92
Table 68 — Service Directory (cont)
LEGEND
*An “X
” in the Keypad Entry column indicates that the read-
ing can be forced by entering a value and then pressing
.
The valid force ranges are listed in the Expansion column.
†For unit size 038, enter “034” for SIZE.
For unit size 048, enter “044” for SIZE.
For unit size 078, enter “074” for SIZE.
For unit size 088, enter “084” for SIZE.
For unit size 104, enter “108” for SIZE.
**Unit control system calculated value.
NOTE: If unit is not configured for a certain subfunction, that sub-
function will not show up when scrolling through values.
SERVICE (cont)
Subfunction
Keypad Entry
Display
Description
10
ECONOMIZER
(cont)
PES1 X (034-078)
PES X (088,104)
Power exhaust set point 1
PES2 X
Power exhaust set point 2 (Sizes 034-078 Only)
SMR X
Submaster reference value
X
*
SMR X
Submaster reference value forced (40 to 120)
DPSP X
Damper set point (F)
X
*
DPSP X
Damper set point forced (45 to 80 F)
OAE X
Outdoor air enthalpy value
RAE X
Return air enthalpy value
11
HEAT
HEAT
Configure staged heat
MLG X
Master loop gain value
SMG X
Submaster gain value
SMR X
Submaster reference value
X
*
SMR X
Submaster reference value forced (35 to 140)
12
NTFC
NTFC
Configure nighttime free cool (NTFC)
NTLO X
NTFC lockout temp (min. OAT to operate NTFC F)
13
AOSS
AOSS
Configure adaptive optimal start/stop
BLDF X
Building factor value (1 to 100; default = 10)
UOCF X
24-hour unoccupied factor (0 to 99; default = 15)
SETB X
Set point bias (0 to 10; default = 2)
OSMT X
Maximum allowable stop time (10 to 120; default = 60)
14
SPACE
TEMPERATURE
RESET
SPCRESET
Configure space temperature reset
RTIO X
Reset ratio (0 to 10; default = 3)
LIMT X
Reset limit (0 to 20; default = 10)
15
LOADSHED
LOADSHED
Configure loadshed
LSGP X
Loadshed group number (1 to 16; default = 1)
16
IAQ/CFM
IAQ
Configure indoor-air quality
LEVEL X
IAQ priority level (1 = high, 2 = medium, 3 = low; default = 2)
IAQS X
IAQ Set point (0 to 5000 ppm; default = 650)
IAQG X
IAQ gain (–2 to 2)
OCS X
Outdoor air cfm set point
OACG X
Outdoor air cfm gain (.1 to 2.0)
ENTER
ENTER
ENTER
AOSS
— Adaptive Optimal Start/Stop
CFM
— Outdoor-Air CFM Control
Cont
— Continuous
CV
— Constant Volume
DTCC
— Discrete Time Clock Control
Exh
— Exhaust
IAQ
— Indoor-Air Quality
MDP
— Minimum Damper Position
NTFC
— Nighttime Free Cooling
OAC
— Outdoor-Air Cfm Control
OAT
— Outdoor-Air Temperature
Rtn
— Return
Temp
— Temperature
VAV
— Variable Air Volume
ENTER
ENTER