N4H7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

A12258

Fig. 9 – Thermidistat Wiring with Fan Coil

and 2-Stage Heat Pump

A12259

Fig. 10 – Thermidistat with Variable Speed Furnace 

and 2--Stage Heat Pump

A09306

Final Wiring Check

IMPORTANT: 

Check  factory  wiring  and  field  wire  connections    to

ensure terminations are secured properly. Check wire routing to ensure

wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

All sizes are equipped with a crankcase heater. Furnish power to heater a

minimum  of 24  hours before starting unit. To furnish power to heater

only,  set thermostat  to OFF and close  electrical disconnect to outdoor

unit. 
A crankcase heater is required if refrigerant tubing is longer than 80 ft.

(24.4 m), or when outdoor unit is 20 ft. (6.1 m) below the indoor unit.

Refer to the Residential Piping and Long Line Guideline.

Install Electrical Accessories

Refer  to  the  individual  instructions  packaged  with  kits  or  accessories

when installing.

Airflow Selections (ECM Furnaces)

The ECM Furnaces provide blower operation to match the capacities of

the  compressor  during  high  and  low  stage  cooling  operation.  Tap

selections on the furnace control board enable the installing technician to

select  the  proper  airflows  for  each  stage  of  cooling.  Below  is  a  brief

summary of the furnace airflow configurations

1. The Y2 call for high stage cooling energizes the “Cool” tap on the

control board. The grey wire from cool tap is connected to tap 5 on

the  motor.  Refer  to  the  furnace  Product  Data  to  find  the

corresponding airflow. If the airflow setting for high cooling needs

to be switched from tap 5 to a different tap, jumper a connection

from  the  cool  tap  to  the  desired  tap  so  that  the  Y2  signal  is

communicated via the cool tap to the desired speed tap.

2. The Y1 call for low stage cooling energizes the “Fan” tap on the

control board. The red wire from the fan tap is connected to tap 1 on

the  motor.  Refer  to  the  furnace  Product  Data  to  find  the

corresponding airflow. If the airflow setting for low cooling needs

to be switched from tap 1 to a different tap, jumper a connection

from  the  Fan    tap  to  the  desired  tap  so  that  the  Y1  signal  is

communicated  via  the  Fan  tap  to  the  desired  speed  tap. The Y1

setting will also govern the continuous fan airflow for the furnace.

Refer to the literature for the furnace for further details.

Airflow Selection for Variable Speed Furnaces 

(non-communicating)

The  variable  speed  furnaces  provide  blower  operation  to  match  the

capacities  of  the  compressor  during  high  and  low  stage  cooling

operation. The furnace control board allows the installing technician to

select the proper airflows for each stage of cooling. Below is a summary

of  required adjustments.  See furnace  installation  instructions  for more

details: 

1. Turn SW1-5 ON for 400 CFM/ton airflow or OFF for 350 CFM/ton

airflow.  Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high stage

cooling operation. Select the A/C DIP switch setting corresponding

to  the  available  airflow  shown  in  the  furnace  Installation

Instructions that most closely matches the required airflow shown

in the air conditioning Product Data for HIGH speed.

3. The  CF  DIP  switch  setting  determines  airflow  during  low  stage

cooling operation. Select the CF DIP switch setting corresponding

to  the  available  airflow  shown  in  the  furnace  installation

instructions that most closely matches the required airflow shown

in the air conditioning Product Data for LOW speed. If a higher or

lower continuous fan speed is desired, the continuous fan speed can

be  changed  using  the  fan  switch  on  the  thermostat.  Refer  to  the

furnace  Installation  Instructions  for  details  of  how  to  use  this

feature.

Summary of Contents for N4H7T

Page 1: ...opriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refri...

Page 2: ...pace for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1...

Page 3: ...ton body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for...

Page 4: ...h a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in...

Page 5: ...readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided a...

Page 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to...

Page 7: ...5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Opera...

Page 8: ...or temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8...

Page 9: ...nit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation an...

Page 10: ...ved A Carrier Company Edition Date 03 22 Catalog No N4H7T 01SI Replaces New N4H7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without not...

Reviews: