0 032 2 0 81 2 0 035 2 0 89 2 0 040 2 1 02 2 0 046 2 1 17 2 0 046 2 1 17 2 0 046 2 1 17 2 Outdoor Coil Rows Fins in face area...

Page 14: ...ries K and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 14 A09098 Fig 13 Typical Insta...

Page 15: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 15 A221468 Fig 14 Connection Wiring Schem...

Page 16: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 16 A221469 Fig 15 Ladder Wiring Schemat...

Page 17: ...WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 17 A221470 Fig 16 Connection Wiring Schem...

Page 18: ...d WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 18 A221471 Fig 17 Ladder Wiring Schemat...

Page 19: ...nd WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A221472 Fig 18 Connection Wiring Di...

Page 20: ...and WPH4 Series K Installation Instruction Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A221473 Fig 19 Ladder Wiring Diag...

Page 21: ...temperature NOTE Once the compressor has started and then has stopped it should not be started again until 5 minutes have elapsed The defrost board has a built in 5 minute delay between cycles The 5 m...

Page 22: ...r than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments NO...

Page 23: ...able range for the speed tap to be used for dehumidification cooling 7 Use any spare vinyl plugs to cap any unused speed tap wires Single Speed Cooling With Higher Electric Heat Speed This unit can al...

Page 24: ...tive defrost cycles the control will lengthen the defrost interval by 15 minutes up to a maximum of 120 minutes or 30 minutes greater than the original setpoint whichever comes first If the previous d...

Page 25: ...0 41 0 41 High Black CFM 1505 1464 1423 1380 1336 1292 1242 1199 1145 1096 BHP 0 38 0 39 0 40 0 42 0 43 0 43 0 44 0 45 0 46 0 47 42 Low Blue CFM 956 899 843 786 729 676 621 558 504 435 BHP 0 13 0 13 0...

Page 26: ...4x24x1 406x610x25 356x610x25 3 0 3 5 4 0 0 09 0 09 0 10 0 12 0 13 0 15 0 17 0 17 0 19 0 21 1500 2200CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 8 Electr...

Page 27: ...slide assembly out Be careful not to tear insulation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscr...

Page 28: ...wet bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check...

Page 29: ...pect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 25 to locate all the electrical controls and wiring Check a...

Page 30: ...e interchanged The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor has no dynamic suction or discharge valves...

Page 31: ...polyethylene plastic drip cloth or tarp Cover an approximate 10x10 ft 3x3 m area 2 Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent ru...

Page 32: ...ng vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liquid leaving circuit of the left condenser coil see Fig 27 The thermostat closes at 32_F...

Page 33: ...nt line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace...

Page 34: ...LECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOU...

Reviews: