c. Molded plug connection to insure proper connection.
23 09 33.23.B. Safeties:
1. Compressor overtemperature, overcurrent.
2. Loss of charge switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres-
sure switches. They shall physically prevent the cross--wiring of the safety switches between circuits 1 and 2.
b. Loss of charge switch shall use different color wire than the high pressure switch. The purpose is to assist the
installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High pressure switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high pres-
sure switches. They shall physically prevent the cross--wiring of the safety switches between circuits 1 and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the
installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Freeze protection thermostat, evaporator coil.
5. Automatic reset, motor thermal overload protector.
23 09 93
Sequence of Operations for HVAC Controls
23 09 93.13
Decentralized, Rooftop Units:
23 09 93.13
INSERT SEQUENCE OF OPERATION
23 40 13
Panel Air Filters
23 40 13.13
Decentralized, Rooftop Units:
23 40 13.13.A. Standard filter section
1. Shall consist of factory--installed, low velocity, throwaway 2--in. thick fiberglass filters of commercially available
sizes.
2. Unit shall use only one filter size. Multiple sizes are not acceptable.
3. Filters shall be accessible through an access panel with “no--tool” removal as described in the unit cabinet section
of this specification (23 81 19.13.H).
23 81 19
Self--Contained Air Conditioners
23 81 19.13
Small--Capacity Self--Contained Air Conditioners (50TCQ*04--14)
23 81 19.13.A. General
1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a(n) hermetic scroll com-
pressor(s) for cooling duty and heat pump for heating duty.
2. Factory assembled, single piece heating and cooling rooftop unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, and special features required prior to field startup.
3. Unit shall use environmentally safe, Puron refrigerant.
4. Unit shall be installed in accordance with the manufacturer’s instructions.
5. Unit must be selected and installed in compliance with local, state, and federal codes.
23 81 19.13.B. Quality Assurance
1. Unit meets ASHRAE 90.1--2004 minimum efficiency requirements.
2. Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.
3. Unit shall be designed to conform to ASHRAE 15, 2001.
4. Unit shall be UL--tested and certified in accordance with ANSI Z21.47 Standards and UL--listed and certified
under Canadian standards as a total package for safety requirements.
5. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
6. Unit casing shall be capable of withstanding 500--hour salt spray exposure per ASTM B117 (scribed specimen).
7. Unit casing shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 5000--hour salt
spray.
8. Unit shall be designed in accordance with ISO 9001:2000, and shall be manufactured in a facility registered by
ISO 9001:2000.
9. Roof curb shall be designed to conform to NRCA Standards.
10. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be
stored at the factory, and must be available upon request.
11. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
12. Unit shall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box up
to 40 mph.
50TC
Q
Summary of Contents for WeatherMaker 50TCQ*07
Page 21: ...21 WEIGHTS DIMENSIONS C09016 Fig 1 Dimensions 50TCQ 04 07 50TCQ ...
Page 24: ...24 WEIGHTS DIMENSIONS cont C08677B Fig 5 Dimensions 50TCQ 08 09 50TCQ ...
Page 25: ...25 WEIGHTS DIMENSIONS cont C10393 Fig 6 Dimensions 50TCQ 08 09 50TCQ ...
Page 27: ...27 WEIGHTS DIMENSIONS cont C10369 Fig 9 Curb Dimensions 50TCQ 08 09 50TCQ ...
Page 28: ...28 WEIGHTS DIMENSIONS cont C09556A Fig 10 Dimensions 50TCQ 12 50TCQ ...
Page 31: ...31 WEIGHTS DIMENSIONS cont C10370 Fig 14 Curb Dimensions 50TCQ 12 50TCQ ...
Page 32: ...32 WEIGHTS DIMENSIONS cont C09895A Fig 15 Dimensions 50TCQ 14 50TCQ ...
Page 33: ...33 WEIGHTS DIMENSIONS cont C09895A Fig 16 Dimensions 50TCQ 14 50TCQ ...
Page 35: ...35 WEIGHTS DIMENSIONS cont C10251 Fig 19 Curb Dimensions 50TCQ 14 50TCQ ...
Page 87: ...87 TYPICAL WIRING DIAGRAMS C09063 Fig 28 1 Stage Cooling Typical Power Diagram 50TCQ ...
Page 88: ...88 TYPICAL WIRING DIAGRAMS cont C09065 Fig 29 2 Stage Cooling Typical Power Diagram 50TCQ ...
Page 89: ...89 TYPICAL WIRING DIAGRAMS cont C09066 Fig 30 PremierLink Option Diagram 50TCQ ...
Page 90: ...90 TYPICAL WIRING DIAGRAMS cont C09067 Fig 31 Multi Protocol Option Diagram 50TCQ ...
Page 91: ...91 C09062 Fig 32 1 Stage Typical Wiring Diagram 50TCQ ...
Page 92: ...92 C09064 Fig 33 2 Stage Typical Wiring Diagram 50TCQ ...