18
Run Times Menu – RUNTIME (continued)
No. Name
Status
Unit
Displayed text*
Description
10
hr_cpum2
-
hour
Cooler Pump #2 Hours
Operating hours, evaporator pump 2
11
hr_hpum1
-
hour
Condenser Pump #1 Hours
Operating hours, condenser pump
12
hr_hpum2
-
hour
Condenser Pump #2 Hours
Not applicable to this unit
*Depends on the selected language (English by default).
Modes Menu – MODES
No. Name
Status
Unit
Displayed text*
Description
1
m_delay
no/yes
-
Start Up Delay In Effect
Start-up delay in effect
2
m_2stpt
no/yes
-
Second Setpoint In Use
Second setpoint in use
3
m_reset
no/yes
-
Reset In Effect
Setpoint reset active
4
m_demlim
no/yes
-
Demand limit active
Demand limit active
5
m_ramp
no/yes
-
Ramp Loading Active
Ramp loading active
6
m_pmprot
no/yes
-
Cooler Pump Rotation
Evaporator pump rotation
7
m_pmpper
no/yes
-
Pump Periodic Start
Pump periodic start active
8
m_night
no/yes
-
Night Low Noise Active
Night low noise active
9
m_slave
no/yes
-
Master Slave Active
Master/Slave mode active
10
m_autoc
no/yes
-
Auto Changeover Active
Not applicable to this unit
11
m_lowEwt
no/yes
-
Heating Low EWT Lockout
Heating low EWT lockout
12
m_cpmpro
no/yes
-
Condenser Pump Rotation
Not applicable to this unit
13
m_cpmppr
no/yes
-
Cond Pump Periodic Start
Condenser pump periodic start
14
m_ice
no/yes
-
Ice Mode In Effect
Ice storage mode active (EMM option)
15
m_sst_a
no/yes
-
Low Suction Circuit A
Low suction, circuit A
16
m_sst_b
no/yes
-
Low Suction Circuit B
Low suction, circuit B
17
m_sst_c
no/yes
-
Low Suction Circuit C
Not applicable to this unit
18
m_map_a
no/yes
-
Map compressor Circuit A
Compressor mapping, circuit A
19
m_map_b
no/yes
-
Map compressor Circuit B
Compressor mapping, circuit B
20
m_map_c
no/yes
-
Map compressor Circuit C
Not applicable to this unit
21
m_hp_a
no/yes
-
High Pres Override Cir A
High pressure override, circuit A
22
m_hp_b
no/yes
-
High Pres Override Cir B
High pressure override, circuit B
23
m_hp_c
no/yes
-
High Pres Override Cir C
Not applicable to this unit
*Depends on the selected language (English by default).
Setpoint Menu – SETPOINT
No. Name
Status
Default
Unit
Displayed text*
Description
1
csp1
-5 to 32
20
°C
Cooling Setpoint 1
Cooling setpoint 1 (used during occupied periods)
2
csp2
-5 to 32
20
°C
Cooling Setpoint 2
Cooling setpoint 2 (used during unoccupied periods)
3
ice_sp
-29 to 26
6.7
°C
Cooling Ice Setpoint
Ice storage setpoint
4
cramp_sp
0.1 to 11.1
0.6
^C
Cooling Ramp Loading Cooling ramp loading setpoint (rate at which the water
temperature may change within one minute in Cooling)
5
hsp1
35 to 85
70
°C
Heating Setpoint 1
Heating setpoint 1 (used during occupied periods)
6
hsp2
35 to 85
70
°C
Heating Setpoint 2
Heating setpoint 2 (used during unoccupied periods)
7
hramp_sp
0.1 to 11.1
0.6
^C
Heating Ramp Loading Heating ramp loading setpoint (rate at which the water
temperature may change within one minute in Heating)
8
cauto_sp
3.9 to 50
23.9
°C
Cool Changeover Setpt Not applicable to this unit
9
hauto_sp
0 to 46
17.8
°C
Heat Changeover Setpt Not applicable to this unit
10
w_sct_sp
26.7 to 60
35
°C
Water Val Condensing
Stp
Water valve condensing setpoint
11
lim_sp1
0 to 100
100
%
Switch Limit Setpoint 1 Demand limit setpoint 1
12
lim_sp2
0 to 100
100
%
Switch Limit Setpoint 2 Demand limit setpoint 2
13
lim_sp3
0 to 100
100
%
Switch Limit Setpoint 3 Demand limit setpoint 3
*Depends on the selected language (English by default).