47
Table 16 – HEATING CAPACITIES
3 TONS
50TCQA04
RETURN
AIR
(
°
F db)
CFM
(STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (
°
F db AT 70% RH)
---10
0
10
17
30
40
47
50
60
55
900
Capacity
11.6
15.1
18.9
21.7
27.6
32.7
36.0
37.1
41.8
Int. Cap.
10.7
13.9
17.4
19.8
24.2
32.7
36.0
37.1
41.8
1200
Capacity
12.0
15.5
19.4
22.3
28.4
33.5
36.7
37.8
42.7
Int. Cap.
11.1
14.3
17.8
20.3
24.9
33.5
36.7
37.8
42.7
1500
Capacity
12.6
16.3
20.2
23.1
29.5
34.2
37.5
38.6
43.5
Int. Cap.
11.6
15.0
18.5
21.1
25.8
34.2
37.5
38.6
43.5
70
900
Capacity
9.8
13.3
17.2
20.0
25.6
30.4
34.5
35.5
40.2
Int. Cap.
9.0
12.3
15.7
18.2
22.5
30.4
34.5
35.5
40.2
1200
Capacity
10.1
13.8
17.7
20.7
26.6
31.7
35.4
36.5
41.2
Int. Cap.
9.3
12.7
16.3
18.8
23.3
31.7
35.4
36.5
41.2
1500
Capacity
10.8
14.6
18.6
21.5
27.7
33.0
36.4
37.4
42.0
Int. Cap.
10.0
13.4
17.1
19.6
24.3
33.0
36.4
37.4
42.0
80
900
Capacity
8.3
11.9
15.7
18.6
24.1
29.0
32.7
34.1
39.0
Int. Cap.
7.7
10.9
14.4
16.9
21.2
29.0
32.7
34.1
39.0
1200
Capacity
8.6
12.4
16.3
19.3
25.1
30.2
34.3
35.4
40.1
Int. Cap.
8.0
11.4
15.0
17.6
22.0
30.2
34.3
35.4
40.1
1500
Capacity
9.3
13.2
17.2
20.2
26.2
31.4
35.5
36.5
41.1
Int. Cap.
8.6
12.1
15.8
18.4
23.0
31.4
35.5
36.5
41.1
--- Indicates standard rating point
LEGEND
Capacity ---
Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. ---
Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH
---
Relative Humidity
db
---
Dry Bulb
Table 17 – HEATING CAPACITIES
4 TONS
50TCQA05
RETURN
AIR
(
°
F db)
CFM
(STANDARD AIR)
TEMPERATURE AIR ENTERING OUTDOOR COIL (
°
F db AT 70% RH)
---10
0
10
17
30
40
47
50
60
55
1200
Capacity
17.5
22.0
26.6
30.0
36.8
42.6
47.1
48.9
55.3
Int. Cap.
16.2
20.2
24.4
27.3
32.2
42.6
47.1
48.9
55.3
1600
Capacity
17.5
22.1
26.7
30.2
37.3
43.5
47.9
49.8
56.1
Int. Cap.
16.2
20.3
24.5
27.5
32.7
43.5
47.9
49.8
56.1
2000
Capacity
18.5
23.1
27.8
31.3
38.7
44.9
49.1
50.9
57.1
Int. Cap.
17.1
21.3
25.5
28.6
33.9
44.9
49.1
50.9
57.1
70
1200
Capacity
15.8
20.3
25.0
28.3
35.0
40.5
44.7
46.7
53.0
Int. Cap.
14.6
18.7
22.9
25.8
30.6
40.5
44.7
46.7
53.0
1600
Capacity
15.9
20.5
25.3
28.7
35.6
41.3
45.8
47.8
53.9
Int. Cap.
14.7
18.9
23.2
26.1
31.2
41.3
45.8
47.8
53.9
2000
Capacity
17.0
21.7
26.5
29.9
36.9
42.9
47.3
49.1
55.2
Int. Cap.
15.7
20.0
24.3
27.3
32.4
42.9
47.3
49.1
55.2
80
1200
Capacity
14.2
18.8
23.5
26.9
33.6
39.0
43.2
45.1
51.4
Int. Cap.
13.1
17.3
21.6
24.6
29.4
39.0
43.2
45.1
51.4
1600
Capacity
14.4
19.1
23.9
27.4
34.2
39.8
44.2
46.1
52.4
Int. Cap.
13.3
17.6
22.0
25.0
30.0
39.8
44.2
46.1
52.4
2000
Capacity
15.5
20.3
25.2
28.7
35.6
41.4
45.9
47.8
53.8
Int. Cap.
14.3
18.7
23.1
26.1
31.2
41.4
45.9
47.8
53.8
--- Indicates standard rating point
LEGEND
Capacity ---
Instantaneous Capacity (1000 Btuh) includes indoor fan motor heat @AHRI static conditions
Int. Cap. ---
Integrated Capacity is Instantaneous Capacity minus the effects of frost on the outdoor coil and the heat
required to defrost
RH
---
Relative Humidity
db
---
Dry Bulb
50TC
Q
Summary of Contents for WeatherMaker 50TCQ*07
Page 21: ...21 WEIGHTS DIMENSIONS C09016 Fig 1 Dimensions 50TCQ 04 07 50TCQ ...
Page 24: ...24 WEIGHTS DIMENSIONS cont C08677B Fig 5 Dimensions 50TCQ 08 09 50TCQ ...
Page 25: ...25 WEIGHTS DIMENSIONS cont C10393 Fig 6 Dimensions 50TCQ 08 09 50TCQ ...
Page 27: ...27 WEIGHTS DIMENSIONS cont C10369 Fig 9 Curb Dimensions 50TCQ 08 09 50TCQ ...
Page 28: ...28 WEIGHTS DIMENSIONS cont C09556A Fig 10 Dimensions 50TCQ 12 50TCQ ...
Page 31: ...31 WEIGHTS DIMENSIONS cont C10370 Fig 14 Curb Dimensions 50TCQ 12 50TCQ ...
Page 32: ...32 WEIGHTS DIMENSIONS cont C09895A Fig 15 Dimensions 50TCQ 14 50TCQ ...
Page 33: ...33 WEIGHTS DIMENSIONS cont C09895A Fig 16 Dimensions 50TCQ 14 50TCQ ...
Page 35: ...35 WEIGHTS DIMENSIONS cont C10251 Fig 19 Curb Dimensions 50TCQ 14 50TCQ ...
Page 87: ...87 TYPICAL WIRING DIAGRAMS C09063 Fig 28 1 Stage Cooling Typical Power Diagram 50TCQ ...
Page 88: ...88 TYPICAL WIRING DIAGRAMS cont C09065 Fig 29 2 Stage Cooling Typical Power Diagram 50TCQ ...
Page 89: ...89 TYPICAL WIRING DIAGRAMS cont C09066 Fig 30 PremierLink Option Diagram 50TCQ ...
Page 90: ...90 TYPICAL WIRING DIAGRAMS cont C09067 Fig 31 Multi Protocol Option Diagram 50TCQ ...
Page 91: ...91 C09062 Fig 32 1 Stage Typical Wiring Diagram 50TCQ ...
Page 92: ...92 C09064 Fig 33 2 Stage Typical Wiring Diagram 50TCQ ...