22
Fig. 15 —
Rigging Details
POSITIONING ON CURB
For Size 07-14
Position unit on roof curb so that the following clearances are
maintained:
1
/
4
-in. (6.4 mm) clearance between the roof curb and
the base rail inside the front and back, 0.0-in. clearance between
the roof curb and the base rail inside on the duct end of the unit.
This will result in the distance between the roof curb and the base
rail inside on the condenser end of the unit being approximately
1
/
4
-in. (6.4 mm).
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of
4 ft (1220 mm) from electric and gas meters, gas regulators, and
gas relief equipment. Minimum distance between unit and other
electrically live parts is 48 inches (1220 mm).
Flue gas can deteriorate building materials. Orient unit such that
flue gas will not affect building materials. Locate mechanical draft
system flue assembly at least 48-in. (1220 mm) from an adjacent
building or combustible material.
NOTE: Installation of accessory flue discharge deflector kit will
reduce the minimum clearance to combustible material to 18-in.
(460 mm).
After unit is in position, remove rigging skids and shipping mate
-
rials.
For Size 16
For full perimeter curbs CRRFCURB074A00 and 075A00, the
clearance between the roof curb and the front and rear base rails
should be
1
/
4
-in. (6.4 mm). The clearance between the curb and the
end base rails should be
1
/
2
-in. (13 mm). For retrofit applications
with curbs CRRFCURB003A01 and 4A01, the unit should be po
-
sitioned as shown in Fig. 16. Maintain the 15
1
/
2
-in. (394 mm) and
8
5
/
8
-in. (220 mm) clearances and allow the 22
5
/
16
-in. (567 mm) di
-
mension to float if necessary.
Fig. 16 —
Retrofit Installation Dimensions
(Size 16 Shown)
If the alternative condensate drain location through the bottom of
the unit is used in conjunction with a retrofit curb, the hole in the
curb must be moved 12.5 in. (320 mm) towards the duct end of the
unit. See Fig. 17.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Remove all shipping materials and top skid. Remove extra center
post from the condenser end of the unit so that the condenser end
of the unit matches Fig. 48 and 49. Recycle or dispose of all ship
-
ping materials.
“C”
“A”
“A”
“B”
36”-54”
(914-1371)
SEE DETAIL
DUCT END
DETAIL “A”
POSITION ALL SEAL STRIPS IN PLACE
BEFORE INSTALLING UNIT ON ROOF CURB
AS CLOSE TO THIS END AS POSSIBLE
UNIT
MAX WEIGHT
DIMENSIONS
A
B
C
LB
KG
IN.
MM
IN.
MM
IN.
MM
48TC 07
1075
489
74.5
1890
39.0
990
41.5
1055
48TC-M08
1295
588
88.0
2235
42.0
1065
41.5
1055
48TC-M09
1335
606
88.0
2235
41.5
1055
49.5
1255
48TC-M12
1435
651
88.0
2235
42.5
1080
49.5
1255
48TC*D/E08
1445
657
88.0
2235
43.0
1090
41.5
1055
48TC*D/E09
1565
711
88.0
2235
42.5
1080
49.5
1255
48TC*D/E12
1605
730
88.0
2235
42.0
1065
49.5
1255
48TC*D/E14
1760
800
88.0
2235
29.5
750
53.0
1345
48TC**D/E16
2140
973
116.0
2945
60.5
1535
59.5
1510
NOTES:
1.
SPREADER BARS REQUIRED FOR SIZES 07-14 — Top damage will occur if spreader bars are not used. Not required for size 16.
2. Dimensions in () are in millimeters.
3.
Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use
wooden top to prevent rigging straps from damaging unit.
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...