background image

N4H7T: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

Evacuate Refrigerant Tubing and Indoor Coil

Refrigerant  tubes  and  indoor  coil  should  be  evacuated  using  the

recommended deep vacuum method of 500 microns. The alternate triple

evacuation  method  may  be  used  (see  triple  evacuation  procedure  in

service manual).  Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a

vacuum  of  500  microns  and  a  vacuum  gage  capable  of  accurately

measuring  this  vacuum  depth.  The  deep  vacuum  method  is  the  most

positive way of assuring a system is free of air and liquid water. A tight

dry system will hold a vacuum of 1000 microns after approximately 7

minutes.  See 

Fig. 7

.

A95424

Fig. 7 – Deep Vacuum Graph

Final Tubing Check

IMPORTANT: 

Check to be certain factory tubing on both indoor and

outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not

rubbing  against  each  other  or  any  sheet  metal.  Pay  close  attention  to

feeder tubes, makings sure wire ties on feeder tubes are secure and tight.
Be  sure field wiring complies with local and national fire, safety, and

electrical codes, and voltage  to system  is within limits shown on unit

rating  plate.  Contact local  power  company  for  correction  of  improper

voltage. See unit rating plate for recommended circuit protection device. 

NOTE: 

Operation of unit on improper line voltage constitutes abuse and

could affect unit reliability. See unit rating plate. Do  not install unit in

system where voltage may fluctuate above or below permissible limits.

Make Electrical Connections

NOTE: 

Use copper wire only between disconnect switch and unit.

NOTE: 

Install  branch circuit disconnect of adequate size  per NEC to

handle  unit  starting  current.  Locate  disconnect  within  sight  from  and

readily accessible from unit, per Section 440-14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from

disconnect  through  power  wiring  hole  provided  and  into  unit  control

box.

Connect Ground and Power Wires

Connect  ground  wire  to  ground  connection  in  control  box  for  safety.

Connect power wiring to contactor as shown in 

Fig. 8

.

A94025

Fig. 8 – Line Connections

Connect Control Wiring

Route 24v  control wires through control wiring  grommet and connect

leads  to  control  wiring.  See  Thermostat  Installation  Instructions  for

wiring specific unit combinations. (See 

Fig. 9

 and 

Fig. 10

.) 

Use  No.  18  AWG  color-coded,  insulated  (35°C  minimum)  wire.  If

thermostat is located more than 100 ft (30.5 m) from unit, as measured

along the control voltage wires, use No. 16 AWG color-coded wire to

avoid excessive voltage drop.
All wiring must be NEC Class 2 and must be separated from incoming

power leads. 
Use furnace transformer, fan coil transformer, or accessory transformer

for control power, 24v/40va minimum.

NOTE: 

Use of available 24v accessories may exceed the minimum 40va

power requirement. Determine total   transformer loading  and increase

the transformer capacity or split the load with an accessory transformer

as required.

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Never use the system compressor as a vacuum pump.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do  not  supply  power  to  unit  with  compressor  terminal  box  cover

removed.

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The  unit  cabinet  must  have  an  uninterrupted  or  unbroken  ground  to

minimize personal injury if an electrical fault should occur. The ground

may  consist  of  electrical  wire  or  metal  conduit  when  installed  in

accordance with existing electrical codes. 

Summary of Contents for N4H7T

Page 1: ...opriate for unit capacity 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure and unit to absorb vibration 5 When passing refri...

Page 2: ...pace for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1...

Page 3: ...ton body of the liquid service valve temporarily held in place with a plastic cap Do not remove the plastic cap until line set tubing is ready to be installed Refer to Fig 4 and follow these steps for...

Page 4: ...h a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Install Liquid Line Filter Drier Indoor Refer to Fig 6 and install filter drier as follows 1 Braze 5 in...

Page 5: ...readily accessible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided a...

Page 6: ...at the Y2 signal is communicated via the cool tap to the desired speed tap 2 The Y1 call for low stage cooling energizes the Fan tap on the control board The red wire from the fan tap is connected to...

Page 7: ...5 minute time guard begins counting Compressor will not come on until this delay expires In the event of a power interruption the time guard will not allow another cycle for 5 minutes Compressor Opera...

Page 8: ...or temperature is between 70 F and 80 F 21 11 C and 26 67 C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjust charge by adding or removing 0 6 oz ft 018 kg m of 3 8...

Page 9: ...nit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system operation an...

Page 10: ...ved A Carrier Company Edition Date 03 22 Catalog No N4H7T 01SI Replaces New N4H7T Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without not...

Reviews: