APPENDIX D — BACnet Points List
CCN
TABLE
NAME
CCN
POINT
NAME
BACnet
OBJECT
NAME
EXPANDED NAME
BACnet
OBJECT
TYPE
BACnet
OBJECT
PROPERTIES
BACLink
DEFAULT
TEMPLATE
DISPLAY FORMAT/
ENGINEERING UNITS
STATUS01
SPT
SPT
Space Temperature
AI
RO
Y
–10 to +245 F
SAT
SAT
Supply Air Temperature
AI
RO
Y
–10 to +245 F
RAT
RAT
Return Air Temperature
AI
RO
Y
–10 to +245 F
SFS
SFS
Supply Fan Status
BI
RO
Y
on/off
SF
SF
Supply Fan Relay
BO
RO
Y
on/off
SP
SP
Duct Static Pressure
AI
RO
Y
0.0 to 5.0 in. wg
IGV
IGV
Inlet Guide Vanes
AI
RO
Y
0 to 100%
OAT
OAT
Outside Air Temperature
AI
RO
–40 to +245 F
ECON
ECON
Economizer Damper
AO
RO
Y
0 to 100%
BP
BP
Building Pressure
AI
RO
–0.5 to +0.5 in. wg
EFRF
EFRF
Exhaust/Return Fan
BO
RO
on/off
FLTS
FLTS
Filter Status
BI
RO
dirty/clean
EXTCLK
EXTCLK
External Clock Input
BV
RW
Y
on/off
PED
PED
Power Exhaust Damper
AO
RO
0 to 100%
STATUS02
MM
MM
Motormaster/Fan Stage 1
BO
RO
on/off
FR2
FR2
Condenser Fan Stage 2
BO
RO
on/off
FR3
FR3
Condenser Fan Stage 3
BO
RO
on/off
HS1
HS1
Heat Stage 1
BO
RO
Y
on/off
HS2
HS2
Heat Stage 2
BO
RO
Y
on/off
STATUS03
RH
RH
Return/Space Humidity
AI
RO
0 to 100%
OARH
OARH
Outside Air Humidity
AI
RO
0 to 100%
ENTH
ENTH
Enthalpy Status
BI
RO
hi/low
OAC
OAC
Outside Air CFM
AI
RO
0 to 50,000 CFM
IAQ
IAQ
IAQ (CO
2
)
AI
RO
0 to 5000 PPM
EVAC
EVAC
Evacuation
BV
RW
alarm/norm
PRES
PRES
Pressurization
BV
RW
alarm/norm
PURG
PURG
Smoke Purge
BV
RW
alarm/norm
FSD
FSD
Fire Shutdown
BV
RW
alarm/norm
FRZ
FRZ
Freezestat Status
BI
RO
alarm/norm
HCV
HCV
Heating Valve
AO
RO
0 to 100%
STATUS04
STRST
STRST
Space Temperature Reset
AI
RO
no/yes
UNCHT
UNCHT
Unoccupied Heating
BV
RO
no/yes
UNCCL
UNCCL
Unoccupied Cooling
BV
RO
no/yes
STDBY
STDBY
Unit in Standby
BV
RO
no/yes
OPTST
OPTST
Optimal Start
BV
RO
no/yes
UNOCC
UNOCC
Unoccupied
BV
RO
no/yes
IAQPG
IAQPG
IAQ Purge
BV
RO
no/yes
OPTSP
OPTSP
Optimal Stop
BV
RO
no/yes
OCCHT
OCCHT
Occupied Heating
BV
RO
no/yes
OCCCL
OCCCL
Occupied Cooling
BV
RO
no/yes
OCCFO
OCCFO
Occupied Fan Only
BV
RO
no/yes
NTFCL
NTFCL
Night Time Free Cooling
BV
RO
no/yes
PRESS
PRESS
Pressurization
BV
RO
no/yes
EVACN
EVACN
Evacuation
BV
RO
no/yes
SMKPG
SMKPG
Smoke Purge
BV
RO
no/yes
FIRES
FIRES
Fire Shutdown
BV
RO
no/yes
TIMOV
TIMOV
Timed Override
BV
RO
no/yes
HHOVR
HHOVR
High Humidity Override
BV
RO
no/yes
IAQCL
IAQCL
IAQ/Outdoor Air CFM Ctrl*
BV
RO
no/yes
STATUS05
CMPA1
CMPA1
Compressor A1
BO
RO
Y
on/off
CPSA1
CPSA1
Compressor A1 Status
BI
RO
on/off
ULDA1
ULDA1
Unloader A1
BO
RO
on/off
CMPA2
CMPA2
Compressor A2*
BO
RO
on/off
ULDA2
ULDA2
Unloader A2*
BO
RO
on/off
CPFA1
CPFA1
Compressor A1 Safety
BI
RO
alarm/norm
STATUS06
CMPB1
CMPB1
Compressor B1
BO
RO
Y
on/off
CMPB2
CMPB2
Compressor B2*
BO
RO
on/off
CPSB1
CPSB1
Compressor B1 Status
BI
RO
on/off
ULDB1
ULDB1
Unloader B1
BO
RO
on/off
ULDB2
ULDB2
Unloader B2*
BO
RO
on/off
CPFB1
CPFB1
Compressor B1 Safety
BI
RO
alarm/norm
CPFB2
CPFB2
Compressor B2 Safety*
BI
RO
alarm/norm