background image

18

OPERATING SEQUENCES
System powered control for the Moduline

®

 terminal is shown

schematically in Fig. 29.

System Powered Cooling

A  high-pressure  signal  and  a  low-pressure  signal,  measured

across  the  control  unit  distribution  baffle,  are  transmitted

through the unit control block to the control air filter and to

the  volume  controller. The  difference  between  the  high  and

low pressure is an indication of the unit airflow. The control

air  filter,  besides  preventing  dirt  from  entering  the  control

system, also acts as a manifold to connect the volume control-

ler to the unit.
The  high-pressure  and  low-pressure  signals  act  on  dia-

phragms in the volume controller to position a seat relative to

a bleed nozzle. The relationship of the seat to the bleed nozzle

determines the air pressure transmitted back through the con-

trol filter to the unit bellows, which inflates to a position nec-

essary to provide the airflow as preset on the volume control-

ler. A  change  in  input  pressures  caused  by  changes  in  duct

pressures will cause the seat to be repositioned, relative to the

bleed nozzle, and change the output pressure to the bellows to

maintain  the  unit  airflow.  The  airflow  is  pre-set  using  the

maximum airflow adjusting lever.
The  thermostat,  wall-mounted  or  diffuser-mounted,  is  con-

nected to the volume controller to provide a means of varying

the airflow delivery as room temperature varies from the ther-

mostat  set  point. As  room  temperature  cools  to  the  cooling

thermostat  set  point,  another  bleed  orifice  in  the  thermostat

opens and bleeds control air from the volume controller low

side. This causes the volume controller seat to move toward

the bleed nozzle, increasing the bellows output pressure, thus

closing the unit.
A  minimum  airflow  can  be  set  on  the  volume  controller  to

prevent the unit from closing completely. The minimum air-

flow  adjustment  restricts  the  volume  controller  seat  from

closing the bleed nozzle, thus preventing the unit from fully

closing. A hood airflow measurement is required to set mini-

mum airflow.

System Powered Cooling With Warm-Up

The  cooling  thermostat  (diffuser-mounted  or  wall-mounted)

is a direct acting thermostat. With the space temperature at a

nighttime condition below the set point, the thermostat port is

open, reducing the pressure on the upper diaphragm (A) and

causing  the  element  assembly  (B)  to  rise.  This  closes  the

bleed port (C), which diverts high pressure to the bellows, re-

ducing the unit flow. In warm-up, hot air flows over the im-

mersion warm-up switch installed in unit plenum. The switch

closes, raising the low-side pressure on the volume controller

diaphragm and moving the element away from the bleed noz-

zle. This reduces the bellows pressure and permits warm duct

air to flow to the space.

System Powered Heating and Cooling

The 37HS can provide heating as well as cooling with the ad-

dition of a changeover switch installed in the unit plenum and

a wall heating/cooling thermostat. A separate amplifier is not

required.
With cold air below 65°F in the duct, the changeover is con-

nected to the cooling side of the thermostat, and the bellows

is bled at the volume controller according to the pilot pressure

from the thermostat. Hot air in the plenum shifts the connec-

tion to the heating side of the thermostat.

Fig. 29 — 37HS Control Schematic

Summary of Contents for MODULINE 37HS

Page 1: ...observe precautions in the literature tags and labels attached to the equipment and any other safety precautions that may apply See Fig 1 for Proposition 65 warning label Fig 1 Proposition 65 Warning...

Page 2: ...it Unit Size Airflow Nominal Cfm 1 100 2 200 4 400 Not used Plenum Size 1 5 x 7 2 7 x 7 3 9 x 9 4 11 x 11 5 13 x 13 X Special Quote Control Inlet Diameter 4 4 Round 6 6 Round 8 8 Round 0 10 Round 2 12...

Page 3: ...ons for dif fuser options are shown in Fig 8 and 9 See Fig 10 for acces sory return air diffuser dimensions and Fig 11 for accessory dummy diffuser dimensions Table 1 lists installation acces sories f...

Page 4: ...lable in inches A 46 92 47 00 47 38 48 00 58 92 59 00 59 38 60 00 F 1 25 1 25 1 25 1 25 7 25 7 25 7 25 7 25 NOTE Dimensions are in inches 37HS4 Plenum Dimensions PLENUM SIZE sq B C D E G H J 9 8 11 50...

Page 5: ...NARROW 9 16 T BAR 23 38 47 38 37HS2 200 cfm Diffuser Options CEILING T BAR STYLE AND WIDTH DIFFUSER LENGTH in STANDARD 15 16 T BAR 47 00 59 00 TEGULAR 15 16 T BAR 46 92 58 92 CONTINUOUS RUN 15 16 T B...

Page 6: ...LUMINUM 3 SLOT Available Lengths in of Accessory Return Air Diffusers 37HS1 37HS2 37HS4 23 00 47 00 47 00 47 00 47 38 47 38 59 00 59 00 NOTES 1 Dummy diffusers for other lengths can be field cut from...

Page 7: ...37HS4 Package No 2 Slot T Bar 37CN900002 2 Slot Tegular 1 2 in 37CN900042 7 16 in 37CN900052 3 8 in 37CN900062 5 16 in 37CN900072 1 4 in 37CN900082 3 Slot T Bar 37CN900012 3 Slot Tegular 1 2 in 37CN9...

Page 8: ...ckets can be used for ceiling alignment Fig 12 37HS Unit Installed in a T Bar Ceiling END TRIM Qty 50 T Bar Tegular Used on 37HS1 HS2 Color Package No 2 Slot T Bar White 37CM900132 2 Slot Tegular Whit...

Page 9: ...r on end of unit 9 If other units are to be connected to the first unit install T bar mounting brackets on each end of the adjoining units 10 Raise each unit above ceiling and lower into position Enga...

Page 10: ...e After alignment channel is installed filler trim piece can be snapped into place Fig 16 One Piece Mounting Bracket Installed on Diffuser End Fig 17 Installed Hanger Mounting Brackets Fig 18 Insertin...

Page 11: ...he unit is flush with the ceiling tile plane The recessed T bar may be painted usually black with white tiles to create an interesting grid pattern The 37HS unit cen ter diffuser when installed on the...

Page 12: ...is left to the discretion of the individual plasterer One typical method shown in Fig 21 shows 2 Model Moduline 37HS air termi nals installed Wire hangers with eyebolts for leveling and supporting the...

Page 13: ...h a special knife like tool to provide access to the ceiling cavity this ceiling also offers the kind of security re quired for such installations as classrooms and other institu tional applications T...

Page 14: ...14 Fig 23 37HS Moduline Units Installed in a Plaster Ceiling Fig 24 Typical Concealed Spline Ceiling Using 37HS Air Terminals Details...

Page 15: ...15 Fig 25 Typical Concealed Spline Ceiling Using 37HS Air Terminals...

Page 16: ...in Fig 27 NOTE Although 37A 37C and 37HS controls operate on simi lar principles the pressure relationships between the 3 models of units are different Therefore 37HS units cannot be operated with 37A...

Page 17: ...17 Fig 28 Control Arrangements Master Units with Slaves SINGLE MASTER UNIT INSTALLATION MASTER UNIT WITH ONE SLAVE MASTER UNIT WITH 3 SLAVES...

Page 18: ...ol air from the volume controller low side This causes the volume controller seat to move toward the bleed nozzle increasing the bellows output pressure thus closing the unit A minimum airflow can be...

Page 19: ...TANT VOLUME COOLING 37HS1 37HS900003 37HS2 37HS900003 37HS4 37HS900003 2 SYSTEM POWERED VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT 37HS1 37HS900001 37HS2 37HS900002 37HS4 37HS900004 3 SYSTEM POWERED...

Page 20: ...a diffuser thermostat in place of the wall thermostat replace constant volume package 37HS900003 and wall thermostat 37CM901012 with variable volume package 37HS900001 37HS1 37HS900002 37HS2 or 37HS9...

Page 21: ...VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT ELECTRIC INTERLOCK TO FAN COIL OR BASEBOARD HEATING 37HS1 37HS900001 37CM900922 37HS2 37HS900002 37CM900922 37HS4 37HS900004 37CM900922 9 SYSTEM POWERED VAR...

Page 22: ...972 NO with 37HS900007 DA 37CM900982 NC with 37HS900008 RA 11 SYSTEM POWERED VARIABLE VOLUME COOLING WALL THERMOSTAT PNEUMATIC WARM UP FIRE SWITCH 37HS1 37HS900003 37CM901012 37HS900017 37HS2 37HS9000...

Page 23: ...the control side should be capped or plugged before installation Moisten the 2 O rings with water then push the filter into the unit end block until the standoffs rest on or close to the unit end plat...

Page 24: ...form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 31 4 To prepare the control filter for installation be sure that the bellows chamber filter plug is pushed tightl...

Page 25: ...ume controller with water and push the controller directly into the filter extensions c Install the thermostat on the center diffuser then snap spring clip over thermostat and onto the side diffusers...

Page 26: ...0003 37HS4 37HS900003 SYSTEM POWERED WARM UP CONTROL QTY 1 Package No 37CM900152 37 A G4 00 45 2 C F M 110 100 80 40 HK 08ZZ016 FILTER MANIFOLD WITH FILTER EXTENSIONS DIFFUSER THERMOSTAT ASPIRATOR DIF...

Page 27: ...VALVE Voltage Package No 24 37CM900792 120 37CM900802 240 37CM900812 208 37CM900822 277 37CM900832 480 37CM900842 ELECTRIC INTERLOCK Used On Package No 37HS1 37CM900922 37HS2 37CM900922 37HS4 37CM9009...

Page 28: ...lenum size the model and the number of units in an air series on one controller See Tables 5 and 6 The 37HS1 unit with 5 x 7 size plenum is available with blank end only multiple units of this size wo...

Page 29: ...just maximum cfm lever to desired percent cfm FUNCTIONAL CHECKOUT With building temperature within Moduline thermostat set point limits 70 F to 80 F VAV supply air at design tem perature and VAV suppl...

Page 30: ...e fan static pressure control is operating properly so that starting the fan without airflow at terminals will not cause duct damage from overpressure 1 Check fan and system controls for proper hookup...

Page 31: ...o leak is detected the bellows are satisfactory 5 If unit appears satisfactory replace the thermostat vol ume controller assembly and connect it to the unit See Control Installation section page 23 6...

Page 32: ...efective Check thermostat operation replace thermostat if temperature at thermostat is below 75 F and airflow does not shut off when lever is at extreme red area Bellows Defective Check bellows remove...

Reviews: