50TCQ

Packaged Heat Pump

3 to 12.5 Nominal Tons

Product Data

C08613

the environmentally sound refrigerant

Summary of Contents for WeatherMaker 50TCQ*07

Page 1: ...50TCQ Packaged Heat Pump 3 to 12 5 Nominal Tons Product Data C08613 the environmentally sound refrigerant ...

Page 2: ...989 Also our large control box gives you room to work and room to mount Carrier accessory controls Easy to maintain Easy access handles by Carrier provide quick and easy access to all normally serviced components Our no strip screw system has superior holding power and guides screws into position while preventing the screw from stripping the unit s metal Take accurate pressure readings by reading ...

Page 3: ...nce in many applications Belt drive motor optional S Provisions for bottom or side condensate drain S Capable of thru the base or thru the curb electrical routing S Dependable time temperature defrost logic provides a defrost cycle if needed every 30 60 90 or 120 minutes and is adjustable S Single point electrical connection S Sloped composite drain pan sheds water and won t rust S Standardized co...

Page 4: ...ectromechanical A None 1 PremierLink DDC controller B RA smoke detector 2 Open protocol DDC controller C SA smoke detector D RA SA smoke detector Design Rev E CO2 sensor Factory assigned F RA smoke detector CO2 G SA smoke detector CO2 Voltage H RA SA smoke detector CO2 1 575 3 60 3 208 230 1 60 Indoor Fan Options 5 208 230 3 60 0 Electric drive X13 5 speed torque motor 3 5 ton only 6 460 3 60 1 St...

Page 5: ...or Air Dampers EconoMi er IV for electro mechanical controlled RTUs X X EconoMi er2 for DDC controlled RTUs X X Motorized 2 position outdoor air damper X X Manual outdoor air damper 25 and 50 X Barometric relief1 X X Power exhaust X Economizer Sensors IAQ Devices Single dry bulb temperature sensors2 X X Differential dry bulb temperature sensors2 X Single enthalpy sensors2 X X Differential enthalpy...

Page 6: ... or un powered Lower service bills by including a convenience outlet in your specification Carrier will install this service feature at our factory powered Provides a convenient 15 amp 115V GFCI receptacle Non fused Disconnect This OSHA compliant factory installed safety switch allows a service technician to locally secure power to the rooftop Power Exhaust Pressure Relief Superior internal buildi...

Page 7: ...ur application A wide selection of motors and pulleys drives are available factory installed to handle nearly any application Thru the Base Connections Thru the base connections available as either an accessory or as a factory option are necessary to ensure proper connection and seal when routing wire and piping through the rooftop s basepan and curb These couplings eliminate roof penetration and ...

Page 8: ...500 2 25 96 000 3 30 D12 N A 62 300 2 25 116 000 3 40 D14 N A 76 000 2 05 142 000 3 20 LEGEND AHRI Air Conditioning Heating and Refrigeration Institute ASHRAE American Society of Heating Refrigerating and Air Conditioning Inc COP Coefficient of Performance EER Energy Efficiency Ratio HSPF Heating Seasonal Performance Factor IEER Integrated Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ra...

Page 9: ... 64 2 A06 80 92 7 84 9 79 0 76 7 73 8 69 6 66 4 62 8 A07 78 88 0 79 5 76 2 75 8 72 5 68 6 65 7 62 4 D08 82 89 7 81 5 80 5 79 2 77 1 73 2 70 2 67 4 D09 84 90 8 85 2 81 6 79 5 78 1 74 0 70 4 66 5 D12 87 88 1 90 0 85 9 83 0 81 6 78 5 76 4 75 5 D14 83 89 3 85 2 80 3 78 0 77 0 74 4 73 7 68 9 LEGEND dB Decibel NOTES 1 Outdoor sound data is measured in accordance with AHRI standard 270 95 2 Measurements ...

Page 10: ...00 1200 600 1200 600 1200 878 1192 Motor Frame Size 48 48 48 56 Fan Qty Type 1 Centrifugal 1 Centrifugal 1 Centrifugal 1 Centrifugal Fan Diameter x Length in 10 x 10 10 x 10 11 x 10 10 x 10 Medium Static 3 phase Motor Qty Drive Type 1 Belt 1 Belt 1 Belt 1 Belt Max BHP 1 5 1 5 2 0 2 9 RPM Range 819 1251 920 1303 1066 1380 1066 1380 Motor Frame Size 56 56 56 56 Fan Qty Type 1 Centrifugal 1 Centrifug...

Page 11: ...h in 15 x 15 15 x 15 15 x 15 18 x 18 High Static 3 phase Motor Qty Drive Type 1 Belt 1 Belt 1 Belt 1 Belt Max BHP 2 9 2 9 3 7 6 1 RPM Range 838 1084 838 1084 838 1084 792 971 Motor Frame Size 56 56 56 S184T Fan Qty Type 1 Centrifugal 1 Centrifugal 1 Centrifugal 1 Centrifugal Fan Diameter x Length in 15 x 15 15 x 15 15 x 15 18 x 18 High Static 3 phase High Eff Motor Qty Drive Type n a n a n a 1 Bel...

Page 12: ... 038A00 038A00 038A00 038A00 MED BD 101A00 4 4 3 3 4 0 102A00 6 5 4 9 6 0 103B00 8 7 6 5 8 0 037A00 037A00 037A00 104B00 10 5 7 9 9 6 037A00 037A00 037A00 038A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 HIGH BD 101A00 4 4 3 3 4 0 102A00 6 5 4 9 6 0 103B00 8 7 6 5 8 0 037A00 037A00 037A00 104B00 10 5 7 9 9 6 037A00 037A00 037A00 038A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 460 ...

Page 13: ...A00 6 5 4 9 6 0 103B00 8 7 6 5 8 0 037A00 037A00 037A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 104B00 104B00 21 0 15 8 19 3 039A00 039A00 039A00 039A00 HIGH BD 102A00 6 5 4 9 6 0 103B00 8 7 6 5 8 0 037A00 037A00 037A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 104B00 104B00 21 0 15 8 19 3 039A00 039A00 039A00 039A00 460 3 60 STD DD 106A00 6 0 5 5 108A00 11 5 10 6 109A00 14 0 12 ...

Page 14: ...104B00 104B00 21 0 15 8 19 3 039A00 039A00 039A00 039A00 104B00 105A00 26 5 19 9 24 3 039A00 039A00 039A00 039A00 HIGH BD 102A00 6 5 4 9 6 0 037A00 037A00 104B00 10 5 7 9 9 6 038A00 038A00 038A00 038A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 104B00 104B00 21 0 15 8 19 3 039A00 039A00 039A00 039A00 104B00 105A00 26 5 19 9 24 3 039A00 039A00 039A00 039A00 460 3 60 STD DD 106A00 6 0 5 5 10...

Page 15: ...039A00 039A00 HIGH 102A00 6 5 4 9 6 0 037A00 037A00 037A00 037A00 104B00 10 5 7 9 9 6 038A00 038A00 038A00 038A00 105A00 16 0 12 0 14 7 038A00 038A00 038A00 038A00 104B00 104B00 21 0 15 8 19 3 039A00 039A00 039A00 039A00 104B00 105A00 26 5 19 9 24 3 039A00 039A00 039A00 039A00 460 3 60 STD 106A00 6 0 5 5 108A00 11 5 10 6 109A00 14 0 12 9 108A00 108A00 23 0 21 1 037A00 037A00 037A00 037A00 108A00 1...

Page 16: ...A00 053A00 053A00 460 3 60 STD 116A00 13 9 12 8 047A00 047A00 047A00 047A00 113A00 16 5 15 2 047A00 047A00 047A00 047A00 114A00 27 8 25 5 047A00 050A00 050A00 050A00 115A00 33 0 30 3 050A00 050A00 050A00 050A00 114A00 116A00 41 7 38 3 052A00 052A00 052A00 052A00 MED 116A00 13 9 12 8 047A00 047A00 047A00 047A00 113A00 16 5 15 2 047A00 047A00 047A00 047A00 114A00 27 8 25 5 050A00 050A00 050A00 050A0...

Page 17: ...A00 053A00 053A00 460 3 60 STD 116A00 13 9 12 8 047A00 047A00 047A00 047A00 113A00 16 5 15 2 047A00 047A00 047A00 047A00 114A00 27 8 25 5 050A00 050A00 050A00 050A00 115A00 33 0 30 3 050A00 050A00 050A00 050A00 114A00 116A00 41 7 38 3 052A00 052A00 052A00 052A00 MED 116A00 13 9 12 8 047A00 047A00 047A00 047A00 113A00 16 5 15 2 047A00 047A00 047A00 047A00 114A00 27 8 25 5 050A00 050A00 050A00 050A0...

Page 18: ...3A00 16 5 15 2 047A00 047A00 047A00 047A00 115A00 33 0 30 3 050A00 050A00 050A00 050A00 114A00 116A00 41 7 38 3 052A00 052A00 052A00 052A00 115A00 113A00 50 0 45 9 052A00 052A00 052A00 052A00 MED 116A00 13 9 12 8 047A00 047A00 047A00 047A00 113A00 16 5 15 2 047A00 047A00 047A00 047A00 115A00 33 0 30 3 050A00 050A00 050A00 050A00 114A00 116A00 41 7 38 3 052A00 052A00 052A00 052A00 115A00 113A00 50 ...

Page 19: ...0 053A00 053A00 294A00 33 5 25 2 30 8 053A00 053A00 053A00 053A00 288A00 294A00 43 5 32 7 40 0 054A00 054A00 054A00 054A00 291A00 294A00 50 0 37 6 45 9 054A00 054A00 054A00 054A00 460 3 60 STD 292A00 16 5 15 2 047A00 047A00 047A00 047A00 289A00 292A00 26 5 24 3 050A00 050A00 050A00 050A00 295A00 33 5 30 8 050A00 050A00 050A00 050A00 289A00 295A00 43 5 40 0 052A00 052A00 052A00 052A00 292A00 295A00...

Page 20: ...0 050A00 050A00 050A00 290A00 296A00 43 5 40 0 052A00 052A00 052A00 052A00 293A00 296A00 50 0 45 9 052A00 052A00 052A00 052A00 HIGH 293A00 16 5 15 2 047A00 047A00 047A00 047A00 290A00 293A00 26 5 24 3 047A00 050A00 050A00 050A00 296A00 33 5 30 8 050A00 050A00 050A00 050A00 290A00 296A00 43 5 40 0 052A00 052A00 052A00 052A00 293A00 296A00 50 0 45 9 052A00 052A00 052A00 052A00 HIGH High Eff 293A00 1...

Page 21: ...21 WEIGHTS DIMENSIONS C09016 Fig 1 Dimensions 50TCQ 04 07 50TCQ ...

Page 22: ...B 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall 36 in 914 mm Surface behind servicer is electrically non conductive e g wood fiberglass Special Check for sources of flue products within 10 ft of unit fresh air intake hood C 36 in 914 mm Side condensate drain is used 18 in 457 mm Minimum clearance D 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall ...

Page 23: ...01 1 2 356 2 0 610 50TCQA04 07 NOTES 1 Roof curb accessory is shipped disassembled 2 Insulated panels 3 Dimensions in are in millimeters 4 Roof curb galvanized steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector package CRBTMPWR001A01 is for thru the curb type gas CRBTMPWR003A01 is for thru the base type gas connecti...

Page 24: ...24 WEIGHTS DIMENSIONS cont C08677B Fig 5 Dimensions 50TCQ 08 09 50TCQ ...

Page 25: ...25 WEIGHTS DIMENSIONS cont C10393 Fig 6 Dimensions 50TCQ 08 09 50TCQ ...

Page 26: ...B 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall 36 in 914 mm Surface behind servicer is electrically non conductive e g wood fiberglass Special Check for sources of flue products within 10 ft of unit fresh air intake hood C 36 in 914 mm Side condensate drain is used 18 in 457 mm Minimum clearance D 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall ...

Page 27: ...27 WEIGHTS DIMENSIONS cont C10369 Fig 9 Curb Dimensions 50TCQ 08 09 50TCQ ...

Page 28: ...28 WEIGHTS DIMENSIONS cont C09556A Fig 10 Dimensions 50TCQ 12 50TCQ ...

Page 29: ...29 WEIGHTS DIMENSIONS cont Horizontal Connections Economizer C10409 Fig 11 Dimensions 50TCQ 12 50TCQ ...

Page 30: ...B 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall 36 in 914 mm Surface behind servicer is electrically non conductive e g wood fiberglass Special Check for sources of flue products within 10 ft of unit fresh air intake hood C 36 in 914 mm Side condensate drain is used 18 in 457 mm Minimum clearance D 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall ...

Page 31: ...31 WEIGHTS DIMENSIONS cont C10370 Fig 14 Curb Dimensions 50TCQ 12 50TCQ ...

Page 32: ...32 WEIGHTS DIMENSIONS cont C09895A Fig 15 Dimensions 50TCQ 14 50TCQ ...

Page 33: ...33 WEIGHTS DIMENSIONS cont C09895A Fig 16 Dimensions 50TCQ 14 50TCQ ...

Page 34: ...B 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall 36 in 914 mm Surface behind servicer is electrically non conductive e g wood fiberglass Special Check for sources of flue products within 10 ft of unit fresh air intake hood C 36 in 914 mm Side condensate drain is used 18 in 457 mm Minimum clearance D 42 in 1067 mm Surface behind servicer is grounded e g metal masonry wall ...

Page 35: ...35 WEIGHTS DIMENSIONS cont C10251 Fig 19 Curb Dimensions 50TCQ 14 50TCQ ...

Page 36: ...2 115 52 115 52 143 65 143 65 143 65 180 82 Roof Curb 24 in curb 197 89 197 89 197 89 197 89 245 111 245 111 245 111 235 107 CO2 sensor 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 Electric Heater 30 14 30 14 30 14 30 14 45 20 45 20 45 20 25 11 Single Point Kit 10 5 10 5 10 5 10 5 12 5 12 5 12 5 25 11 Optional Indoor Motor Drive 10 5 10 5 10 5 10 5 15 7 15 7 15 7 45 20 Motormaster Controller 35 16 35 16 35 16 ...

Page 37: ...e There is no need for extra safety factors as Carrier s motors are designed and rigorously tested to use the entire listed BHP range without either nuisance tripping or premature motor failure Sizing a rooftop Bigger isn t necessarily better While an air conditioner needs to have enough capacity to meet the load it doesn t need excess capacity In fact having excess capacity typically results in v...

Page 38: ... additional electric heat capacity in kW 20 700 Btuh 6 1 kW of heat required 3413 Btuh kW Enter the Electric Heating Capacities table for 50TCQA07 at 208 230 3 phase The 6 5 kW heater at 230V most closely satisfies the heating required 6 5 kW x 3413 22 185 Btuh Total unit heating capacity is 46 485 Btuh 22 185 24 300 VI Calculate RTU Latent Heat Capacity LC TC SHC LC 69 0 MBH 50 7 MBH 18 3 MBH VII...

Page 39: ...29 0 34 3 67 THC 40 4 40 4 40 4 37 8 37 8 37 8 34 7 34 7 34 7 31 4 31 4 32 6 SHC 23 6 30 0 36 4 22 5 28 9 35 3 21 3 27 6 34 0 19 9 26 3 32 6 72 THC 44 1 44 1 44 1 42 0 42 0 42 0 39 2 39 2 39 2 36 0 36 0 36 0 SHC 17 7 23 9 30 2 16 9 23 3 29 6 15 9 22 3 28 6 14 7 21 1 27 5 76 THC 46 6 46 6 44 4 44 4 42 3 42 3 39 4 39 4 SHC 19 0 25 5 18 3 24 7 17 6 24 0 16 6 23 1 1350 Cfm EAT wb 58 THC 37 5 37 5 42 6...

Page 40: ...39 6 46 8 67 THC 51 2 51 2 51 2 48 7 48 7 48 7 45 9 45 9 45 9 42 8 42 8 42 8 SHC 31 1 38 0 45 0 30 1 37 1 44 0 28 9 35 9 43 0 27 5 34 7 42 0 72 THC 55 3 55 3 55 3 52 9 52 9 52 9 50 0 50 0 50 0 46 9 46 9 46 9 SHC 23 2 30 1 37 1 22 3 29 3 36 3 21 2 28 3 35 4 19 9 27 1 34 4 76 THC 57 8 57 8 55 4 55 4 52 6 52 6 49 3 49 3 SHC 23 9 30 8 23 1 30 1 22 1 29 2 20 9 28 2 1800 Cfm EAT wb 58 THC 47 7 47 7 55 5...

Page 41: ... 48 8 57 9 67 THC 65 1 65 1 65 1 61 3 61 3 61 3 56 9 56 9 56 9 52 2 52 2 52 8 SHC 40 2 48 9 57 6 38 6 47 3 56 1 36 7 45 6 54 5 34 6 43 7 52 8 72 THC 71 3 71 3 71 3 67 3 67 3 67 3 62 8 62 8 62 8 57 8 57 8 57 8 SHC 29 9 38 6 47 3 28 3 37 1 45 9 26 5 35 5 44 4 24 5 33 6 42 7 76 THC 75 9 75 9 71 7 71 7 66 6 66 6 61 2 61 2 SHC 30 2 38 9 28 7 37 6 27 0 36 0 25 1 34 3 2250 Cfm EAT wb 58 THC 61 0 61 0 70 ...

Page 42: ...4 57 3 68 3 67 THC 74 3 74 3 74 3 70 4 70 4 70 4 66 1 66 1 66 1 61 4 61 4 61 7 SHC 45 3 55 7 66 1 43 7 54 2 64 7 41 9 52 6 63 3 39 9 50 8 61 7 72 THC 80 4 80 4 80 4 76 6 76 6 76 6 72 1 72 1 72 1 67 1 67 1 67 1 SHC 32 6 43 0 53 4 31 2 41 7 52 3 29 3 40 1 50 8 27 2 38 2 49 2 76 THC 84 0 84 0 80 7 80 7 76 0 76 0 70 4 70 4 SHC 32 6 43 1 31 6 42 2 30 0 40 8 28 1 39 1 2700 Cfm EAT wb 58 THC 69 7 69 7 81...

Page 43: ...THC 95 5 95 5 95 5 90 5 90 5 90 5 85 1 85 1 85 1 79 0 79 0 79 6 SHC 56 1 71 2 86 2 54 1 69 2 84 2 51 9 67 0 82 1 49 5 64 6 79 6 72 THC 103 8 103 8 103 8 98 8 98 8 98 8 93 4 93 4 93 4 87 5 87 5 87 5 SHC 41 8 56 7 71 6 39 9 54 8 69 8 37 9 52 9 67 8 35 8 50 7 65 7 76 THC 109 1 109 1 104 0 104 0 98 3 98 3 92 2 92 2 SHC 44 9 60 6 43 1 58 6 41 1 56 4 39 0 54 2 3375 Cfm EAT wb 58 THC 88 9 88 9 100 9 84 9...

Page 44: ...1 105 5 105 5 105 5 98 4 98 4 98 4 90 8 90 8 94 2 SHC 67 7 85 3 102 9 65 1 82 7 100 2 62 2 79 8 97 3 59 2 76 7 94 2 72 THC 123 0 123 0 123 0 116 5 116 5 116 5 109 4 109 4 109 4 101 6 101 6 101 6 SHC 50 5 68 2 85 9 48 2 65 8 83 5 45 6 63 2 80 8 42 8 60 4 78 1 76 THC 131 5 131 5 124 9 124 9 117 7 117 7 109 9 109 9 SHC 54 1 72 1 51 8 69 7 49 4 67 2 46 8 64 6 3825 Cfm EAT wb 58 THC 104 5 104 5 118 0 9...

Page 45: ...31 3 73 6 99 6 125 5 66 4 92 3 118 3 67 THC 125 4 125 4 125 4 118 2 118 2 118 2 109 5 109 5 111 2 99 1 99 1 107 7 SHC 64 5 90 5 116 4 62 2 88 1 114 1 59 3 85 3 111 2 55 8 81 8 107 7 72 THC 137 2 137 2 137 2 130 7 130 7 130 7 122 8 122 8 122 8 113 5 113 5 113 5 SHC 43 6 69 6 95 5 41 7 67 6 93 6 39 2 65 1 91 1 36 3 62 2 88 2 76 THC 146 3 146 3 139 9 139 9 132 5 132 5 SHC 52 8 78 7 50 8 76 8 48 6 74 ...

Page 46: ...137 6 67 THC 156 6 156 6 156 6 148 8 148 8 148 8 138 1 138 1 138 1 126 3 126 3 130 2 SHC 91 7 115 6 139 5 89 3 113 9 138 6 85 3 110 2 135 0 80 6 105 4 130 2 72 THC 167 0 167 0 167 0 160 5 160 5 160 5 153 3 153 3 153 3 142 9 142 9 142 9 SHC 67 3 90 6 113 9 64 9 88 6 112 2 62 5 87 0 111 4 58 9 83 7 108 5 76 THC 174 6 174 6 167 5 167 5 160 7 160 7 152 9 152 9 SHC 72 2 98 1 69 8 95 6 67 4 92 9 64 8 90...

Page 47: ...f frost on the outdoor coil and the heat required to defrost RH Relative Humidity db Dry Bulb Table 17 HEATING CAPACITIES 4 TONS 50TCQA05 RETURN AIR F db CFM STANDARD AIR TEMPERATURE AIR ENTERING OUTDOOR COIL F db AT 70 RH 10 0 10 17 30 40 47 50 60 55 1200 Capacity 17 5 22 0 26 6 30 0 36 8 42 6 47 1 48 9 55 3 Int Cap 16 2 20 2 24 4 27 3 32 2 42 6 47 1 48 9 55 3 1600 Capacity 17 5 22 1 26 7 30 2 37...

Page 48: ...ects of frost on the outdoor coil and the heat required to defrost RH Relative Humidity db Dry Bulb Table 19 HEATING CAPACITY 6 TONS 50TCQ07 RETURN AIR F DB CFM STANDARD AIR TEMPERATURE AIR ENTERING OUTDOOR COIL F db AT 70 RH 10 0 10 17 30 40 47 50 60 55 1800 Capacity 22 4 29 8 37 1 42 5 53 5 62 4 68 6 71 2 80 3 Int Cap 20 7 27 4 34 1 38 8 46 9 62 4 68 6 71 2 80 3 2400 Capacity 24 6 32 1 39 6 45 1...

Page 49: ...the heat required to defrost RH Relative Humidity dD Dry Bulb Table 21 HEATING CAPACITY 8 5 TONS 50TCQD09 RETURN AIR F db CFM STANDARD AIR TEMPERATURE AIR ENTERING OUTDOOR COIL F db AT 70 RH 10 0 10 17 30 40 47 50 60 55 2550 Capacity 33 1 42 7 52 7 60 0 75 6 87 4 97 5 100 6 113 8 Int Cap 30 7 39 3 48 3 54 7 66 2 87 4 97 5 100 6 113 8 3400 Capacity 34 4 44 0 54 2 61 8 77 5 89 9 100 2 103 1 115 7 In...

Page 50: ...f frost on the outdoor coil and the heat required to defrost RH Relative Humidity db Dry Bulb Table 23 HEATING CAPACITY 12 5 TONS 50TCQD14 RETURN AIR F dB CFM STANDARD AIR TEMPERATURE AIR ENTERING OUTDOOR COIL F db AT 70 RH 10 0 10 17 30 40 47 50 60 55 3750 Capacity 33 7 47 5 69 8 83 1 109 3 131 7 149 7 155 6 180 1 Int Cap 31 2 43 7 64 0 75 8 95 8 131 7 149 7 155 6 180 1 5000 Capacity 35 7 49 7 72...

Page 51: ...ater Module 0 03 0 05 0 07 0 09 0 09 0 10 0 11 0 11 0 12 0 13 2 Electric Heater Modules 0 13 0 15 0 16 0 16 0 16 0 17 0 17 0 17 0 18 0 18 7 5 10 TONS CFM in wg 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000 1 Electric Heater Module 0 03 0 04 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 18 2 Electric Heater Modules 0 04 0 05 0 05 0 06 0 07 0 08...

Page 52: ...UCT STATIC PRESSURE DROP in wg C09881 Fig 21 Return Air Pressure Drop 0 500 1000 1500 2000 2500 0 0 05 0 1 0 15 0 2 0 25 0 3 3 6 Ton 7 5 10 Ton VERTICAL ECONOMIZERS RELIEF FLOW CFM RETURN DUCT STATIC PRESSURE in wg C09883 Fig 22 Barometric Relief Flow Capacity 0 1000 2000 3000 4000 5000 6000 0 0 1 0 2 0 3 0 4 3 6 Ton 7 5 10 Ton VERTICAL ECONOMIZERS RETURN AIR FLOW CFM RETURN DUCT STATIC PRESSURE D...

Page 53: ...c pressure losses as shown in the above tables Selection software is available through your salesperson to help you select the best motor drive combination for your application 4 The Fan Performance tables offer motor drive recommendations In cases when two motor drive combinations would work Carrier recommended the lower horsepower option 5 For information on the electrical properties of Carrier ...

Page 54: ...1 18 0 52 975 1 14 0 54 1050 1 10 0 56 1125 1 06 0 58 1200 1 02 0 60 1275 0 98 0 63 1350 0 94 0 65 1425 0 90 0 68 1500 0 87 0 71 Table 26 50TCQA04 ELECTRIC DRIVE X13 MOTOR 3 TON VERTICAL SUPPLY SPEED TORQUE TAP CFM ESP BHP 1 900 0 44 0 22 975 0 35 0 21 1050 0 24 0 20 1125 0 15 0 19 1200 0 08 0 19 1275 0 02 0 18 1350 1425 1500 2 900 0 64 0 30 975 0 53 0 29 1050 0 42 0 28 1125 0 32 0 27 1200 0 24 0 ...

Page 55: ... 1 02 0 60 1300 0 97 0 64 1400 0 92 0 67 1500 0 87 0 71 1600 0 82 0 75 1700 0 77 0 79 1800 0 71 0 84 1900 0 65 0 88 2000 0 58 0 92 Table 28 50TCQA05 ELECTRIC DRIVE X13 MOTOR 4 TON VERTICAL SUPPLY SPEED TORQUE TAP CFM ESP BHP 1 1200 0 50 0 39 1300 0 36 0 37 1400 0 19 0 35 1500 0 10 0 33 1600 0 02 0 32 1700 1800 1900 2000 2 1200 0 80 0 55 1300 0 69 0 55 1400 0 50 0 54 1500 0 38 0 52 1600 0 24 0 50 1...

Page 56: ... 1 49 0 90 1625 1 38 0 95 1750 1 28 1 00 1875 1 18 1 05 2000 1 11 1 09 2125 0 97 1 11 2250 0 72 1 07 2375 0 47 1 02 2500 0 20 0 96 Table 30 50TCQA06 ELECTRIC DRIVE X13 MOTOR 5 TON VERTICAL SUPPLY SPEED TORQUE TAP CFM ESP BHP 1 1500 1 00 0 70 1625 0 72 0 65 1750 0 46 0 60 1875 0 28 0 55 2000 0 14 0 51 2125 0 00 0 52 2250 2375 2500 2 1500 1 18 0 88 1625 1 00 0 90 1750 0 75 0 87 1875 0 51 0 83 2000 0...

Page 57: ... High static 1035 1466 RPM Max BHP 2 0 Table 32 50TCQA04 3 TON VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 900 594 0 15 740 0 25 867 0 37 981 0 52 1084 0 68 975 618 0 17 758 0 28 881 0 40 991 0 55 1092 0 71 1050 642 0 19 777 0 30 896 0 43 1003 0 58 1102 0 75 1125 668 0 22 797 0 34 912 0 47 1017 0 62 1113 0 79 1200 695 0 2...

Page 58: ...indicates field supplied drive Recommend using field supplied fan pulley part no KR11AD561 motor pulley part no KR11HY181 and belt part no KR29AF041 Table 34 50TCQA05 4 TON VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1200 695 0 25 818 0 37 930 0 51 1032 0 66 1126 0 83 1300 731 0 30 849 0 43 955 0 57 1053 0 72 1145 0 89 14...

Page 59: ...427 2 24 1487 2 47 1543 2 70 1597 2 94 1649 3 18 Med static 1066 1380 RPM Max BHP 2 0 High static 1208 1639 RPM Max BHP 2 9 Table 36 50TCQA06 5 TON VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1500 794 0 41 902 0 55 993 0 69 1074 0 85 1147 1 00 1625 840 0 49 945 0 64 1034 0 80 1113 0 96 1185 1 13 1750 888 0 59 988 0 75 107...

Page 60: ...12 1638 3 37 3000 1571 3 18 1626 3 44 1680 3 70 Std static 878 1192 RPM Max BHP 1 5 Med static 1066 1380 RPM Max BHP 2 9 High static 1208 1639 RPM Max BHP 2 9 Table 38 50TCQA07 6 TON VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1800 907 0 63 1006 0 80 1092 0 97 1169 1 14 1239 1 32 1950 965 0 77 1060 0 95 1143 1 13 1218 1 3...

Page 61: ...4 2 80 Std static 460 652 RPM Max BHP 1 2 Med static 591 838 RPM Max BHP 2 9 High static 838 1084 RPM Max BHP 2 9 Table 40 50TCQD08 7 5 TON VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2250 447 0 31 528 0 43 597 0 54 658 0 66 713 0 78 2438 470 0 37 548 0 50 615 0 62 675 0 75 729 0 88 2625 494 0 45 569 0 58 634 0 71 692 0 8...

Page 62: ...7 3 45 Std static 460 652 RPM Max BHP 1 2 Med static 591 838 RPM Max BHP 2 9 High static 838 1084 RPM Max BHP 2 9 Table 42 50TCQD09 8 5 VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2550 495 0 43 570 0 56 634 0 70 693 0 83 746 0 96 2763 524 0 53 595 0 67 657 0 81 714 0 95 766 1 09 2975 552 0 63 620 0 79 681 0 94 736 1 09 78...

Page 63: ...156 4 55 Std static 591 839 RPM Max BHP 2 4 Med static 733 949 RPM Max BHP 2 9 High static 838 1084 RPM Max BHP 3 7 Table 44 50TCQD12 10 VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3000 556 0 65 623 0 80 684 0 95 738 1 11 789 1 26 3250 590 0 79 655 0 96 713 1 13 766 1 29 815 1 46 3500 625 0 96 687 1 14 742 1 32 794 1 50 8...

Page 64: ...motor pulley 684 864 Table 46 50TCQD14 12 5 VERTICAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE IN WG 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3750 441 0 65 513 0 88 582 1 15 647 1 45 707 1 78 4063 466 0 78 533 1 03 598 1 30 660 1 61 718 1 95 4375 491 0 94 554 1 19 615 1 48 674 1 80 730 2 14 4688 517 1 11 576 1 38 634 1 68 690 2 00 744 2 36 5000 543 1 31 599 1 59 653 1 90 706...

Page 65: ... 1251 1208 08 3 phase Standard Static 652 633 614 594 575 556 537 518 498 479 460 Medium Static 838 813 789 764 739 715 690 665 640 616 591 High Static 1084 1059 1035 1010 986 961 936 912 887 863 838 09 3 phase Standard Static 652 633 614 594 575 556 537 518 498 479 460 Medium Static 838 813 789 764 739 715 690 665 640 616 591 High Static 1084 1059 1035 1010 986 961 936 912 887 863 838 12 3 phase ...

Page 66: ...87 253 21 8 117 325 1 5 DD STD 84 7 4 230 1 60 187 253 21 8 117 325 1 5 DD STD 84 7 4 208 3 60 187 253 13 7 83 325 1 5 DD STD 84 7 4 MED 80 5 2 HIGH 80 5 2 230 3 60 187 253 13 7 83 325 1 5 DD STD 84 7 4 MED 80 5 2 HIGH 80 5 2 460 3 60 414 506 6 2 41 325 0 8 DD STD 84 7 6 MED 80 2 6 HIGH 80 2 6 575 3 60 518 633 4 8 37 325 0 6 DD STD 84 4 0 MED 80 2 4 HIGH 80 2 0 Table 50 50TCQA06 1 Stage Cooling 5 ...

Page 67: ...l Load FLA MIN MAX 208 3 60 187 253 13 1 83 13 1 83 325 1 5 STD 80 5 2 MED 81 7 5 HIGH 81 7 5 230 3 60 187 253 13 1 83 13 1 83 325 1 5 STD 80 5 2 MED 81 7 5 HIGH 81 7 5 460 3 60 414 506 6 1 41 6 1 41 325 0 8 STD 80 2 6 MED 81 3 4 HIGH 81 3 4 575 3 60 518 633 4 4 33 4 4 33 325 0 6 STD 80 2 4 MED 81 2 8 HIGH 81 2 8 Table 53 50TCQD09 2 Stage Cooling 8 5 TONS V Ph Hz VOLTAGE RANGE COMP Cir 1 COMP Cir ...

Page 68: ...8 633 5 8 39 5 7 39 800 2 5 STD 80 2 MED 80 2 8 HIGH 81 5 6 Table 55 50TCQD14 2 Stage Cooling 12 5 TONS V Ph Hz VOLTAGE RANGE COMP Cir 1 COMP Cir 2 OFM ea IFM RLA LRA RLA LRA WATTS FLA TYPE EFF at Full Load FLA MIN MAX 208 3 60 187 253 22 4 149 22 4 149 325 1 5 STD 80 7 5 MED 80 7 5 HIGH 84 17 0 HIGH High Eff 89 5 20 4 230 3 60 187 253 22 4 149 22 4 149 325 1 5 STD 80 7 5 MED 80 7 5 HIGH 88 15 0 H...

Page 69: ...51 142 145 51 9 56 1 60 60 50 53 144 147 12 0 16 0 33 4 38 5 64 4 70 7 70 80 61 66 153 159 66 3 72 6 70 80 63 69 155 161 460 3 60 DD STD 16 0 20 16 53 17 0 20 17 54 6 0 7 2 25 0 30 24 60 26 0 30 26 61 8 8 10 6 29 3 30 28 64 30 3 35 30 65 11 5 13 8 33 3 35 32 67 34 3 35 33 68 14 0 16 8 37 0 40 36 70 38 0 40 37 71 MED 10 6 15 10 54 11 6 15 12 55 6 0 7 2 19 6 20 19 61 20 6 25 20 62 8 8 10 6 23 9 25 2...

Page 70: ...50 39 41 120 122 42 7 45 2 50 50 41 44 122 124 6 5 8 7 18 1 20 9 46 5 50 0 50 50 44 47 124 127 48 4 51 9 50 60 46 50 126 129 12 0 16 0 33 4 38 5 65 6 72 0 70 80 62 68 139 145 67 5 73 9 70 80 64 70 141 147 15 8 21 0 43 8 50 5 78 6 87 0 80 90 74 82 194 207 80 5 88 9 90 90 76 84 196 209 HIGH 23 8 30 23 117 25 7 30 26 119 4 9 6 5 13 6 15 6 40 8 43 3 50 50 39 41 131 133 42 7 45 2 50 50 41 44 133 135 6 ...

Page 71: ... 7 60 60 53 57 168 171 12 0 16 0 33 4 38 5 68 0 74 3 70 80 64 70 177 183 69 9 76 2 70 80 66 72 179 185 15 8 21 0 43 8 50 5 81 0 89 3 90 90 76 84 232 245 82 9 91 2 90 100 78 86 234 247 19 9 26 5 55 2 63 8 95 2 106 0 100 110 89 99 254 272 97 1 107 9 100 110 91 101 256 274 HIGH 28 5 40 28 170 30 4 45 30 172 4 9 6 5 13 6 15 6 45 5 48 0 50 50 44 46 184 186 47 4 49 9 50 60 46 48 186 188 7 9 10 5 21 9 25...

Page 72: ...14 4 110 125 98 108 295 313 HIGH 32 8 50 32 183 34 7 50 34 185 4 9 6 5 13 6 15 6 49 8 52 3 60 60 48 50 197 199 51 7 54 2 60 60 50 52 199 201 7 9 10 5 21 9 25 3 60 1 64 4 70 70 57 61 205 208 62 0 66 3 70 70 60 63 207 210 12 0 16 0 33 4 38 5 74 5 80 9 80 90 71 76 216 222 76 4 82 8 80 90 73 79 218 224 15 8 21 0 43 8 50 5 87 5 95 9 90 100 83 90 271 284 89 4 97 8 90 100 85 92 273 286 19 9 26 5 55 2 63 ...

Page 73: ...9 75 0 80 80 72 75 256 259 12 0 16 0 33 4 38 5 81 7 88 1 90 90 81 86 263 269 85 5 91 9 90 100 85 91 267 273 18 6 24 8 51 7 59 7 104 6 114 6 110 125 102 111 282 290 108 4 118 4 110 125 106 115 286 294 24 0 32 0 66 7 77 0 123 4 136 2 125 150 119 131 297 307 127 2 140 0 150 150 123 135 301 311 31 8 42 4 88 4 102 0 150 5 167 5 175 175 144 160 407 434 154 3 171 3 175 175 148 164 411 438 460 3 60 STD 17...

Page 74: ...79 3 80 80 76 79 264 267 12 0 16 0 33 4 38 5 86 0 92 3 90 100 85 91 271 277 89 8 96 1 90 100 89 95 275 281 18 6 24 8 51 7 59 7 108 8 118 8 110 125 106 115 290 298 112 6 122 6 125 125 110 119 294 302 24 0 32 0 66 7 77 0 127 6 140 5 150 150 123 135 305 315 131 4 144 3 150 150 127 139 309 319 31 8 42 4 88 4 102 0 154 7 171 7 175 175 148 164 415 442 158 5 175 5 175 200 152 168 419 446 460 3 60 STD 19 ...

Page 75: ... 99 105 367 373 102 2 108 6 110 110 103 109 371 377 24 0 32 0 66 7 77 0 140 1 152 9 150 175 137 149 401 411 143 9 156 7 150 175 142 154 405 415 31 8 42 4 88 4 102 0 167 2 184 2 175 200 162 178 511 538 171 0 188 0 175 200 167 182 515 542 37 6 50 0 104 2 120 3 186 9 177 0 200 200 180 199 542 575 190 7 180 8 200 200 185 203 546 579 460 3 60 STD 23 0 30 24 135 24 8 30 26 137 13 9 16 7 43 9 45 43 152 4...

Page 76: ...5 175 175 161 171 468 479 32 7 43 5 90 7 104 7 185 3 200 8 200 225 181 194 575 603 189 1 204 6 200 225 185 199 579 607 37 6 50 0 104 3 120 3 202 3 190 2 225 200 196 212 603 635 206 1 194 0 225 200 200 217 607 639 HIGH High Eff 75 3 90 80 402 79 1 100 85 406 12 4 16 5 34 4 39 7 118 3 124 9 125 125 120 126 436 442 122 1 128 7 125 150 124 130 440 446 19 9 26 5 55 3 63 8 144 4 155 1 150 175 144 154 51...

Page 77: ...40 0 16 5 15 9 43 9 45 43 152 47 7 50 48 156 26 5 25 5 55 9 60 55 187 59 7 60 59 191 33 5 32 2 64 3 70 62 168 68 1 70 67 172 43 5 41 8 76 3 80 73 220 80 1 90 78 224 50 0 48 1 72 1 80 81 232 75 9 80 85 236 HIGH 27 3 30 0 29 0 139 0 31 1 35 0 33 0 143 0 16 5 15 9 47 2 50 47 155 51 0 60 52 159 26 5 25 5 59 2 60 58 190 63 0 70 63 194 33 5 32 2 67 6 70 66 171 71 4 80 70 175 43 5 41 8 79 6 80 77 223 83 ...

Page 78: ...3 6 15 6 44 4 46 9 50 50 43 46 128 130 46 3 48 8 50 50 46 48 130 132 6 5 8 7 18 1 20 9 50 0 53 5 60 60 49 52 132 135 51 9 55 4 60 60 51 54 134 137 7 9 10 5 21 9 25 3 54 8 59 0 60 60 53 57 136 139 56 7 60 9 60 70 55 59 138 141 12 0 16 0 33 4 38 5 69 2 75 5 70 80 66 72 147 153 71 1 77 4 80 80 68 74 149 155 HIGH 27 4 40 28 125 29 3 40 30 127 3 3 4 4 9 2 10 6 38 9 40 7 45 50 38 40 134 136 40 8 42 6 50...

Page 79: ...27 47 5 50 0 50 60 47 49 127 129 6 5 8 7 18 1 20 9 51 3 54 8 60 60 50 53 129 132 53 2 56 7 60 60 52 55 131 134 12 0 16 0 33 4 38 5 70 4 76 8 80 80 67 73 144 150 72 3 78 7 80 80 70 75 146 152 15 8 21 0 43 8 50 5 83 4 91 8 90 100 79 87 199 212 85 3 93 7 90 100 82 89 201 214 HIGH 28 6 40 29 122 30 5 40 31 124 4 9 6 5 13 6 15 6 45 6 48 1 50 50 45 47 136 138 47 5 50 0 50 60 47 49 138 140 6 5 8 7 18 1 2...

Page 80: ...2 173 176 12 0 16 0 33 4 38 5 72 8 79 1 80 80 70 75 182 188 74 7 81 0 80 90 72 78 184 190 15 8 21 0 43 8 50 5 85 8 94 1 90 100 82 89 237 250 87 7 96 0 90 100 84 91 239 252 19 9 26 5 55 2 63 8 100 0 110 8 100 125 95 105 259 277 101 9 112 7 110 125 97 107 261 279 HIGH 33 3 45 34 175 35 2 50 36 177 4 9 6 5 13 6 15 6 50 3 52 8 60 60 49 52 189 191 52 2 54 7 60 60 52 54 191 193 7 9 10 5 21 9 25 3 60 7 6...

Page 81: ... 125 103 113 300 318 HIGH 37 6 50 38 188 39 5 50 40 190 4 9 6 5 13 6 15 6 54 6 57 1 60 60 53 56 202 204 56 5 59 0 60 60 56 58 204 206 7 9 10 5 21 9 25 3 64 9 69 2 70 80 63 67 210 213 66 8 71 1 80 80 65 69 212 215 12 0 16 0 33 4 38 5 79 3 85 7 80 90 76 82 221 227 81 2 87 6 90 90 78 84 223 229 15 8 21 0 43 8 50 5 92 3 100 7 100 110 88 96 276 289 94 2 102 6 100 110 90 98 278 291 19 9 26 5 55 2 63 8 1...

Page 82: ...80 80 77 81 261 264 12 0 16 0 33 4 38 5 86 5 92 9 90 100 86 92 268 274 90 3 96 7 100 100 91 96 272 278 18 6 24 8 51 7 59 7 109 4 119 4 110 125 107 116 287 295 113 2 123 2 125 125 112 121 291 299 24 0 32 0 66 7 77 0 128 2 141 0 150 150 124 136 302 312 132 0 144 8 150 150 129 141 306 316 31 8 42 4 88 4 102 0 155 3 172 3 175 175 149 165 412 439 159 1 176 1 175 200 154 169 416 443 460 3 60 STD 20 1 25...

Page 83: ...90 81 85 269 272 12 0 16 0 33 4 38 5 90 8 97 1 100 100 90 96 276 282 94 6 100 9 100 110 95 100 280 286 18 6 24 8 51 7 59 7 113 6 123 6 125 125 111 120 295 303 117 4 127 4 125 150 116 125 299 307 24 0 32 0 66 7 77 0 132 4 145 3 150 150 128 140 310 320 136 2 149 1 150 150 133 145 314 324 31 8 42 4 88 4 102 0 159 5 176 5 175 200 153 169 420 447 163 3 180 3 175 200 158 173 424 451 460 3 60 STD 21 4 25...

Page 84: ...5 110 372 378 107 0 113 4 110 125 109 115 376 382 24 0 32 0 66 7 77 0 144 9 157 7 150 175 143 155 406 416 148 7 161 5 150 175 147 159 410 420 31 8 42 4 88 4 102 0 172 0 189 0 175 200 168 183 516 543 175 8 192 8 200 200 172 188 520 547 37 6 50 0 104 2 120 3 191 7 181 8 200 200 186 204 547 580 195 5 185 6 200 200 190 209 551 584 460 3 60 STD 25 2 30 27 137 27 0 30 29 139 13 9 16 7 46 1 50 46 154 47 ...

Page 85: ...200 167 177 473 484 32 7 43 5 90 7 104 7 190 1 205 6 200 225 186 200 580 608 193 9 209 4 200 225 190 204 584 612 37 6 50 0 104 3 120 3 207 1 195 0 225 225 202 218 608 640 210 9 198 8 225 225 206 222 612 644 HIGH High Eff 80 1 100 86 407 83 9 100 90 411 12 4 16 5 34 4 39 7 123 1 129 7 125 150 125 131 441 447 126 9 133 5 150 150 130 136 445 451 19 9 26 5 55 3 63 8 149 2 159 9 150 175 149 159 518 535...

Page 86: ...45 6 50 45 154 49 4 50 50 158 26 5 25 5 57 6 60 56 189 61 4 70 61 193 33 5 32 2 66 0 70 64 170 69 8 70 69 174 43 5 41 8 78 0 80 75 222 81 8 90 80 226 50 0 48 1 73 8 80 82 234 77 6 80 87 238 HIGH 29 0 35 0 31 0 141 0 32 8 40 0 35 0 145 0 16 5 15 9 48 9 50 49 157 52 7 60 54 161 26 5 25 5 60 9 70 60 192 64 7 70 65 196 33 5 32 2 69 3 70 68 173 73 1 80 72 177 43 5 41 8 81 3 90 79 225 85 1 90 83 229 50 ...

Page 87: ...87 TYPICAL WIRING DIAGRAMS C09063 Fig 28 1 Stage Cooling Typical Power Diagram 50TCQ ...

Page 88: ...88 TYPICAL WIRING DIAGRAMS cont C09065 Fig 29 2 Stage Cooling Typical Power Diagram 50TCQ ...

Page 89: ...89 TYPICAL WIRING DIAGRAMS cont C09066 Fig 30 PremierLink Option Diagram 50TCQ ...

Page 90: ...90 TYPICAL WIRING DIAGRAMS cont C09067 Fig 31 Multi Protocol Option Diagram 50TCQ ...

Page 91: ...91 C09062 Fig 32 1 Stage Typical Wiring Diagram 50TCQ ...

Page 92: ...92 C09064 Fig 33 2 Stage Typical Wiring Diagram 50TCQ ...

Page 93: ...tage 2 heating W2 closes Terminal W2 is energized Defrost Board issues an output at EHEAT Heater contactor 1 and heater contactor 2 if installed are energized all electric heaters are energized When space heating load is partially satisfied thermostat terminal W2 is de energized heater contactors are de energized and all electric heat is terminated Stage 1 heating continues When the space heating ...

Page 94: ...fans will be energized and de energized If field installed accessory CO2 sensors are connected to the PremierLink control a PID controlled demand ventilation strategy will begin to operate As the CO2 level in the zone increases above the CO2 setpoint the minimum position of the damper will be increased proportionally As the CO2 level decreases because of the increase in fresh air the outdoor air d...

Page 95: ...the position of the reversing valves and shuts off the outdoor fan The electric heaters if installed will be energized The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65_F 18_C or the duration of defrost cycle completes a 10 minute period During the Defrost mode if circuit 1 defrosts first RVS1 will oscillate between Heating and Cooling modes until the Defrost ...

Page 96: ...heating b include capability for occupancy scheduling 23 09 23 Direct digital Control system for HVAC 23 09 23 13 Decentralized Rooftop Units 23 09 23 13 A PremierLinkt controller 1 Shall be ASHRAE 62 2001 compliant 2 Shall accept 18 32VAC input power 3 Shall have an operating temperature range from 40_F 40_C to 158_F 70_C 10 95 RH non condens ing 4 Shall include an integrated economizer controlle...

Page 97: ...s Polyswitches shall be used on in coming power and network connections Polyswitches will return to normal when the trip condition clears 11 Shall have a battery back up capable of a minimum of 10 000 hours of data and time clock retention during power outages 12 Shall have built in support for Carrier technician tool 13 Shall include an EIA 485 protocol communication port an access port for conne...

Page 98: ...ty Self Contained Air Conditioners 50TCQ 04 14 23 81 19 13 A General 1 Outdoor rooftop mounted electrically controlled heating and cooling unit utilizing a n hermetic scroll com pressor s for cooling duty and heat pump for heating duty 2 Factory assembled single piece heating and cooling rooftop unit Contained within the unit enclosure shall be all factory wiring piping controls and special featur...

Page 99: ...net shall be constructed of galvanized steel and shall be bonderized and coated with a prepainted baked enamel finish on all externally exposed surfaces 2 Unit cabinet exterior paint shall be film thickness dry 0 003 inches minimum gloss per ASTM D523 60_F 60 Hardness H 2H Pencil hardness 3 Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210 240 or 340 360 mi...

Page 100: ...b Galvanized steel tube sheets shall not be acceptable c A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan 4 Optional E coated aluminum fin evaporator and condenser coils on all models a Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material bridgin...

Page 101: ...nently lubricated bearings b Shall have inherent automatic reset thermal overload protection or circuit breaker c Shall have a maximum continuous bhp rating for continuous duty operation no safety factors above that rating shall be required 2 Electric Drive Direct Drive X13 5 Speed Torque Evaporator Fan a Multi speed motor with easy quick adjustment settings b Blower fan shall be double inlet type...

Page 102: ...en in free cooling mode in the DCV mode or the exhaust fan contact is closed r Economizer equipped with a mixed air sensor field mounted on the indoor fan blower side plate to control return air and outdoor air dampers to maintain 55_F 13_C temperature 2 Two Position Motorized Damper a Damper shall be a Two Position Motorized Damper Damper travel shall be from the full closed position to the field...

Page 103: ...haust air without supply air contamination b Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight c Permits installation and securing of ductwork to curb prior to mounting unit on the curb 11 High Static Indoor Fan Motor s and Drive s 04 14 a High static motor s and drive s shall be factory installed to provide additional performance range 12 Thru th...

Page 104: ...e nickel chrome alloy 0 29 inches inside diameter strung through ceramic insulators mounted on metal frame Coil ends are staked and welded to terminal screw slots 2 Heater assemblies are provided with integral fusing for protection of internal heater circuits not exceeding 48 amps each Auto reset thermo limit controls magnetic heater contactors 24V coil and terminal block all mounted in electric h...