background image

30

Fig. 42 — Thermostat Level Detail

NOTE: Maximum inlet pressure 

— 3.0-in. wg.

START-UP

Principles of Operation

GENERAL
Units are normally open (bellows deflated). Rise in bellows

pressure closes unit. When thermostat is calling for no flow,

pressure differences between unit plenum (measured at con-

trol filter) and bellows should be less than 0.1-in. wg.

A leak

 may cause bellows in circuit to be fully open, partially

open or fully closed depending on location of the leak.

An  obstruction

  prevents  operation  of  all  bellows  down-

stream. The inoperative bellows may remain open or closed,

depending on whether air has been trapped in them.
CONSTANT VOLUME OPERATION
Both high-pressure and low-pressure control air from the ple-

num of the master unit passes through the filter to the volume

controller. An adjustable bleed orifice reacting to the relative

change of high and low pressure allows a set amount of con-

trol air to pressurize the bellows until unit air delivery match-

es the controller setting.
VARIABLE AIR VOLUME OPERATION
The constant volume control becomes variable volume con-

trol with the addition of a thermostat. The thermostat enables

the control to sense changes in the room temperature, over-

ride the volume controller and reduce the unit flow to match

the thermostat setting. If room temperature rises, the bellows

will bleed, increasing unit flow until the thermostat is satis-

fied.  If  room  temperature  falls,  the  bellows  will  inflate,  de-

creasing the unit flow until the thermostat is satisfied.

Preliminary System Check

Perform  air  balancing  and  control  system  checkout  before

building is occupied but after conditioned spaces are reason-

ably clean. The high induction ratio of 37HS Moduline

®

 dif-

fusers can produce ceiling smudges within a few days if con-

struction dirt is present.
Before starting system, thoroughly check the air handling ap-

paratus and controls. Verify that the fan static pressure control

is operating properly so that starting the fan without airflow

at terminals will not cause duct damage from overpressure.
1. Check fan and system controls for proper hookup.
2. Be  sure  that  all  dampers,  including  fan  inlet,  fan  outlet

and outdoor-air and return-air dampers, have proper free-

dom of movement. Lubricate as required.

3. Check fan belts, motors, sheave alignment and fan wheel

rotation. Check bearings for proper lubrication. Refer to

fan manufacturer’s recommendations.

4.

Be sure that fan final filters are in place.

 If not, accumu-

lated  dirt  will  be  distributed  throughout  the  system  and

can  accumulate  in  unit  or  fall  into  space.  Dirt  can  also
disrupt air terminal operation.

5. Be  sure  that  fan,  coil,  filter  section  and  ductwork  are

clean and free of any construction debris.

6. Remove protective tape from all diffusers.

Initial Start-Up

GENERAL CHECKOUT
1. Start  the  variable  volume  air-supply  system  and  obtain

suitable  supply-air  temperature  and  pressure.  If  design
speed of supply fan is based on a diversified block load,

close  zone  fire  dampers  or  set  Moduline  thermostats  at

highest  setting  to  obtain  sufficient  pressure  at  terminal
being balanced.

2. Check  the  air  terminal  system  for  open  control  loops.

Noise and excessive airflow at unit may indicate discon-
nected tubes, loose plugs or fittings. Correct the problem

before beginning detailed checkout below.

SERVICE

Gaining Access to Control Area

On standard units, center diffuser is not removable. Remove

ceiling  tile or reach through  nearby light fixture  to  gain  ac-

cess to controls.

Table 8 — Minimum Static Pressure at Control 

(Master) Unit - Units with System-Powered Controls 

and Standard Diffusers

AIRFLOW 

(cfm)

37HS1

37HS2

37HS4

PLENUM SIZE (in.)

5 X 7

7 X 7

7 X 7

9 X 9

9 X 9

9 X 9

11 X 11

11 X 11

11 X 11

13 X 13

Minimum Static Pressure (in. wg.)

40
50
60
70

0.75

0.75

80
90

100

0.75

0.75

0.75

110

0.90

0.90

0.75

120
140

0.75

160
180
200

0.75

0.75

220

0.90

0.75

240
280
320
360
400

0.75

440

0.90

Table 9 — Minimum Airflow (cfm)

MINIMUM AIRFLOW (cfm)

37HS1

37HS2

37HS4

40

80

160

THERMOSTAT
LEVER
IN CEILING

Summary of Contents for MODULINE 37HS

Page 1: ...observe precautions in the literature tags and labels attached to the equipment and any other safety precautions that may apply See Fig 1 for Proposition 65 warning label Fig 1 Proposition 65 Warning...

Page 2: ...it Unit Size Airflow Nominal Cfm 1 100 2 200 4 400 Not used Plenum Size 1 5 x 7 2 7 x 7 3 9 x 9 4 11 x 11 5 13 x 13 X Special Quote Control Inlet Diameter 4 4 Round 6 6 Round 8 8 Round 0 10 Round 2 12...

Page 3: ...ons for dif fuser options are shown in Fig 8 and 9 See Fig 10 for acces sory return air diffuser dimensions and Fig 11 for accessory dummy diffuser dimensions Table 1 lists installation acces sories f...

Page 4: ...lable in inches A 46 92 47 00 47 38 48 00 58 92 59 00 59 38 60 00 F 1 25 1 25 1 25 1 25 7 25 7 25 7 25 7 25 NOTE Dimensions are in inches 37HS4 Plenum Dimensions PLENUM SIZE sq B C D E G H J 9 8 11 50...

Page 5: ...NARROW 9 16 T BAR 23 38 47 38 37HS2 200 cfm Diffuser Options CEILING T BAR STYLE AND WIDTH DIFFUSER LENGTH in STANDARD 15 16 T BAR 47 00 59 00 TEGULAR 15 16 T BAR 46 92 58 92 CONTINUOUS RUN 15 16 T B...

Page 6: ...LUMINUM 3 SLOT Available Lengths in of Accessory Return Air Diffusers 37HS1 37HS2 37HS4 23 00 47 00 47 00 47 00 47 38 47 38 59 00 59 00 NOTES 1 Dummy diffusers for other lengths can be field cut from...

Page 7: ...37HS4 Package No 2 Slot T Bar 37CN900002 2 Slot Tegular 1 2 in 37CN900042 7 16 in 37CN900052 3 8 in 37CN900062 5 16 in 37CN900072 1 4 in 37CN900082 3 Slot T Bar 37CN900012 3 Slot Tegular 1 2 in 37CN9...

Page 8: ...ckets can be used for ceiling alignment Fig 12 37HS Unit Installed in a T Bar Ceiling END TRIM Qty 50 T Bar Tegular Used on 37HS1 HS2 Color Package No 2 Slot T Bar White 37CM900132 2 Slot Tegular Whit...

Page 9: ...r on end of unit 9 If other units are to be connected to the first unit install T bar mounting brackets on each end of the adjoining units 10 Raise each unit above ceiling and lower into position Enga...

Page 10: ...e After alignment channel is installed filler trim piece can be snapped into place Fig 16 One Piece Mounting Bracket Installed on Diffuser End Fig 17 Installed Hanger Mounting Brackets Fig 18 Insertin...

Page 11: ...he unit is flush with the ceiling tile plane The recessed T bar may be painted usually black with white tiles to create an interesting grid pattern The 37HS unit cen ter diffuser when installed on the...

Page 12: ...is left to the discretion of the individual plasterer One typical method shown in Fig 21 shows 2 Model Moduline 37HS air termi nals installed Wire hangers with eyebolts for leveling and supporting the...

Page 13: ...h a special knife like tool to provide access to the ceiling cavity this ceiling also offers the kind of security re quired for such installations as classrooms and other institu tional applications T...

Page 14: ...14 Fig 23 37HS Moduline Units Installed in a Plaster Ceiling Fig 24 Typical Concealed Spline Ceiling Using 37HS Air Terminals Details...

Page 15: ...15 Fig 25 Typical Concealed Spline Ceiling Using 37HS Air Terminals...

Page 16: ...in Fig 27 NOTE Although 37A 37C and 37HS controls operate on simi lar principles the pressure relationships between the 3 models of units are different Therefore 37HS units cannot be operated with 37A...

Page 17: ...17 Fig 28 Control Arrangements Master Units with Slaves SINGLE MASTER UNIT INSTALLATION MASTER UNIT WITH ONE SLAVE MASTER UNIT WITH 3 SLAVES...

Page 18: ...ol air from the volume controller low side This causes the volume controller seat to move toward the bleed nozzle increasing the bellows output pressure thus closing the unit A minimum airflow can be...

Page 19: ...TANT VOLUME COOLING 37HS1 37HS900003 37HS2 37HS900003 37HS4 37HS900003 2 SYSTEM POWERED VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT 37HS1 37HS900001 37HS2 37HS900002 37HS4 37HS900004 3 SYSTEM POWERED...

Page 20: ...a diffuser thermostat in place of the wall thermostat replace constant volume package 37HS900003 and wall thermostat 37CM901012 with variable volume package 37HS900001 37HS1 37HS900002 37HS2 or 37HS9...

Page 21: ...VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT ELECTRIC INTERLOCK TO FAN COIL OR BASEBOARD HEATING 37HS1 37HS900001 37CM900922 37HS2 37HS900002 37CM900922 37HS4 37HS900004 37CM900922 9 SYSTEM POWERED VAR...

Page 22: ...972 NO with 37HS900007 DA 37CM900982 NC with 37HS900008 RA 11 SYSTEM POWERED VARIABLE VOLUME COOLING WALL THERMOSTAT PNEUMATIC WARM UP FIRE SWITCH 37HS1 37HS900003 37CM901012 37HS900017 37HS2 37HS9000...

Page 23: ...the control side should be capped or plugged before installation Moisten the 2 O rings with water then push the filter into the unit end block until the standoffs rest on or close to the unit end plat...

Page 24: ...form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 31 4 To prepare the control filter for installation be sure that the bellows chamber filter plug is pushed tightl...

Page 25: ...ume controller with water and push the controller directly into the filter extensions c Install the thermostat on the center diffuser then snap spring clip over thermostat and onto the side diffusers...

Page 26: ...0003 37HS4 37HS900003 SYSTEM POWERED WARM UP CONTROL QTY 1 Package No 37CM900152 37 A G4 00 45 2 C F M 110 100 80 40 HK 08ZZ016 FILTER MANIFOLD WITH FILTER EXTENSIONS DIFFUSER THERMOSTAT ASPIRATOR DIF...

Page 27: ...VALVE Voltage Package No 24 37CM900792 120 37CM900802 240 37CM900812 208 37CM900822 277 37CM900832 480 37CM900842 ELECTRIC INTERLOCK Used On Package No 37HS1 37CM900922 37HS2 37CM900922 37HS4 37CM9009...

Page 28: ...lenum size the model and the number of units in an air series on one controller See Tables 5 and 6 The 37HS1 unit with 5 x 7 size plenum is available with blank end only multiple units of this size wo...

Page 29: ...just maximum cfm lever to desired percent cfm FUNCTIONAL CHECKOUT With building temperature within Moduline thermostat set point limits 70 F to 80 F VAV supply air at design tem perature and VAV suppl...

Page 30: ...e fan static pressure control is operating properly so that starting the fan without airflow at terminals will not cause duct damage from overpressure 1 Check fan and system controls for proper hookup...

Page 31: ...o leak is detected the bellows are satisfactory 5 If unit appears satisfactory replace the thermostat vol ume controller assembly and connect it to the unit See Control Installation section page 23 6...

Page 32: ...efective Check thermostat operation replace thermostat if temperature at thermostat is below 75 F and airflow does not shut off when lever is at extreme red area Bellows Defective Check bellows remove...

Reviews: