GENERAL
These installation instructions cover the 48TC units with gas heat
and electric cooling. Units are pre-wired and pre-charged with
environmentally balanced Puron
®
(R-410A) refrigerant at the
factory.
See Fig. 1 for model number nomenclature. See Fig. 2 and
3 (size 07), Fig. 7 (size 08-12), Fig. 8 (size 14), and Fig. 9
(size 16) for unit dimensions. See Fig. 4 (size 07) and Fig. 10
(size 08-16) for service clearances. See Fig. 5 (size 07), and
Fig. 15 (size 08-16) for base rail details. See Fig. 6 (size 07) for
thru-the-base charts.
Installation of this unit at altitudes above 2000 ft (610 m) shall be
made in accordance with the Listed High Altitude Conversion Kit
available with this furnace.
L'installation de ce générateur de chaleur à des altitudes
supérieures à 2000 pi (610 m) doit être effectuée conformément
aux instructions accompagnant la trousse de conversion pour
haute altitude fournie avec cet appareil.
Rated Indoor Airflow (cfm)
Table 1 lists the rated indoor airflow used for the AHRI efficiency
rating for the units covered in this document.
Table 1 — AHRI Efficiency — Rated Indoor Airflow
Pre-Installation
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Elec
-
trical Code) ANSI/NFPA 70 for special installation
requirements.
WARNING
FIRE HAZARD
Failure to follow this warning could result in severe personal
injury and/or property damage.
Inlet pressure tap set screw must be tightened and
1
/
8
-in. NPT
pipe plug must be installed to prevent gas leaks.
WARNING
FIRE HAZARD
Failure to follow this warning could result in severe personal
injury and/or property damage.
Manifold pressure tap set screw must be tightened and
1
/
8
-in.
NPT pipe plug must be installed to prevent gas leaks.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety glasses and gloves
when handling parts and servicing air conditioning equipment.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in se
-
rious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commer
-
cially available soap solution made specifically for the detec
-
tion of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of life.
GAS VALVE
INLET PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
AVERTISSEMENT
RISQUE D'INCENDIE OU D'EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre, cela
peut entraîner la mort, de graves blessures ou des dommages
matériels. Ne jamais vérifier la présence de fuites de gaz au
moyen d’une flamme nue. Vérifier tous les raccords en util
-
isant une solution savonneuse commerciale conçue spéciale
-
ment pour la détection de fuites. Un incendie ou une explo
-
sion risque de se produire, ce qui peut entraîner la mort, des
blessures ou des dommages matériels.
CAUTION
Ensure clearances are in accordance with local installation
codes, the requirements of the gas supplier and the manufac
-
turer's installation instructions.
ATTENTION
Assurez-vous que les dégagements sont conformes aux codes
d'installation locaux, aux exigences du fournisseur de gaz et
aux instructions d'installation du fabricant.
MODEL NUMBER
FULL LOAD AIRFLOW (CFM)
48TC*A/B07
2,200
48TC*M08
2,400
48TC*D/E08
2,250
48TC*M09
3,000
48TC*D/E09
3,400
48TC*M12
3,400
48TC*D/E12
3,000
48TC*D/E14
3,600
48TC*D/E16
5,250
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...