VVT Zone Controller
39
4
For each zone in the system that was balanced, go to its
Pressure Dependent Control
>
Details
tab, then
click
Automatic Control
to return the zone to normal control.
5
In the tree, select the air source controller, then do one of the following.
a)
For an RTU Open or WSHP Open controller, go to
Properties
>
Equipment
>
Configuration
>
Service
Configuration
>
Service Test
and disable
Service Test
and
Fan Test
b)
For any equipment whose wiring was disconnected to insure that only the fan only was running,
reconnect it the wires for normal operation.
.
CAUTION
You must complete steps 4 and 5 to prevent loss of temperature control to the space and to
maintain normal operation of the system.