![Carrier WeatherMaker 48TC A/B07 Series Installation Instructions Manual Download Page 54](http://html.mh-extra.com/html/carrier/weathermaker-48tc-a-b07-series/weathermaker-48tc-a-b07-series_installation-instructions-manual_2560313054.webp)
54
PremierLink™ Control
For details on operating units equipped with the factory-installed
PremierLink controller option, refer to the
PremierLink Retrofit
Rooftop Controller Version 3.x Installation, Start-Up, and Config
-
uration Instructions
manual.
RTU Open Control System
For details on operating units equipped with the factory-installed
RTU Open controller, refer to the
“Factory-Installed RTU Open
Multi-Protocol Controller Control, Start-Up, Operation and Trou
-
bleshooting”
manual.
SMOKE DETECTORS
Smoke detectors are available as factory-installed options on
48TC models. Smoke detectors may be specified for supply air
only, for return air without or with economizer, or in combination
of supply air and return air. All components necessary for opera
-
tion are factory-provided and mounted. The unit is factory-config
-
ured for immediate smoke detector shutdown operation; addition
-
al wiring or modifications to unit terminal board may be necessary
to complete the unit and smoke detector configuration to meet
project requirements.
Units equipped with factory-optional return-air smoke detectors
require a relocation of the sensor module at unit installation. See
Fig. 78 for the as-shipped location.
COMPLETING INSTALLATION OF RETURN-AIR
SMOKE SENSOR
1. Unscrew the two screws holding the return-air smoke
detector assembly. See Fig. 79, Step 1.
2. Save the screws.
3. Turn the assembly 90 degrees and then rotate end to end.
Make sure that the elbow fitting is pointing down. See
Fig. 79, Step 2.
4. Screw the sensor and detector plate into its operating posi
-
tion using screws from Step 1. See Fig. 79, Step 3.
5. Connect the flexible tube on the sampling inlet to the sam
-
pling tube on the basepan.
ADDITIONAL APPLICATION DATA
Refer to the application data sheet titled “
Factory-Installed Smoke
Detector, for Small and Medium Rooftop Units 2 to 25 Tons
” for
discussions on additional control features of these smoke detectors
including multiple unit coordination.
Fig. 78 —
Return Air Smoke Detector; Shipping
Position
Fig. 79 —
Completing Installation of Return Air Smoke Sensor
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor start-up and shut
-
down between checkout tests so that you do not short-cycle the
compressors.
RETURN AIR
SMOKE DETECTOR
(AS SHIPPED)
STEP 1
STEP 2
STEP 3
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...