16
Pressures Menu – PRESSURE
No. Name
Status
Unit
Displayed text*
Description
1
DP_A
-
kPa
Discharge Pressure A
Discharge pressure, circuit A
2
SP_A
-
kPa
Main Suction Pressure A
Main suction pressure, circuit A
3
OP_A
-
kPa
Oil Pressure A
Oil pressure, circuit A
4
DOP_A
-
kPa
Oil Pressure DifferenceA
Oil pressure difference, circuit A
5
ECON_P_A
-
kPa
Economizer Pressure A
Economizer pressure, circuit A
6
DP_B
-
kPa
Discharge Pressure B
Discharge pressure, circuit B
7
SP_B
-
kPa
Main Suction Pressure B
Main suction pressure, circuit B
8
OP_B
-
kPa
Oil Pressure B
Oil pressure, circuit B
9
DOP_B
-
kPa
Oil Pressure DifferenceB
Oil pressure difference, circuit B
10
ECON_P_B
-
kPa
Economizer Pressure B
Economizer pressure, circuit B
11
DP_C
-
kPa
Discharge Pressure C
Not applicable to this unit
12
SP_C
-
kPa
Main Suction Pressure C
Not applicable to this unit
13
OP_C
-
kPa
Oil Pressure C
Not applicable to this unit
14
DOP_C
-
kPa
Oil Pressure DifferenceC
Not applicable to this unit
15
ECON_P_C
-
kPa
Economizer Pressure C
Not applicable to this unit
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
No. Name
Status
Unit
Displayed text*
Description
1
ONOFF_SW
open/close
-
Remote On/Off Switch
Remote on/off switch
2
HC_SW
open/close
-
Remote HeatCool Switch
Remote heating/cooling selection switch
3
SETP_SW
open/close
-
Remote Setpoint Switch
Remote setpoint selection switch
4
LIM_SW1
open/close
-
Limit Switch 1
Demand limit switch 1
5
LIM_SW2
open/close
-
Limit Switch 2
Demand limit switch 2 (EMM option)
6
OIL_L_A
open/close
-
Oil Level Input A
Oil level input, circuit A
7
OIL_L_B
open/close
-
Oil Level Input B
Oil level input, circuit B
8
OIL_L_C
open/close
-
Oil Level Input C
Not applicable to this unit
9
CURREN_A
-
A
Motor Current A
Motor current, circuit A
10
CURREN_B
-
A
Motor Current B
Motor current, circuit B
11
CURREN_C
-
A
Motor Current C
Not applicable to this unit
12
SP_RESET
-
mA
Reset/Setpnt4-20mA Sgnl
4-20 mA signal, setpoint reset
13
REM_LOCK
open/close
-
Customer Interlock
Customer interlock: When the contact is closed, the unit
will be stopped with no delay. The switch is provided on
the customer's terminal block of the optional EMM.
14
ICE_SW
open/close
-
Ice Done Storage Switch
Ice storage end switch
15
OCC_OVSW
open/close
-
Occupied Override Switch
Occupied override switch
16
LIM_ANAL
-
mA
Limit 4-20mA Signal
4-20 mA signal, capacity limit
17
ELEC_BOX
open/close
-
Electrical Box Interlock
Electrical box interlock
18
bacdongl
no/yes
-
BACnet Dongle
BACnet dongle: Used when the unit is incorporated
into the BACnet network
19
leak_v
-
V
Leakage detector 1 val
Refrigerant leakage detection (optional)
20
leak_2_v
-
V
Leakage detector 2 val
Refrigerant leakage detection (optional)
21
ElBxF1_s
off/on
-
Electrical Box Fan status 1
Electrical box fan status
*Depends on the selected language (English by default).