background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53370001-01

Printed in U.S.A.

Form 37HS-10SI

Pg 32 

8-18

Replaces: 37HS-1SI

© Carrier Corporation 2018

Table 10 — Troubleshooting Chart

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE PROCEDURE

ROOM TOO 

COLD

Thermostat Setting Incorrect

Check thermostat setting—move thermostat lever slightly toward red area. If unit

shuts off, leave in this (or in an intermediate) position. See Fig. 42.

Volume Controller Setting Incorrect

Check actual volume controller setting vs design cfm — readjust volume controller

setting. Minimum flow set above stop.

Minimum Flow Set Above Internal Stop

Turn minimum flow star wheel counterclockwise to zero position.

Supply-Air Temperature Too Low

Check actual temperature of supply air vs design supply air temperature. If required,

raise supply-air temperature.

Controls Improperly Seated

Check connections between filter and plenum, volume controller and filter, filter and

bellows.

Tubing Loose or Kinked

Check interconnecting tubing between units. Refer to job drawings; check control

arrangement — secure as required.

Plugs and Caps Not Installed Properly

Check cap on bellows end connection. Check caps and plugs on filter.

Unit Controlled by More than One Set of 

Controls

Check job drawings for proper control arrangement—make changes as required.

Filter Clogged

Visually check filter media — replace only if excessively dirty. (Normally, filter will not

require replacement.)

Volume Controller Defective

Check volume controller operation with thermostat lever set at extreme blue area —

replace volume controller if unit airflow does not decrease when cfm setting is

decreased.

Thermostat Defective

Check thermostat operation — replace thermostat if temperature at thermostat is

below 75°F and airflow does not shut off when lever is at extreme red area.

Bellows Defective

Check bellows — remove controls, cap one end of bellows, connect tube to other end

and inflate until unit shuts off. Trap air in bellows. If unit flow increases, bellows is

defective — replace.

Supply Pressure to Filter Not Correct

Remove controls including filter. Check pressures at end plug. There must be

pressure reading at each connection. Top connection pressure reading must be

higher than low connection pressure reading. If pressure readings are the same or

opposite of above — move controls to another unit.

ROOM TOO 

WARM

Thermostat Setting Incorrect

Check thermostat setting—move thermostat lever slightly toward blue area. If air is

discharged from unit, leave lever in this (or in an intermediate) position. See Fig. 42.

Volume Controller Setting Incorrect

Check actual volume controller setting vs design cfm —readjust volume controller

setting.

Supply-Air Temperature Too High

Check actual temperature of supply air vs design supply air temperature. If required,

reduce supply-air temperature.

Duct Pressure Incorrect

Measure duct pressure — verify per Table 6.

Unit Controlled by More than One Set of 

Controls

Check job drawings for proper control arrangement—make changes as required.

Tubing Loose; Control Caps Not Installed 

Properly

Check interconnecting tube between volume controller and thermostat. Check caps

on volume controller at thermostat connection.

Volume Controller Defective

Check volume controller operation with thermostat lever set at extreme blue area.

Replace volume controller if airflow does not increase when volume controller cfm

setting is increased.

Thermostat Defective

Check thermostat operation — replace thermostat if temperature at thermostat is

above 69°F and the cfm is not at design requirements, although lever is at the extreme

blue area.

Summary of Contents for MODULINE 37HS

Page 1: ...observe precautions in the literature tags and labels attached to the equipment and any other safety precautions that may apply See Fig 1 for Proposition 65 warning label Fig 1 Proposition 65 Warning...

Page 2: ...it Unit Size Airflow Nominal Cfm 1 100 2 200 4 400 Not used Plenum Size 1 5 x 7 2 7 x 7 3 9 x 9 4 11 x 11 5 13 x 13 X Special Quote Control Inlet Diameter 4 4 Round 6 6 Round 8 8 Round 0 10 Round 2 12...

Page 3: ...ons for dif fuser options are shown in Fig 8 and 9 See Fig 10 for acces sory return air diffuser dimensions and Fig 11 for accessory dummy diffuser dimensions Table 1 lists installation acces sories f...

Page 4: ...lable in inches A 46 92 47 00 47 38 48 00 58 92 59 00 59 38 60 00 F 1 25 1 25 1 25 1 25 7 25 7 25 7 25 7 25 NOTE Dimensions are in inches 37HS4 Plenum Dimensions PLENUM SIZE sq B C D E G H J 9 8 11 50...

Page 5: ...NARROW 9 16 T BAR 23 38 47 38 37HS2 200 cfm Diffuser Options CEILING T BAR STYLE AND WIDTH DIFFUSER LENGTH in STANDARD 15 16 T BAR 47 00 59 00 TEGULAR 15 16 T BAR 46 92 58 92 CONTINUOUS RUN 15 16 T B...

Page 6: ...LUMINUM 3 SLOT Available Lengths in of Accessory Return Air Diffusers 37HS1 37HS2 37HS4 23 00 47 00 47 00 47 00 47 38 47 38 59 00 59 00 NOTES 1 Dummy diffusers for other lengths can be field cut from...

Page 7: ...37HS4 Package No 2 Slot T Bar 37CN900002 2 Slot Tegular 1 2 in 37CN900042 7 16 in 37CN900052 3 8 in 37CN900062 5 16 in 37CN900072 1 4 in 37CN900082 3 Slot T Bar 37CN900012 3 Slot Tegular 1 2 in 37CN9...

Page 8: ...ckets can be used for ceiling alignment Fig 12 37HS Unit Installed in a T Bar Ceiling END TRIM Qty 50 T Bar Tegular Used on 37HS1 HS2 Color Package No 2 Slot T Bar White 37CM900132 2 Slot Tegular Whit...

Page 9: ...r on end of unit 9 If other units are to be connected to the first unit install T bar mounting brackets on each end of the adjoining units 10 Raise each unit above ceiling and lower into position Enga...

Page 10: ...e After alignment channel is installed filler trim piece can be snapped into place Fig 16 One Piece Mounting Bracket Installed on Diffuser End Fig 17 Installed Hanger Mounting Brackets Fig 18 Insertin...

Page 11: ...he unit is flush with the ceiling tile plane The recessed T bar may be painted usually black with white tiles to create an interesting grid pattern The 37HS unit cen ter diffuser when installed on the...

Page 12: ...is left to the discretion of the individual plasterer One typical method shown in Fig 21 shows 2 Model Moduline 37HS air termi nals installed Wire hangers with eyebolts for leveling and supporting the...

Page 13: ...h a special knife like tool to provide access to the ceiling cavity this ceiling also offers the kind of security re quired for such installations as classrooms and other institu tional applications T...

Page 14: ...14 Fig 23 37HS Moduline Units Installed in a Plaster Ceiling Fig 24 Typical Concealed Spline Ceiling Using 37HS Air Terminals Details...

Page 15: ...15 Fig 25 Typical Concealed Spline Ceiling Using 37HS Air Terminals...

Page 16: ...in Fig 27 NOTE Although 37A 37C and 37HS controls operate on simi lar principles the pressure relationships between the 3 models of units are different Therefore 37HS units cannot be operated with 37A...

Page 17: ...17 Fig 28 Control Arrangements Master Units with Slaves SINGLE MASTER UNIT INSTALLATION MASTER UNIT WITH ONE SLAVE MASTER UNIT WITH 3 SLAVES...

Page 18: ...ol air from the volume controller low side This causes the volume controller seat to move toward the bleed nozzle increasing the bellows output pressure thus closing the unit A minimum airflow can be...

Page 19: ...TANT VOLUME COOLING 37HS1 37HS900003 37HS2 37HS900003 37HS4 37HS900003 2 SYSTEM POWERED VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT 37HS1 37HS900001 37HS2 37HS900002 37HS4 37HS900004 3 SYSTEM POWERED...

Page 20: ...a diffuser thermostat in place of the wall thermostat replace constant volume package 37HS900003 and wall thermostat 37CM901012 with variable volume package 37HS900001 37HS1 37HS900002 37HS2 or 37HS9...

Page 21: ...VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT ELECTRIC INTERLOCK TO FAN COIL OR BASEBOARD HEATING 37HS1 37HS900001 37CM900922 37HS2 37HS900002 37CM900922 37HS4 37HS900004 37CM900922 9 SYSTEM POWERED VAR...

Page 22: ...972 NO with 37HS900007 DA 37CM900982 NC with 37HS900008 RA 11 SYSTEM POWERED VARIABLE VOLUME COOLING WALL THERMOSTAT PNEUMATIC WARM UP FIRE SWITCH 37HS1 37HS900003 37CM901012 37HS900017 37HS2 37HS9000...

Page 23: ...the control side should be capped or plugged before installation Moisten the 2 O rings with water then push the filter into the unit end block until the standoffs rest on or close to the unit end plat...

Page 24: ...form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 31 4 To prepare the control filter for installation be sure that the bellows chamber filter plug is pushed tightl...

Page 25: ...ume controller with water and push the controller directly into the filter extensions c Install the thermostat on the center diffuser then snap spring clip over thermostat and onto the side diffusers...

Page 26: ...0003 37HS4 37HS900003 SYSTEM POWERED WARM UP CONTROL QTY 1 Package No 37CM900152 37 A G4 00 45 2 C F M 110 100 80 40 HK 08ZZ016 FILTER MANIFOLD WITH FILTER EXTENSIONS DIFFUSER THERMOSTAT ASPIRATOR DIF...

Page 27: ...VALVE Voltage Package No 24 37CM900792 120 37CM900802 240 37CM900812 208 37CM900822 277 37CM900832 480 37CM900842 ELECTRIC INTERLOCK Used On Package No 37HS1 37CM900922 37HS2 37CM900922 37HS4 37CM9009...

Page 28: ...lenum size the model and the number of units in an air series on one controller See Tables 5 and 6 The 37HS1 unit with 5 x 7 size plenum is available with blank end only multiple units of this size wo...

Page 29: ...just maximum cfm lever to desired percent cfm FUNCTIONAL CHECKOUT With building temperature within Moduline thermostat set point limits 70 F to 80 F VAV supply air at design tem perature and VAV suppl...

Page 30: ...e fan static pressure control is operating properly so that starting the fan without airflow at terminals will not cause duct damage from overpressure 1 Check fan and system controls for proper hookup...

Page 31: ...o leak is detected the bellows are satisfactory 5 If unit appears satisfactory replace the thermostat vol ume controller assembly and connect it to the unit See Control Installation section page 23 6...

Page 32: ...efective Check thermostat operation replace thermostat if temperature at thermostat is below 75 F and airflow does not shut off when lever is at extreme red area Bellows Defective Check bellows remove...

Reviews: