91
Table 68 — Service Directory (cont)
SERVICE (cont)
Subfunction
Keypad Entry
Display
Description
6
USER
CONFIGURATION
USER CFG
User configuration
HUSN X
Humidity sensors (0 = None, 1 = Differential [2 Sensors],
2 = Space Override [1 Sensor])
SUSN X
Suction sensors (0 = No, 1 = Yes)
VENT X
Ventilation control (0 = MDP, 1 = IAQ, 2 = CFM, 3 = All)
MMAS X
Motormaster (0 = No, 1 = Yes)
PURG X
Indoor-air quality (0 = Disable, 1 = Enable)
NTEN X
Nighttime free cool (0 = Double, 1 = Enable)
OSEN X
Adaptive optimal start/stop (0 = Disable, 1 = Enable)
DLEN X
Demand limit (0 = Disable, 1 = Enable)
OHEN X
Occupied heating (0 = Disable, 1 = Enable)
RSEN X
Space temperature reset (0 = Disable, 1 = Enable)
DPEN X
Duct pressure control (0 = Disable, 1 = Enable)
FANM X
Fan mode auto/cont (0 = Auto, 1 = Cont)
TSCH X
Timed override schedules (1 = Unit, 2 = DTCC, 3 = Both)
TOVR X
Timed override value (0 to 4 hours)
LLAG X
Lead/Lag option (0 = Disable, 1 = Enable)
7
HEATING
COIL
HEATCOIL
Configure heating coil
MLG X
Master loop gain value
SMG X
Submaster gain value
SCV X
Submaster center value
FOV X
Fan off value (F)
SMR X
Submaster reference value
X
*
SMR X
Submaster reference value forced (35 to 140 F)
8
COOLING
COOLING
Configure cooling parameters
MLG X
Master loop gain value
HHL X
High humidity limit (0 to 99%)
9
DUCT
PRESSURE
DUCTPRES
Configure duct pressure control
MLG X
Master loop gain value
SMG X
Submaster gain value
SCV X
Submaster center value
SMR X
Submaster reference value
X
*
SMR X
Submaster reference value forced (0.0 to 5.0 in. wg)
10
ECONOMIZER
ECONMIZR
Configure economizer
MLG X
Master loop gain value
SMG X
Submaster gain value
SCV X
Submaster center value
MDP X
Minimum damper position (percent open)
ENTER
ENTER