Installation, Start-Up and

Configuration Instructions

Part Number 33ZCBC-01

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . . . . .1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11

General

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Bypass Controller Hardware

. . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Field-Supplied Hardware

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

DUCT TEMPERATURE (DAT) SENSOR

Mount Bypass Controller

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

LOCATION

MOUNTING

Connect the Power Transformer

. . . . . . . . . . . . . . . . . . . . . . . .2

Bypass Controller Inputs and Outputs

. . . . . . . . . . . . . . . . . 5

Install Duct Temperature Sensor

. . . . . . . . . . . . . . . . . . . . . . . 5

Install Pressure Tubing

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Install Field-Supplied Actuators

. . . . . . . . . . . . . . . . . . . . . . . .6

FLOATING POINT HIGH-TORQUE ACTUATORS

LINKED ACTUATORS

Damper Stops

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Connect the Carrier Network Communication Bus

. . . . . 6

COMMUNICATION BUS WIRE SPECIFICATIONS

CONNECTION TO THE COMMUNICATION BUS

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Perform System Checkout

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

CONFIGURATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-17

Status Display Table

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Maintenance Tables

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

BYPASS CONTROLLER MAINTENANCE TABLE

BYPASS CONTROLLER COMMISSIONING

MAINTENANCE TABLE

BYPASS CONTROLLER SYSTEM PILOT DEFAULT

MAINTENANCE TABLE

Configuration Tables

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

ALARM CONFIGURATION TABLE

BYPASS CONTROLLER CONFIGURATION TABLE

SYSTEM PRESSURE SET POINT CONFIGURATION

TABLE

DUCT SENSOR CONFIGURATION TABLE

DEVICE CONFIGURATION TABLE

LANGUAGE CONFIGURATION TABLE

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-20

System Pressure Operation

. . . . . . . . . . . . . . . . . . . . . . . .18

Bypass Controller Calibration

. . . . . . . . . . . . . . . . . . . . . .18

SAFETY CONSIDERATIONS

GENERAL

The 3V control system VVT bypass controller (33ZCBC-01)

is a system static pressure controller that operates to maintain the
desired system duct pressure based on the system pressure set
point. The VVT bypass controller is used with a system of VVT
zone controllers. Zone controllers maintain precise temperature
control in the space by regulating the flow of conditioned air into
the space and operating an optional terminal fan.

As part of the 3V control system, the bypass controller is

designed to communicate using a Carrier protocol with a
Linkage Coordinator zone controller. One Linkage Coordina-
tor zone controller can coordinate up to 31 additional zone
controllers. The purpose of the Linkage Coordinator/zone
relationship is to provide an efficient data path for communica-
tion between the zone controllers, bypass controller, and
associated Carrier network air source. This arrangement makes
up the 3V control system.

A user interface is not required for everyday operation of

the bypass controller. A service person or building owner can
configure or operate the bypass controller through a Carrier
network user interface such as the System Pilot or Carrier
software.

INSTALLATION

General —

The bypass controller is used to control the

bypass damper actuator in the 3V control system. The purpose
of the bypass damper is to account for fluctuations in the sup-
ply air pressure caused by the zone dampers modulating to sat-
isfy individual set points. The bypass system allows a constant
volume HVAC (heating, ventilation and air conditioning) unit
to supply variable volumes of air to the building. The system
bypasses air from the supply side to the return side of the unit.

Determining the proper size for the bypass damper is criti-

cal for the operation of the VVT (variable volume/variable
temperature) system. If the damper selected is too large, it may
have to modulate more than necessary to react to system pres-
sure changes. The ability of the system to stay within a pressure
range is compromised. When the damper is undersized, the
capability of the damper to control the pressure may be com-
promised due to the inability to bypass enough air volume. An
undersized damper also creates higher airflow velocities which
add to the noise generated by the system.

SAFETY NOTE

Air-conditioning equipment will provide safe and reli-

able service when operated within design specifications.
The equipment should be operated and serviced only by
authorized personnel who have a thorough knowledge
of system operation, safety devices and emergency
procedures.

Good judgement should be used in applying any manu-

facturer’s instructions to avoid injury to personnel or dam-
age to equipment and property.

Disconnect all power to the unit before performing mainte-
nance or service. Unit may automatically start if power is
not disconnected. Electrical shock and personal injury
could result.

3V™ Control System

VVT® Bypass Controller

33ZC

Summary of Contents for VVT 33ZC

Page 1: ...oordinate up to 31 additional zone controllers The purpose of the Linkage Coordinator zone relationship is to provide an efficient data path for communica tion between the zone controllers bypass cont...

Page 2: ...ding the damper shaft through the actuator clamp assembly See Fig 2 for details Remove the controller wiring access cover Secure the controller by installing the screw provided through the grommet in...

Page 3: ...3 Fig 2 Bypass Controller Dimensions Fig 1 Bypass Controller Details...

Page 4: ...ENSOR 1 6 J5 3 1 G CCN 3 3 G 1 1 5 1 6 1 J4 1 2 NOT USED NOT USED NOT USED DAT NOT USED NOT USED NOT USED NOT USED DAT TO COMMUNICATION BUS TO FEEDBACK POTENTIOMETER LINE VOLTAGE EQUIPMENT GROUND TO D...

Page 5: ...p the grommet into the hole until it is secure Pull on the leads of the duct sensor until the sensor is snug against the grommet 3 Connect the sensor leads to the bypass controller s termi nal board a...

Page 6: ...reverse rotation the actuator switch may be changed to the CCW position LINKED ACTUATORS Field supplied linked actuators may be used to link to the bypass controller actuator Install the actuators pe...

Page 7: ...7 Fig 7 High Torque Actuator Wiring...

Page 8: ...8 Fig 8 High Torque Actuator with Linked Dampers Wiring...

Page 9: ...9 Fig 9 Field Supplied Linked Damper Wiring...

Page 10: ...10 Fig 10 Multiple Field Supplied Linked Damper Wiring...

Page 11: ...s cable a color code system for the entire network is recommended to simplify installation and checkout See Table 4 for the recommended color code Table 4 Color Code Recommendations 3 Connect the othe...

Page 12: ...ew bypass pressure set point 10 Read the airflow with a measuring device If the reading varies from the screen value force the value to the mea sured value Once the pressure sensor is forced the contr...

Page 13: ...iable displays whether the leaving air temperature exceeds the heating or cooling limit configured in the Bypass Controller Service Configuration Table If Yes is displayed the System Pressure Set Poin...

Page 14: ...zone controller to turn the system fan off If the communication fails the damper calibration process will be terminated and this decision will be Disabled When the fan is off the zone controller will...

Page 15: ...NT Duct Temperature This variable displays the duct tempera ture at the bypass damper through a 10K thermistor with a measurement range from 40 to 245 F in 0 1 F increments Duct Temperature Display Un...

Page 16: ...efault Value Close Max Damper Alarm Limit This decision is used to gener ate alarms during system heating and cooling modes When the bypass damper position is greater than this configured limit and th...

Page 17: ...ease to within the zero tolerance 1 0 0 1 vdc of the sensor The alarm is disabled if this decision is set to Disable Press Sensr Cal Alarm Default Value Enable Display Range Enable Disable Duct Temp C...

Page 18: ...is off When the fan is off the bypass controller will drive its damper to the fully closed position The bypass controller will read the value of the actuator s feedback potentiometer until the value...

Page 19: ...l terminate the calibration Once at the fully open damper position the bypass controller will read the output voltage of the pressure sensor If the voltage reads within the range of 1 0 vdc 0 1 volt i...

Page 20: ...b 11a 13a Copyright 2004 Carrier Corporation SEN Fig 12 Bypass Controller Operation Flow Chart LEGEND BP Bypass BP_SETPT System Pressure Setpoint DAT Duct Air Temperature DMP_POS Damper Position LAT L...