your area.) If a de-energize via unit disconnect switch operation of
the convenience outlet is desired, connect the source leads to the
load side of the unit disconnect. On a unit without a unit-mounted
disconnect, connect the source leads to compressor contactor C
and indoor fan contactor IFC pressure lugs with unit field power
leads (see Fig. 46).
Fig. 46 —
Power Wiring Connections (Sizes 07-14)
Fig. 47 —
Power Wiring Connections (Size 16)
Field power wires are connected to the unit at line-side pressure
lugs on compressor contactor C and indoor fan contactor IFC (see
wiring diagram label for control box component arrangement) or
at factory-installed option non-fused disconnect switch. Max wire
size is #4 AWG (copper only) (sizes 07-14) and #2 AWG (copper
only) (size 16).
FIELD POWER SUPPLY (SIZE 16)
See Fig. 47. For those units without thru-the-curb power, conduit
must be used to route the main power from the condenser end, via
the power entry in the corner post of the unit (see Fig. 48 and 49)
to either the factory option disconnect or the bottom of the control
box. A 1-in. conduit is provided wrapped around compressor. A
second conduit is provided with factory-installed powered conve
-
nience outlet. For those units that require conduit larger than 1-in.,
it must be field supplied. Fig. 48 and 49 show the wire routings.
If the field disconnect is larger than 100A, it must be attached to
the unit using accessory CRDISBKT001A00 — disconnect
switch bracket (see Fig. 50). Follow the instructions provided with
this accessory. For smaller field disconnects, be sure to use
1
/
2
in.
screws to mount the disconnect directly to the end panel (see
Fig. 51). In either case, set the disconnect vertical location on the
unit so that a 90 degree fitting can be used to connect the conduit
to the disconnect.
Fig. 48 —
Conduit into Factory Option Disconnect
(Size 16)
Fig. 49 —
Conduit into Control Box (Size 16)
C
IFC
Disconnect factory test leads
and discard.
Optional
Disconnect
Switch
13
13
L1
L2
L3
208/230-3-60
460-3-60
575-3-60
Units Without Disconnect Option
Units With Disconnect Option
1
3
5
2
4
6
L1
L2
L3
Factory
Wiring
Disconnect
per
NEC
11
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
11
12
13
L1
L2
L3
TB1
208/230-3-60
460-3-60
575-3-60
Disconnect
per
NEC
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...