Step 2—Install Thermostat

Before installing thermostat, turn off all power to unit. There
may be more than 1 disconnect. Electrical shock can cause
personal injury or death.

1. Turn OFF all power to unit.

2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, one at a time.

Be careful not to allow wires to fall back into wall.

c. As each wire is disconnected, record wire color and

terminal marking.

d. Discard or recycle old thermostat.

NOTE:

Mercury is a hazardous waste and MUST be disposed of

properly.

3. Separate front and back plastic assembly of thermostat.

4. Route thermostat wires through hole in mounting base. Level

mounting base against wall (for aesthetic value only, thermo-
stat need not be leveled for proper operation) and mark wall
through 2 mounting holes.

5. Drill two 3/16-in. mounting holes in wall where marked.

6. Secure back plate to wall with 2 anchors and screws provided

making sure all wires extend through hole in plastic.

7. Connect wires to proper terminal location on backplate.

8. Push any excess wire back into wall. Seal hole in wall to

prevent air leaks. Leaks can affect thermostat operation. Any
excess wire left inside thermostat casing may also affect
thermostat operation by interfering with airflow across the
temperature sensor.

9. Snap thermostat together making sure assembly is secure.

10. Turn ON power to unit.

On power up, depending on the thermostat model being used, the
LCD readout will display either, AC for air conditioner model
(1-stage heat/1-stage cool), or HP for heat pump model (2-stage
heat/1-stage cool).

Step 3—Set Thermostat Configuration

Available thermostat configuration options and their numbers are:

Option 1 -- Anticipator adjustment

Option 2 -- Not available

Option 3 -- Fahrenheit or Celsius operation

Option 4 -- Enable fan (G) ON with heat (W)

Options 5 through 9 -- Not available

Option 10 -- O (reversing valve) On with Heat or Cool (present on
Heat Pump model only)

Options 11 and 12 -- Not available

Option 13 -- Room temperature offset adjustment

An explanation for each configuration option is as follows.

TO ENTER THE CONFIGURATION MODE:

Press and hold FAN button for approximately 10 sec until room
temperature disappears and the display reads

1

and is flashing.

You are now in configuration mode.

NOTE:

If HOLD/END button is pressed, or if no button is

pressed for 3 minutes, the thermostat will exit configuration mode
and return to normal operation. To re-enter configuration mode,
the FAN button must be pressed and held for 10 sec again.

While in configuration mode, the following options are available:

OPTION 1—ANTICIPATOR VALUE ADJUSTMENT

This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the cycle rate. Lower num-
bers increase the cycle rate. However, this feature will not allow
more than 4 equipment cycles per hour (or 1 cycle every 15
minutes), regardless of setting. Values can range from 1 to 3.
Factory default setting is 2. This default selection will provide
optimum performance in nearly all installations. Try this setting
first. Do not change setting unless there is evidence or need to do
so. Unlike conventional anticipators, this setting is not to be
determined by current draw. There is no need to measure, know, or
compensate for current.

TO SELECT:

1. Enter configuration mode if not already there (see above).

2. Use UP and DOWN buttons to make the large (now flashing)

display indicate 1.

3. Press the TIME/TEMP button once to flash the small display.

4. Use UP and DOWN buttons to move between 1, 2, or 3 on the

small display. Factory default is 2.

5. Press TIME/TEMP button again to flash the large display for

selection of another option, or press HOLD/END TO exit the
configuration mode.

OPTION 3—FAHRENHEIT/CELSIUS SELECTION

This selection operates the thermostat in either Fahrenheit or
Celsius.

TO SELECT:

1. Enter configuration mode if not already there (see above).

2. Use UP and DOWN buttons to make the large (now flashing)

display indicate 3.

3. Press TIME/TEMP button once to flash the small display.

4. Use UP and DOWN buttons to move between F or C on the

small display. Factory default is F.

5. Press TIME/TEMP button again to flash the large display for

selection of another option, or press HOLD/END to exit the
configuration mode.

OPTION 4—G (FAN) ON WITH W (HEAT) SELECTION

This selection determines whether G (fan) output is to be ON or
OFF when W (furnace or strip heat) output is ON. Most furnaces
and fan coils manage their own blowers and do not require a
separate G signal. For these applications, select OFF. Some
auxiliary heaters require a separate G signal from the thermostat to
turn on the blower. In this case, select ON.

TO SELECT:

1. Enter configuration mode if not already there (see above).

2. Use UP and DOWN buttons to make the large (now flashing)

display indicate 4.

3. Press TIME/TEMP button once to flash the small display.

4. Use UP and DOWN buttons to move between ON or OF (off)

on the small display. Factory default is OF (off).

5. Press TIME/TEMP button again to flash the large display for

selection of another option, or press HOLD/END to exit the
configuration mode.

OPTION 10—O (REVERSING VALVE) ON WITH HEAT
OR COOL SELECTION

This selection is only available on heat pump model thermostats.
This selection determines whether the reversing valve is energized
in the heating or cooling mode.

3

Summary of Contents for Standard Programmable Thermostat

Page 1: ...ime appears on the display press the HOLD END button NOTE If you choose not to press the HOLD END button the thermostat will automatically exit the time setting mode after 10 sec SETTING THE CURRENT DAY 1 Press the DAY button to advance to the correct day MANUAL OPERATION TO OPERATE MANUALLY WITHOUT THE PRO GRAMMED COMFORT SCHEDULE Press the HOLD END button to make the HOLD icon appear Then follow...

Page 2: ...mporary Override At the first press of the UP or DOWN button the current temperature setting will appear on the display Pressing the UP or DOWN button again will temporarily change the set point as needed At the next programmed time the programmed comfort schedule will resume INSTALLATION START UP AND OPERATING INSTRUCTIONS INTRODUCTION The Standard Programmable Thermostat is an electronic 24 vac ...

Page 3: ...llowing options are available OPTION 1 ANTICIPATOR VALUE ADJUSTMENT This adjustment controls the sensitivity and cycle rate of the thermostat Higher numbers decrease the cycle rate Lower num bers increase the cycle rate However this feature will not allow more than 4 equipment cycles per hour or 1 cycle every 15 minutes regardless of setting Values can range from 1 to 3 Factory default setting is ...

Page 4: ...ER In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour or 1 cycle every 15 minutes Both the Y and W outputs have a 15 minute timer that starts counting down when the output is turned on e g if Y output is turned on for 9 minutes and then satisfies it cannot turn back on for another 6 minutes regardless of demand However pressing UP and FAN bu...

Page 5: ...VALVE REVERSING HEAT COOL STAGE 1 HEATING FAN 24 VAC HOT 24 VAC COMM COOLING N A W G R C Y W G R C Y AC THERMOSTAT TYPICAL FAN COIL FURNACE See note 1 O A01400 Fig 3 Typical Heat Only HEATING FAN 24 VAC HOT 24 VAC COMM COOLING N A W G R C W1 G R C Y Y1 AC THERMOSTAT TWO ZONE THERMOSTAT INPUT O A01401 Fig 5 Two Zone with Air Conditioner NOTE 1 It is recommended to use a 5 wire hookup whenever possi...

Page 6: ...iguration Options 1 _____ Anticipator 1 3 factory default 2 2 _____ N A 3 _____ Fahrenheit or Celsius F or C factory default F 4 _____ Fan On with W Off or On factory default Off 5 9 _____ N A 10 _____ O reversing valve On with Heat or Cool H or C factory default C 11 12 _____ N A 13 _____ Room Temperature Offset 5 to 5 factory default 0 C Schedule MORNING DAY EVE NIGHT TIME HEAT COOL TIME HEAT CO...

Page 7: ...7 ...

Page 8: ... tstat 26si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab misc miscPC 101 Catalog No O3TS TA32 Printed in U S A Form TSTAT 26SI Pg 8 9 01 Replaces TSTAT 24SI ...

Reviews: