background image

The DAY button moves between the weekdays, (MoTuWeThFr)
and the weekend (SaSu) selections. A different schedule may be
set for the weekdays and the weekend.

You may exit programming at any time by pressing the
HOLD/END button.

PROGRAMMING A WEEKLY COMFORT SCHEDULE:

1. Press the PROGRAM button. The word PROGRAMMING

appears on the display and the words SET TIME flash on the
display. MoTuWeThFr or SaSu and the present period icons
will appear on the display. The current mode (HEAT or
COOL) will also show. Use the DAY button to select
weekdays and the PROGRAM button to select MORNING.

2. Press the UP or DOWN button to set the start time for

MORNING (box 1 value).

3. Press the TIME/TEMP button until COOL is on and SET

TEMP flashes on the display.

4. Press the UP or DOWN button to select the cooling tempera-

ture set point (box 2 value).

5. Press the TIME/TEMP button until HEAT is on and SET

TEMP flashes on the display.

6. Press the UP or DOWN buttons to select the heating tempera-

ture set point (box 3 value).

7. Press the PROGRAM button to advance to the next time

period. Enter time and temperature settings from boxes 4
through 12 for the periods DAY, EVE, and NIGHT by
following steps 2-6 above.

8. Press the DAY button to change between weekday and

weekend programming. To set the weekend schedule, repeat
steps 2 through 7, entering values in boxes 13 though 24.

9. Press END/HOLD to exit the programming mode.

MODIFYING YOUR WEEKLY COMFORT SCHEDULE

If you choose to change any of your weekly schedule, press
PROGRAM at any time. You will enter the programming schedule
at the present day, present mode, but always in the morning period.
You are ready to set the new starting time for the morning period.
One press of the TIME/TEMP button and you are ready to set the
new temperature. Press HOLD/END and you are finished.

OVERRIDING YOUR COMFORT SCHEDULE

There are two ways to override your comfort schedule:

Method 1—Manual Operation

By pressing the HOLD/END button to turn on the HOLD icon, the
thermostat will maintain the current temperature settings and
ignore the comfort schedule for an indefinite period of time. The
word HOLD will appear in the display. Press the HOLD/END
button a second time and the thermostat will return the temperature
settings

to

the

programmed

comfort

schedule.

Pressing

HOLD/END will not alter your programmed comfort schedule.

Method 2—Temporary Override

At the first press of the UP or DOWN button, the current
temperature setting will appear on the display. Pressing the UP or
DOWN button again will temporarily change the set point as
needed. At the next programmed time, the programmed comfort
schedule will resume.

INSTALLATION, START-UP,

AND OPERATING INSTRUCTIONS

INTRODUCTION

The Standard Programmable Thermostat is an electronic 24-vac,
manual changeover wall mount thermostat. This thermostat uses
two set points to maintain and control room temperature in both
the heating and air conditioning modes. The thermostat is designed
to ma/- 2 degrees (F) accuracy. No batteries are required;
program schedule, temperature, fan, mode, and installer configu-
ration settings are preserved with power off.

INSTALLATION CONSIDERATIONS

AIR CONDITIONER MODEL

The Standard Programmable AC (air conditioner model only)
thermostat may be wired with or without connecting a common
wire between the indoor equipment and the thermostat. However,
it is recommended to use a common wire whenever possible.
Without a common wire this thermostat becomes

power stealing.

This means it will need to steal a small amount of power from the
equipment to which it is connected.

NOTE:

All Carrier equipment, with the exception of the Ther-

mostat Conversion Kit, TSTATXXCNV10, is compatible with this
thermostat in both power stealing and non-power stealing connec-
tions.

HEAT PUMP MODEL

The Standard Programmable HP (heat pump) thermostat is not
power stealing and MUST have both R and C wires connected to
operate properly. This thermostat uses a green LED to indicate
auxiliary heat and emergency heat operation.

INSTALLATION

Step 1—Thermostat Location

Thermostat should be mounted:

Approximately 5 ft (1.5m) from floor.

Close to or in a frequently used room, preferably on an inside
partitioning wall.

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading
to the outside.

Exposed to direct light and heat from a lamp, sun, fireplace, or
other heat-radiating object which may cause a false reading.

Close to or in direct airflow from supply registers and return-air
grilles.

In areas with poor air circulation, such as behind a door or in
an alcove.

Table 1—Programming Table

ENERGYSTAR FACTORY DEFAULTS

NEW COMFORT SCHEDULE

PERIOD

TIME

COOL

HEAT

MoTuWeThFr

TIME

COOL

HEAT

SaSu
TIME

COOL

HEAT

MORNING

6:00 A.M.

78

68

1)

2)

3)

13)

14)

15)

DAY

8:00 A.M.

85

60

4)

5)

6)

16)

17)

18)

EVE

5:00 P.M.

78

68

7)

8)

9)

19)

20)

21)

NIGHT

10:00 P.M.

82

60

10)

11)

12)

22)

23)

24)

2

Summary of Contents for Standard Programmable Thermostat

Page 1: ...ime appears on the display press the HOLD END button NOTE If you choose not to press the HOLD END button the thermostat will automatically exit the time setting mode after 10 sec SETTING THE CURRENT DAY 1 Press the DAY button to advance to the correct day MANUAL OPERATION TO OPERATE MANUALLY WITHOUT THE PRO GRAMMED COMFORT SCHEDULE Press the HOLD END button to make the HOLD icon appear Then follow...

Page 2: ...mporary Override At the first press of the UP or DOWN button the current temperature setting will appear on the display Pressing the UP or DOWN button again will temporarily change the set point as needed At the next programmed time the programmed comfort schedule will resume INSTALLATION START UP AND OPERATING INSTRUCTIONS INTRODUCTION The Standard Programmable Thermostat is an electronic 24 vac ...

Page 3: ...llowing options are available OPTION 1 ANTICIPATOR VALUE ADJUSTMENT This adjustment controls the sensitivity and cycle rate of the thermostat Higher numbers decrease the cycle rate Lower num bers increase the cycle rate However this feature will not allow more than 4 equipment cycles per hour or 1 cycle every 15 minutes regardless of setting Values can range from 1 to 3 Factory default setting is ...

Page 4: ...ER In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour or 1 cycle every 15 minutes Both the Y and W outputs have a 15 minute timer that starts counting down when the output is turned on e g if Y output is turned on for 9 minutes and then satisfies it cannot turn back on for another 6 minutes regardless of demand However pressing UP and FAN bu...

Page 5: ...VALVE REVERSING HEAT COOL STAGE 1 HEATING FAN 24 VAC HOT 24 VAC COMM COOLING N A W G R C Y W G R C Y AC THERMOSTAT TYPICAL FAN COIL FURNACE See note 1 O A01400 Fig 3 Typical Heat Only HEATING FAN 24 VAC HOT 24 VAC COMM COOLING N A W G R C W1 G R C Y Y1 AC THERMOSTAT TWO ZONE THERMOSTAT INPUT O A01401 Fig 5 Two Zone with Air Conditioner NOTE 1 It is recommended to use a 5 wire hookup whenever possi...

Page 6: ...iguration Options 1 _____ Anticipator 1 3 factory default 2 2 _____ N A 3 _____ Fahrenheit or Celsius F or C factory default F 4 _____ Fan On with W Off or On factory default Off 5 9 _____ N A 10 _____ O reversing valve On with Heat or Cool H or C factory default C 11 12 _____ N A 13 _____ Room Temperature Offset 5 to 5 factory default 0 C Schedule MORNING DAY EVE NIGHT TIME HEAT COOL TIME HEAT CO...

Page 7: ...7 ...

Page 8: ... tstat 26si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc miscPC 101 Catalog No O3TS TA32 Printed in U S A Form TSTAT 26SI Pg 8 9 01 Replaces TSTAT 24SI ...

Reviews: