TROUBLESHOOTING
For ease of service, the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units. The
outdoor diagnostic display consists of two LEDs (red and green) on the outdoor unit board and is limited to a few errors. The
indoor diagnostic display is a combination of flashing LEDs on the display panel or the front of the unit. If possible, always check
the diagnostic codes displayed on the indoor unit first before consulting a service technician.
The diagnostic codes, displayed in the indoor and outdoor units, are listed in Table 15
INDOOR UNIT DIAGNOSTIC GUIDES
Table 15 — Indoor Unit Diagnostic Guides
O (light) X (off) «(flash)
For additional diagnostic information, refer to the indoor unit service manual.
OPERATION
LAMP
TIMER LAMP
DISPLAY
LED STATUS
1 time
X
E0
Indoor unit EEPROM parameter error
2 times
X
E1
Indoor / outdoor units communication error
8 times
X
EE
Water level alarm malfunction
4 times
X
E3
Indoor fan speed is out of control
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short circuit
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or short circuit
9 times
X
E8
Dual indoor unit (twin model only) communication malfunction
10 times
X
E9
Other twin model malfunction
7 times
X
EC
Refrigerant leakage detection
1 time
O
F0
Overload Protection
11 times
O
Fa
Indoor unit communication malfunction
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or short circuit
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or short circuit
4 times
O
F3
Compressor discharge temperature sensor T5 open circuit or short circuit
5 times
O
F4
Outdoor unit EEPROM parameter error
6 times
O
F5
Outdoor fan speed is out of control
7 times
O
F6
Compressor low-pressure protection
1 time
«
P0
IPM malfunction or IGBT over-strong current protection
2 times
«
P1
Over voltage or over low voltage protection
3 times
«
P2
High temperature protection of compressor top diagnosis and solution (9K,12K models only)
4 times
«
P3
Outdoor low temperature protection
5 times
«
P4
Inverter compressor drive error
7 times
«
P6
Compressor low-pressure protection
8 times
«
P7
Outdoor IGBT sensor error