S-BUS SENSOR WIRING
The labels on the sensors and controller are color coded for ease of
installation. Orange labeled sensors can only be wired to orange
terminals on the controller. Brown labeled sensors can only be
wired to S-bus (brown) terminals. Use Fig. 74 and Table 10 to lo
-
cate the wiring terminals for each S-Bus sensor.
Use Fig. 74 and Table 10 to locate the wiring terminals for each
enthalpy control sensor.
Fig. 74 —
S-Bus Sensor DIP Switches
Table 10 —
HH57AC081 Sensor Wiring Terminations
Use Fig. 74 and Table 11 to set the DIP switches for the desired
use of the sensor.
Table 11 —
HH57AC081 Sensor DIP Switch
NOTE: When a S-Bus sensor is connected to an existing network,
it will take 60 minutes for the network to recognize and auto-con
-
figure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures
(except SAT) will be issued and no economizing function will be
available.
CO
2
SENSOR WIRING
When using a CO
2
sensor, the black and brown common wires are
internally connected and only one is connected to “IAQ COM” on
the W7220. Use the power from the W7220 to power the CO
2
sensor OR make sure the ground for the power supplies are com
-
mon. See Fig. 75 for CO
2
sensor wiring.
LABEL
TYPE
DESCRIPTION
Top Left Terminal Block
MAT
MAT
20k NTC
and COM
Mixed Air Temperature Sensor (Polarity
Insensitive Connection)
OAT
OAT
20k NTC
and COM
Outdoor Air Temperature Sensor
(Polarity Insensitive Connection)
S-BUS
S-BUS
S-BUS
(Sylk* Bus)
Enthalpy Control Sensor
(Polarity Insensitive Connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
Air Quality Sensor Input (e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24-v
24 vac
Damper Actuator 24 vac Source
LABEL
TYPE
DESCRIPTION
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
OCC
24 vac IN
Shut Down (SD) or HEAT (W)
Conventional only
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
EXH1
24 vac OUT Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2-I
24 vac IN
Y2 in - Cooling Stage 2 Input from space
thermostat
Y2-O
24 vac OUT Y2 out - Cooling Stage 2 Output to stage
2 mechanical cooling
Y1-I
24 vac IN
Y1 in - Cooling Stage 2 Input from space
thermostat
Y1-O
24 vac OUT Y1 out - Cooling Stage 2 Output to stage
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)
TERMINAL
TYPE
DESCRIPTION
NUMBER
LABEL
1
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
2
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
USE
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1
2
3
DA
OFF
ON
OFF
RA
ON
OFF
OFF
OA
OFF
OFF
OFF
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
S-BUS
TERMINALS
(1 AND 2)
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...