VVT Zone Controller
27
Wiring field-supplied actuators to the analog output
You can wire a high-torque actuator or parallel actuators to the controller's 0–10 Vdc analog output.
High-torque actuators
You can wire one of the following Belimo actuators to the VVT Zone Controller's analog output instead of using
the controller's built-in, 35 in.-lb actuator.
NMX24-MFT P-10028
90 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
AMX24-MFT P-10028
180 in.-lb actuator with 0–10 Vdc control and 0–10 Vdc feedback
1
Install the actuator according to the manufacturer's instructions.
2
Wire the actuator to the controller using the diagram below.
NOTE
For proper operation and to prevent damage to the devices, use the same polarity for the actuator's
power and the VVT Zone Controller's power.