34
No. Code
Alarm description
Reset type
Action taken
Possible cause
105 1103
Compressor A High pressure switch
protection
Manual
Unit shuts down
Coil fouled, lack of
condenser flow,
condenser valve blocked,
fan circuit fault, high
entering air or condenser
water temperature
106 1104
Compressor A Over current
Manual
Unit shuts down
-
107 1105
Compressor A Locked rotor
Manual
Unit shuts down
Mechanical compressor
fault, motor fault or
defective compressor
slide valve
108 1106
Compressor A Phase loss L1
Manual
Unit shuts down
Power supply wiring fault
109 1107
Compressor A Phase loss L2
Manual
Unit shuts down
As above
110 1108
Compressor A Phase loss L3
Manual
Unit shuts down
As above
111 1109
Compressor A Low current alarm
Manual
Unit shuts down
Defective contactor or
capacity fault
112 1110
Compressor A Y delta starter current
increase failure alarm
Manual
Unit shuts down
Incorrect wiring or no
power for the delta
contactor
113 1111
Compressor A Contactor failure
Manual
Unit shuts down
Incorrect wiring or
defective contactor or
TCPM board
114 1112
Compressor A Unable to stop motor
Manual
Unit shuts down
Incorrect wiring or
defective contactor
115 1113
Compressor A Phase reversal
Manual
Unit shuts down
-
116 1114
Compressor A MTA configuration fault
Manual
Unit shuts down
MTA configuration
incorrect or defective
TCPM board
117 1115
Compressor A Configuration switch
mismatch
Manual
Unit shuts down
Configuration switch S1
incorrect wiring or
defective TCPM board
118 1116
Compressor A Unexpected switch setting
change
Manual
Unit shuts down
As above
119 1117
Compressor A Power on reset
Manual
Unit shuts down
Verify that power supply
cuts have occurred
120 1118
Compressor A UL 1998 critical section
software error
Manual
Unit shuts down
Power network noise or
defective TCPM board
121 1119
Compressor A UL 1998 current measure
dual channel mismatch
Manual
Unit shuts down
Power network noise or
defective TCPM board
122 2101
Compressor B Motor temperature too high Manual
Unit shuts down
Motor/wiring fault
123 2102
Compressor B Motor temperature out of
range
Manual
Unit shuts down
Probe defective or
incorrect wiring
124 2103
Compressor B High pressure switch
protection
Manual
Unit shuts down
Coil fouled, lack of
condenser flow,
condenser valve blocked,
fan circuit fault, high
entering air or condenser
water temperature
125 2104
Compressor B Over current
Manual
Unit shuts down
-
126 2105
Compressor B Locked rotor
Manual
Unit shuts down
Mechanical compressor
fault, motor fault or
defective compressor
slide valve
127 2106
Compressor B Phase loss L1
Manual
Unit shuts down
Power supply wiring fault
128 2107
Compressor B Phase loss L2
Manual
Unit shuts down
As above
129 2108
Compressor B Phase loss L3
Manual
Unit shuts down
As above
130 2109
Compressor B Low current alarm
Manual
Unit shuts down
Defective contactor or
capacity fault
131 2110
Compressor B Y delta starter current
increase failure alarm
Manual
Unit shuts down
Incorrect wiring or no
power for the delta
contactor
132 2111
Compressor B Contactor failure
Manual
Unit shuts down
Incorrect wiring or
defective contactor or
TCPM board