Installing the VVT Bypass II
VVT Bypass II Controller
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
9
NOTE
For service access, allow at least 1 foot (.3 m) of clearance between the front of the controller and
adjacent surfaces.
3
Secure the controller and the actuator by installing the screws, anti-rotation slot's bushings, and o-rings that
are supplied with the VVT Bypass II.
O-ring
Bushing
Anti-rotation slot
NOTES
○
Center the bushing in the slot. Failure to do so may cause the actuator to stick or bind.
○
The VVT Bypass II must be secured, but loose enough to allow movement. of the damper shaft.