background image

N4H7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

3

In Long-Line Applications, Install Liquid-Line 

Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths greater than

80 ft. (24.38 m) and/or when elevation difference between indoor and

outdoor unit is greater than ±20 ft. (±6.10 m), follow all requirements of

the  Residential  Piping  and  Long-Line  Guideline.  If  required  by

Long-Line Guideline, install LSV kit, part no. NASA001LS, specifically

designed for  R-410A  refrigerant heat  pumps.  LSV should  be installed

within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing toward

outdoor  unit.  Follow  the  Installation  Instructions  included  with

accessory kit. 

IMPORTANT: 

Flow arrow must point toward outdoor unit. 

Make Piping Connections

Outdoor  units  may  be  connected  to  indoor  section  using  accessory

tubing package or field-supplied refrigerant grade tubing of correct size

and  condition.  For  tubing  requirements  beyond  80  ft  (24.4  m),

substantial  capacity  and  performance  losses  can  occur.  Following  the

recommendations  in  the  Residential  Piping  and  Long  Line  Guideline

will reduce these losses.  Refer to 

Table 1

 for accessory requirements.

Refer to 

Table 2

 for field tubing diameters.

There are no buried-line applications greater than 36 in. (914.4 mm)

If refrigerant tubes or indoor coil are exposed to atmosphere, they must

be evacuated to 500 microns to eliminate contamination and moisture in

the system.

Outdoor Unit Connected to Factory Approved Indoor 

Unit:

Outdoor unit contains the correct system refrigerant charge for operation

with  factory  approved,  AHRI  rated,  indoor  unit  with  highest  sales

volume when connected by 15 ft (4.57 m) of field-supplied or factory

accessory  tubing  and  factory-supplied  filter  drier.    Check  refrigerant

charge for maximum efficiency.

Service Valves

Service valves are closed and plugged from the factory. Outdoor units

are shipped with a refrigerant charge sealed in the unit. Leave the service

valves closed until all other refrigerant system work is complete or the

charge will be lost. Leave the plugs in place until line set tubing is ready

to be inserted.
Heat pumps require a piston metering device in the liquid service valve

for proper heating operation. Piston is shipped in the piston body of the

liquid service valve, temporarily held in place with a plastic cap. Do not

remove the plastic cap until line set tubing is ready to be installed.
Refer to 

Fig. 4

  and follow these steps for piston installation:

1. Remove plastic cap holding piston in piston body of liquid service

valve.

2. Check  that  piston  size  (stamped  on  side  of  piston)  matches  with

number listed on unit rating plate. Return piston to piston body of

liquid service valve (either direction).

3. Find plastic bag taped to unit containing copper adapter tube, brass

nut, and plastic washer.

4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube onto liquid service

valve. Tighten nut finger tight, then wrench additional ½ turn only

[15-ft  lbs  (20.3  N-m)].  Over  tightening  may  damage  the  plastic

washer and service valve’s piston body.

A14235

Fig. 4 – Liquid Service Valve with Heating Piston and Adapter Tube

Table 1 – Accessory Usage

Accessory

Required for Low Ambient

Cooling Applications 

(Below 55°F / 12.8°C)

Required for Long Line 

Applications

*

*. For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m)  and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline.

Required for Sea Coast

Applications

(within 2 miles/3.2 km)

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Crankcase Heater

Yes (standard)

Yes (standard)

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

(standard w/factory approved

indoor unit)

Yes

(standard w/factory approved

indoor unit)

Yes

(standard w/factory approved

indoor unit)

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Residential Piping

and Long Line Guideline

No

Low-Ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

WARNING

!

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury or death.

Relieve  pressure  and  recover  all  refrigerant  before  system  repair  or

final unit disposal. 

Use  all  service  ports  and  open  all  flow-control  devices,  including

solenoid valves.

Federal  regulations  require  that  you  do  not  vent  refrigerant  into  the

atmosphere.    Recover  refrigerant  during  system  repair  or  final  unit

disposal

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.

If ANY refrigerant tubing is buried, provide a 6-in (152.4 mm). vertical

rise  at  service valve.   Refrigerant tubing  lengths  up  to  36-in   (914.4

mm). may be buried without further special consideration.  Do not bury

lines longer than 36 in (914.4 mm). 

Summary of Contents for N4H7T

Page 1: ...opriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refri...

Page 2: ...pace for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1...

Page 3: ...ton body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for...

Page 4: ...h a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in...

Page 5: ...readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided a...

Page 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to...

Page 7: ...5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Opera...

Page 8: ...or temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8...

Page 9: ...nit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation an...

Page 10: ...ved A Carrier Company Edition Date 03 22 Catalog No N4H7T 01SI Replaces New N4H7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without not...

Reviews: