background image

IM-40MBDQ-05                                                                            Specifications subject to change without notice.                                                                                         

19

Step 7 - Setting Static Pressure or Automatic Airflow

The indoor ducted units can be programmed for different static 

pressures settings or airflows and the factory default setting is 

SP1. Use the following steps to set the static pressure or 

Automatic Airflow

 using the Wired Remote Controller or the 

Wireless Remote Controller according to the installation 

conditions.

WHEN USING THE KSACN0501AAA WIRED 
CONTROLLER:

• The external static pressure can be manually changed to the fan

curves SP1, SP2, SP3, SP4.

• Use the Automatic Airflow 

“AF”

 Adjustment function to 

automatically identify the static pressure and regulate the airflow 

amount.

Follow these instructions to configure:

1. Ensure the test run is done with a dry coil. If the coil is not dry, run

the unit for 2 hours in the 

FAN ONLY

 mode to dry the coil.

2. Check that both the power supply wiring and the duct installation

have been completed. Check that dampers are properly positioned.

Check that the air filter is properly attached to the air inlet side

passage of the unit.

3. If there is more than one air inlet and/or outlet, adjust the dampers

so that the airflow rate of each air inlet and outlet conforms to the

designed airflow rate. Ensure the unit is in 

FAN ONLY

 mode.

Press and set the 

Airflow Adjustment  “AF” 

on the remote

controller to adjust the airflow rate from 

H

 to 

L

. Turn the indoor

unit 

OFF

 with the Wired Controller.

4. Set the parameters for airflow adjustment. When the system is

OFF

, perform the following steps:

a.

Press and hold 

COPY

 for approximately 4 seconds

b.

Press “

+

” or “

-

” to scroll through the menu and make a

selection, either 

SP

 or 

AF

.

NOTE: 

T1, T2, T2b, T3, T4 are sub-menus for thermistors. 

DO NOT select to set the external static pressure.

Fig. 53 — Wired Controller Menu Selection

1. If setting the external static pressure manually, select 

SP 

and press

CONFIRM

. Select the 

SP

 number (SP1, SP2, SP3, SP4 

 see

static pressure Table 13 and curves (Figs. 55 through 61)). Power

down the unit to lock in the selection.

2. If choosing the 

AUTOMATIC AIRFLOW ADJUSTMENT

 

function, select 

AF 

and press 

CONFIRM

. The system starts the 

fan for the airflow automatic adjustment. The 

ON 

indicator flashes 

when the fan runs during the 

AUTOMATIC AIRFLOW 

ADJUSTMENT

. After 3 to 6 minutes, the system stops operating 

once the 

AUTOMATIC AIRFLOW ADJUSTMENT

 is 

complete.

Fig. 54 — Automatic Airflow ON signal

NOTE: 

The external static pressure can also be selected using 

the wireless remote controller (RG57F3(B)/BGEFU1), 

included with the indoor unit, by pointing it toward the indoor 

unit’s Infrared Receiver typically located inside the control 

box. Refer to the wireless remote controller service manual for 

further instructions.

WHEN USING THE 24V INTERFACE KSAIC** 

The wireless remote controller, wired controllers KSACN** 

and Wi-Fi kits would be disabled. Since a wired controller is 

required to setup the static pressure of the indoor ducted units, 

the 24V interface must be temporarily bypassed using the steps 

below:

1. Turn off the power to the unit
2. On the 24V interface, disconnect the plugs from the CN11 (to

Outdoor) and CN12 (to Indoor) connections.

3. Sizes:

a.

For sizes 9K-24K only: 

Add a jumper between the indoor 

S terminal to the outdoor S terminal.

b.

For sizes 36K-58K only: 

Disconnect S1 and S2 from the 

24V interface (CN8 and CN9) and splice together 

S1

 from 

outdoor to 

S1

 from indoor and 

S2

 from outdoor to 

S2

 from 

indoor. 

4. Connect the Wired Controller (KSACN0501AAA) and follow the

external static pressure setup.

5. Once the static pressure is adjusted, disconnect the wired controller 

6.

Sizes

:

a.

For sizes 9K-24K only:

 Remove the S jumper from the 

terminal block.

b.

For sizes 36K-58K only: 

Remove the splice and reconnect

S1

 and 

S2

 back to the 24V interface accordingly.

7. Reconnect the plugs back to CN11 (to outdoor) and CN12 (to 

indoor) accordingly. 

8.

Restore power to the unit

.

NOTE: 

When a system uses the 24V interface, the indoor 

unit’s fan speed defaults to 

AUTO

 with the indoor unit’s 

default logic.

 

ON

is running during the 

AUTOMATIC AIRFLOW ADJUSTMENT

Do not use the 

AUTOMATIC AIRFLOW ADJUSTMENT

 with the 

remote control if using booster fans, an outdoor air processing unit, or a 
HRV via duct.
If the ductwork or static pressure have been changed, reset the 

AUTOMATIC AIRFLOW ADJUSTMENT

 following steps 3 and 4.

CAUTION

DUCT SIZING

Duct work must be properly sized using the standard duct sizing 
program practices. Failure to do so could result in inadequate 
airflow to the target area. It is recommended to follow the 
standard practices listed on the ACCA Manual D for designing 
Duct Systems.

CAUTION

Summary of Contents for Performance 40MBDQ09---3

Page 1: ...NSTALLATIONS 7 MAINTENANCE CLEARANCES 7 INSTALLATION 8 Step 1 Check Equipment 8 Step 2 Mount Unit 8 Step 3 Installing Ductwork 10 Step 4 Condensate Drain Installation 11 Step 5 Electrical Connections 14 WIRING 15 ELECTRICAL DATA 16 CONNECTION DIAGRAMS 16 Step 6 Refrigerant Piping 17 WIRELESS REMOTE CONTROLLER INSTALLATION 18 WIRED REMOTE CONTROLLER INSTALLATION 18 START UP 18 Step 7 Setting Static...

Page 2: ...ations only WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing unit always turn off all power to the unit There may be more than one disconnect switch Turn off the accessory heater power if applicable Lock out and tag switch with a suitable warning label WARNING EXPLOSION HAZARD Failure to follow this warning c...

Page 3: ...3 Indoor Unit Representation NOTES If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall and enters the indoor unit Doing so helps ensure rain drips from the connection pipe before it enters the wall Piping and the interconnecting wiring are field suppli...

Page 4: ...Heating Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 PRODUCT INSTALLATION Installation must be performed by an authorized dealer or specialist A defective installation can cause water leakage electrical shock or fire The installation must be performed according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America install...

Page 5: ...47 27 56 5 51 36 46 1 97 6 89 39 41 8 98 0 2 44 88 23 54 3 15 5 91 5 12 6 1 87 mm 1100 249 774 700 140 926 50 175 1001 228 5 1140 598 80 150 130 155 39 4 36 In 53 54 9 8 30 47 27 56 5 51 46 69 1 97 6 89 49 65 8 98 0 2 55 12 23 54 3 15 5 91 5 12 6 1 106 mm 1360 249 774 700 140 1186 50 175 1261 228 5 1400 598 80 150 130 155 48 3 48 In 47 24 11 81 34 41 31 5 4 84 41 1 1 97 8 94 43 35 11 02 0 2 48 82 ...

Page 6: ...tions subject to change without notice IM 40MBDQ 05 DIMENSIONS CONT Fig 6 Indoor Unit Size 58K LEFT VIEW BOTTOM VIEW REAR VIEW Air Inlet TOP VIEW RIGHT VIEW FRONT VIEW Air Outlet NOTE Size 58K draw through system ...

Page 7: ...the connection end and 2 inches on the opposite end CAPACITY KBTU B 9K 11 81in 30cm 12K 11 81in 30cm 18K 11 81in 30cm 24K 11 81in 30cm 36K 11 81in 30cm 48K 15 75in 40cm 58K 15 75in 40cm Maintenance space Left side Right side Strong and durable ceiling Indoor unit m c 0 3 n i 8 1 1 m c 0 1 n i 4 0 8in 2cm 0 8in 2cm 11 8in 30cm n i 2 8 m c 0 5 2 Floor Service access Ceiling When there is no ceiling ...

Page 8: ...condensate pan under the entire unit Some localities may allow as an alternative the running of a separate secondary condensate line Consult the local codes for additional restrictions or precautions Ceiling Mounting Options Different ceiling types call for different mount applications Wood Place the wood mounting across the roof beam then install the hanging screw bolts Fig 11 Wood Mounting New C...

Page 9: ...t Insert the suspension bolts into the unit s hanging holes Fasten the bolts with the washers and nuts provided Fig 17 Suspension bolt 3 Mount the indoor unit onto the hanging screw bolts with a block Position the indoor unit with a level indicator to prevent leaks 4 Adjust the unit s height until the bottom is level with the false ceiling Leave enough space to provide an adequate pitch for the dr...

Page 10: ...ges provided on the unit Secure the canvas tie to the indoor unit s flange using the proper fasteners for the type of duct used and the seal duct to unit joint Use canvas duct flexible connectors between the ductwork and the unit to prevent transmission of vibration Maintain an adequate distance between the return and supply diffusers to avoid short circulation of air within the space The filter i...

Page 11: ...d the lift pipe must be less than 8in 20cm An incorrect installation could allow water to flow back into the unit and flood To prevent air bubbles keep the drain hose horizontal or slightly upward See letter A Figure 28 1 Cover the drain hose with heat insulation to prevent condensation and leakage 2 Attach the mouth of the drain hose to the unit s outlet pipe Sheath the mouth of the hose and clip...

Page 12: ...l pump to CN13 PUMP pin and plug the water level sensor cable to CN5 WATER to enable the pump see Fig 34 Fig 30 Condensate lift pump installation sizes 09K 12K Fig 31 Condensate lift pump installation size 18K 3 Sizes 24K 36K 48K and 58K have a built in condensate lift pump Drain connections A B and C are covered with caps Connect the drainpipe to connector D see Fig 32 Fig 32 Connection of drain ...

Page 13: ...these steps to perform the test 1 Remove the test cover by rotating it counter clockwise see Fig 38 2 Using a piece of tubing or pipe to fill the condensate lift pump reservoir with 70 oz of water see Fig 39 3 Turn the unit ON in the COOLING mode and the condensate lift pump turns on Watch the end of the drain pipe for any water NOTE It may take some time for the water to travel depending on the l...

Page 14: ...d wiring diagram located on the cover of the electric control box Fig 41 Control Box Ferrite Core Magnetic Ring If supplied and packed with the accessories wrap the signal wires between the indoor unit and outdoor unit after installation and around the Ferrite core twice Fig 42 Ferrite Core Magnetic Ring 6 Clamp the cable with the cable clamp Ensure the cable is not loose as to not pull on the u l...

Page 15: ...o the outdoor unit The field supplied power wiring from the outdoor unit to the indoor unit consists of three 3 wires and provides the power for the indoor unit Two wires are high voltage AC power and one is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 stranded with a ground Communication Wiring A separate shielded stranded copper conductor only with a 600 volt ...

Page 16: ... 0 18 130 12 1 11 0 18 130 18 1 2 0 27 200 24 1 2 0 27 200 36 2 45 0 56 420 48 3 2 0 75 560 58 3 65 0 952 1 000 S L1 L2 208 230 1 60 Power Supply Main L1 208 230 1 60 L2 S L1 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indoor Signal High GND Ground Power to Indoor Unit 208 230 1 60 GND FIELD POWER SUPPLY Voltage Indoor Signal High Voltage 208 230 1 60 L1 L2 FIELD PO...

Page 17: ... Tighten the flare nut 4 Connect the drain line Ensure there are absolutely no traps in the drain line anywhere in its length Ensure the drain line pitches down and insulated up to the outside wall NOTE For applications where gravity cannot be used for drainage a condensate pump accessory is available Consult the condensate pump installation instructions for more information Refrigerant tubes and ...

Page 18: ...le supplied with the wired controller to plug into the 5 pin connector from the IR receiver located in the control box see figure 51 For setup instructions refer to the wired remote controller installation manual START UP Test Operation After completing the gas leak and electrical safety check perform the test operation see Fig 52 Fig 52 IR Receiver Display Panel IR Receiver Display Panel 1 Press ...

Page 19: ...r flashes when the fan runs during the AUTOMATIC AIRFLOW ADJUSTMENT After 3 to 6 minutes the system stops operating once the AUTOMATIC AIRFLOWADJUSTMENT is complete Fig 54 Automatic Airflow ON signal NOTE The external static pressure can also be selected using the wireless remote controller RG57F3 B BGEFU1 included with the indoor unit by pointing it toward the indoor unit s Infrared Receiver typi...

Page 20: ...32 44 0 50 12 In WG 0 064 0 10 0 136 0 20 0 0 20 Pa 16 25 34 50 0 50 18 In WG 0 096 0 168 0 288 0 392 0 0 40 Pa 24 42 72 98 0 100 24 In WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 160 0 160 58 In WG 0 296 0 416 0 584 0 8 0 0 80 Pa 74 104 146 200 0 200 Factory Setting SYSTEM S...

Page 21: ...18 100 59 1200 706 1100 647 1000 588 900 529 800 471 700 412 600 353 500 294 400 235 300 176 200 118 100 59 1200 706 1100 647 1000 588 900 529 800 471 700 412 600 353 500 294 400 235 300 176 200 118 100 59 1200 706 1100 647 1000 588 900 529 800 471 700 412 600 353 500 294 400 235 300 176 200 118 100 59 External static pressure pa in w c 10 20 25 30 40 50 0 10 0 12 0 16 0 20 0 08 0 04 0 External st...

Page 22: ...essure pa in w c 10 20 25 30 40 50 0 10 0 12 0 16 0 20 0 08 0 04 0 External static pressure pa in w c 10 20 25 30 40 50 0 10 0 12 0 16 0 20 0 08 0 04 0 1200 706 1100 647 1000 588 900 529 800 471 700 412 600 353 500 294 400 235 300 176 200 118 100 59 Air volume m3 h CFM 1200 706 1100 647 1000 588 900 529 800 471 700 412 600 353 500 294 400 235 300 176 200 118 100 59 Air volume m3 h CFM 1200 706 110...

Page 23: ... 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 10 E t l t ti i 20 25 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 10 External static pressure pa in w c 20 25 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 0 08 0 04 0 08 0 04 0 08 0 04 1800 1059 1...

Page 24: ... 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 10 External static pressure pa in w c 20 25 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 1800 1059 1600 941 1400 823 1200 706 1000 588 800 471 600 353 400 235 200 118 0 2000 1176 220...

Page 25: ... 3600 2118 2500 1471 1800 1059 1600 941 1400 823 1200 706 1000 588 800 471 600 353 400 235 200 118 0 2000 1176 2200 1294 2400 1412 2600 1529 2800 1647 3000 1765 3200 1882 3400 2000 3600 2118 2500 1471 1800 1059 1600 941 1400 823 1200 706 1000 588 800 471 600 353 400 235 200 118 0 2000 1176 2200 1294 2400 1412 2600 1529 2800 1647 3000 1765 3200 1882 3400 2000 3600 2118 2500 1471 10 External static ...

Page 26: ...atic pressure pa in w c 20 25 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 170 0 68 180 0 72 190 0 76 200 0 80 10 External static pressure pa in w c 20 25 30 60 70 80 90 100 120130140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 170 0 68 180 0 72 190 0 76 2...

Page 27: ...in w c 20 25 30 60 70 80 90 100 120130 140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 170 0 68 180 0 72 190 0 76 200 0 80 10 External static pressure pa in w c 20 25 30 60 70 80 90 100 120 130 140 150160 40 50 110 0 10 0 12 0 16 0 20 0 24 0 28 0 32 0 36 0 40 0 44 0 48 0 52 0 56 0 60 0 64 0 08 0 04 170 0 68 180 0 72 190 0 76 200 0 80 1800 1...

Page 28: ...ce and minimize possible equipment failure it is essential that periodic maintenance be performed on this equipment Consult your local dealer as to the proper frequency of maintenance contract The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools If you do not possess these contact your dealer for maintenance The only consumer service recommende...

Page 29: ... fan speed is out of control 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit 6 times X E5 Evaporator coil temperature sensor T2 open circuit or short circuit 9 times X E8 Dual indoor unit twin model only communication malfunction 10 times X E9 Other twin model malfunction 7 times X EC Refrigerant leakage detection 1 time O F0 Overload Protection 11 times O Fa Indoor un...

Page 30: ...ut incurring obligations Replaces IM 40MBDQ 04 ADVANCED SERVICE AND INSTALLATION FUNCTIONS Refer to the Wireless Remote Controller service manual for access to advanced functions such as Auto Start Temperature Compensation Filter Reminder Indoor Fan Motor Speed Control after set temperature is reached Lowest or Highest Temperature Setting Static Pressure Setting All changes should be performed ONL...

Reviews: