VVT Zone Controller
53
Point Name/Description
Default/Range
Local Sensor Calibration
Space Temperature
R:
– The current space temperature.
-56 to 245°F
Space Temp Calibration
D:
– A calibration offset value to allow the local space
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
R:
0°F
-9.9 to 10°F
Supply Air Temperature
R:
– The current supply air temperature.
-56 to 245°F
Supply Air Temp Calibration
D:
– A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
R:
0°F
-9.9 to 10°F
Space Relative Humidity –
R:
Displays the current value of relative humidity sensor, if
present.
0 to 100%
Relative Humidity Calibration
– You can enter a calibration offset for the relative
humidity. The offset is added to or subtracted from the controller's RH input value, and
the calculated value is shown in the
Status
>
Space Relative Humidity
D:
.
R:
0%
-15 to 15%rh
Setpoints
i-Vu / Field Assistant:
Navigation:
BACview:
Properties
>
Equipment
>
Configuration
>
Setpoints
HOME
>
CONFIG
>
SETPOINT
Select a color band on the setpoint graph to see the current setpoints in the
Heating
and
Cooling
fields. See setpoint
descriptions below.