19
6.2 -
Configuration menu
Icon
Displayed text*
Description
Associated table
General Configuration
General configuration
GEN_CONF
Pump Configuration
Pump configuration
PUMPCONF
User Configuration
User configuration
USERCONF
Reset Configuration
Reset configuration
RESETCFG
Schedule Menu
Schedule menu
SCHEDULE
Holiday Menu
Holiday menu
HOLIDAY
Broadcast Menu
Broadcast configuration
BROCASTS
Date/Time configuration
Date/time configuration
DATETIME
Control Identification
Control identification
CTRL_ID
*Depends on the selected language (English by default).
CAUTION:
Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
General Configuration Menu – GEN_CONF
No. Name
Status
Default
Unit
Displayed text*
Description
1
lead_cir
0 to 2
0
-
Cir Priority Sequence
Circuit priority
2
0=Auto, 1=A Prio
0 = Automatic circuit selection
1 = Circuit A priority
3
2=B Prio
2 = Circuit B priority
4
seq_typ
0 to 2
0
-
Loading Sequence
Loading sequence (see also section 7.12)
5
0=Equal, 1=Staged
0 = Equal loading sequence
1 = Staged loading sequence
6
2=Smart
2 = Smart loading sequence
7
ramp_sel
no/yes
no
-
Ramp Loading Select
Ramp loading selection
8
off_on_d
1 to 15
1
min
Unit Off to On Delay
Unit Off to On delay
9
nh_start
00:00
00:00
hour
Night Mode Start Hour
Night mode start time
10
nh_end
00:00
00:00
hour
Night Mode End Hour
Night mode end time
11
nh_limit
0 to 100
100
%
Night Capacity Limit
Night capacity limit
12
bas_menu
0 to 3
0
-
Basic Menu Configuration
Basic menu configuration
13
0 = All Access
0 = All access
14
1 = no alarm menu
1 = No alarm menu
15
2 = no setpoint menu
2 = No setpoint menu
16
3 = 1 + 2
3 = No alarm and no setpoint menu
17
lim_sel
0 to 2
0
-
Demand Limit Type Select
Demand limit selection
18
0 = None
0 = None
19
1 = Switch Control
1 = Switch Control
20
2 = 4-20mA Control
2 = 4-20mA Control
21
lim_mx
0 to 20
0
mA
mA For 100% Demand Limit
100% demand limit (mA)
22
lim_ze
0 to 20
10
mA
mA For 0% Demand Limit
0% demand limit (mA)
23
curr_sel
no/yes
no
-
Current Limit Select
Current limit selection
24
curr_ful
0 to 4000
2000
A
CurrentLimit at 100%
Current limit at 100%