9
Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT
UNIT
COOLING
ELECTRIC HEATERS
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
50TCQ*04
900
1500
900
1500
50TCQ*05
1200
2000
1200
2000
50TCQ*06
1500
2500
1500
2500
50TCQ*07
1800
3000
1800
3000
50TCQ*08
2250
3750
2250*
3750
50TCQ*09
2550
4250
2550*
4250
50TCQ*12
3000
5000
3000
5000
50TCQ*14
3750
6250
3750
6250
*Minimum electric heat CFM exceptions :
UNIT
UNIT VOLTAGE
HEATER kW
UNIT
CONFIGURATION
REQUIRED MINIMUM
CFM
50TCQ*08
50TCQ*09
575
17.0
Horizontal or Vertical
2800
34.0
2350
Table 4 – SOUND PERFORMANCE TABLE
50TCQ
OUTDOOR SOUND (dB)
A---WEIGHTED
63
125
250
500
1000
2000
4000
8000
A04
77
78.9
81.7
74.9
72.5
70.3
65.6
65.6
62.6
A05
80
90.4
84.6
77.6
77.5
74.8
70.6
68.0
64.2
A06
80
92.7
84.9
79.0
76.7
73.8
69.6
66.4
62.8
A07
78
88.0
79.5
76.2
75.8
72.5
68.6
65.7
62.4
D08
82
89.7
81.5
80.5
79.2
77.1
73.2
70.2
67.4
D09
84
90.8
85.2
81.6
79.5
78.1
74.0
70.4
66.5
D12
87
88.1
90.0
85.9
83.0
81.6
78.5
76.4
75.5
D14
83
89.3
85.2
80.3
78.0
77.0
74.4
73.7
68.9
LEGEND
dB --- Decibel
NOTES
:
1. Outdoor sound data is measured in accordance with
AHRI standard 270---95.
2. Measurements are expressed in terms of sound power.
Do not compare these values to sound pressure values
because sound pressure accounts for specific environ-
mental factors which do not match individual applica-
tions. Sound power values are independent of the envir-
onment and therefore more accurate.
3. A---weighted sound ratings filter out very high and very
low frequencies, to better approximate the response of
an “average” human ear. A---weighted measurements for
Carrier units are taken in accordance with 270---95.
50TC
Q
Summary of Contents for WeatherMaker 50TCQ*07
Page 21: ...21 WEIGHTS DIMENSIONS C09016 Fig 1 Dimensions 50TCQ 04 07 50TCQ ...
Page 24: ...24 WEIGHTS DIMENSIONS cont C08677B Fig 5 Dimensions 50TCQ 08 09 50TCQ ...
Page 25: ...25 WEIGHTS DIMENSIONS cont C10393 Fig 6 Dimensions 50TCQ 08 09 50TCQ ...
Page 27: ...27 WEIGHTS DIMENSIONS cont C10369 Fig 9 Curb Dimensions 50TCQ 08 09 50TCQ ...
Page 28: ...28 WEIGHTS DIMENSIONS cont C09556A Fig 10 Dimensions 50TCQ 12 50TCQ ...
Page 31: ...31 WEIGHTS DIMENSIONS cont C10370 Fig 14 Curb Dimensions 50TCQ 12 50TCQ ...
Page 32: ...32 WEIGHTS DIMENSIONS cont C09895A Fig 15 Dimensions 50TCQ 14 50TCQ ...
Page 33: ...33 WEIGHTS DIMENSIONS cont C09895A Fig 16 Dimensions 50TCQ 14 50TCQ ...
Page 35: ...35 WEIGHTS DIMENSIONS cont C10251 Fig 19 Curb Dimensions 50TCQ 14 50TCQ ...
Page 87: ...87 TYPICAL WIRING DIAGRAMS C09063 Fig 28 1 Stage Cooling Typical Power Diagram 50TCQ ...
Page 88: ...88 TYPICAL WIRING DIAGRAMS cont C09065 Fig 29 2 Stage Cooling Typical Power Diagram 50TCQ ...
Page 89: ...89 TYPICAL WIRING DIAGRAMS cont C09066 Fig 30 PremierLink Option Diagram 50TCQ ...
Page 90: ...90 TYPICAL WIRING DIAGRAMS cont C09067 Fig 31 Multi Protocol Option Diagram 50TCQ ...
Page 91: ...91 C09062 Fig 32 1 Stage Typical Wiring Diagram 50TCQ ...
Page 92: ...92 C09064 Fig 33 2 Stage Typical Wiring Diagram 50TCQ ...