background image

31

TROUBLESHOOTING

General

If system design parameters have been met, such as ductwork

size, airflow rate, etc., improper operation can often be traced

to  leaks  or  obstructions. The  following  paragraphs  describe

the general procedure for checking for leaks or obstructions.
Before performing any check, be sure that plenum pressure is

a minimum of 0.75-in. wg and that supply-air temperature is

50°F to 60°F and room temperature is 70°F to 80°F.

Checking for Obstruction

If there is an obstruction, the unit fails to respond either par-

tially or completely to thermostat changes, but does not show

any indication of a control circuit leak.
Check the bellows pressure at each inlet and outlet. Pressure

at every point in bellows circuit should be the same. The ob-

struction may be kinked control tube.

Checking for Leaks

The center diffuser of these units is not removable. Gain ac-

cess to unit controls by raising ceiling tile.
1. Master  units  can  be  identified  by  means  of  thermostat

lever extending below diffuser. See Fig 42.

2. Disconnect slave from master by disconnecting the inter-

unit tubing. Mark tubes clearly to assure proper reassem-
bly.  Cap  ports  on  master  unit  to  isolate  it.  Then  move

thermostat  lever  to  full  red  (warm)  setting  and  observe

whether unit shuts off.

3. Check for cracked plastic parts, loose or cracked tubing

or a loose filter. Remove filter and check that filter open-

ing is not obstructed; then replace filter.

4. Remove  thermostat/volume  controller  assembly. Attach

Magnehelic  gage  to  bellows  connection  with  rubber

tube.  (See  Fig.  43.)  Blow  into  tube  until  unit  shuts  off.
Hold  tube  so  that  no  air  escapes.  Dial  on  Magnehelic

gage  dropping  or  the  opening  of  the  diffuser  slot  dis-

charging air will indicate a bellows leak. If after approxi-
mately  30  seconds  no  leak  is  detected,  the  bellows  are

satisfactory.

5. If  unit  appears  satisfactory,  replace  the  thermostat/vol-

ume controller assembly and connect it to the unit. See

Control Installation section page 23.

6. Test  whether  master  unit  (isolated,  without  slave  units)

will  control.  If  no  control,  check  duct  pressure  as

described in the section below.

7. If master unit controls properly, add one slave unit, mak-

ing sure air is flowing from both sides of diffuser. If both

units control, add another slave; and so on down the line.

8. If control is lost by adding a new slave, check for loose,

cracked  or  disconnected  tubing.  Isolate  that  slave  and
cap all bellows ports. Attach a Magnehelic gage to  one

port  and  blow  into  it.  The  Magnehelic  gage  will  be

needed to detect a leaking bellows.

9. If possible, check bellows pressure at each unit by attach-

ing Magnehelic gage  tubing  to a bellows port for  2  to  3

minutes after stabilization takes place. Record values.

10. Take duct readings with all units connected and operat-

ing.  Reference  the  Check  Duct  Pressure  section.  To

record data on slave unit, remove high-pressure port plug
(Fig. 36) and insert Magnehelic gage tube into opening.

Replace plug after test.

11. If units are still not controlling, check inter-unit control

tubing for possible holes, breaks or pinching between the

2 units where control apparently was lost.

To Check Duct Pressure

To  check  duct  pressure  on  master  unit,  remove  the  volume

controller from the filter and connect a Magnehelic gage tube

to  the  filter  high-pressure  port  (shown  on  Fig.  33).  After

checking, replace volume controller. Check the slave unit by

removing  the  plug  from  the  high-pressure  port  on  the  slave

unit (shown on Fig. 30) and connecting the Magnehelic gage

tube. Replace plug after checking.
See Table 6 for minimum required duct pressures at various

air quantities.

Fig. 43 — Checking Unit Bellows for Leaks

0

1

2

3

4

5

6

MA

GN

EH

ELI

C

OF

 W

AT

E R

®

BLOW INTO
THIS TUBE,
CLOSE OFF

METAL  "T"

DIFFUSER
BELLOWS
CONNECTION

Summary of Contents for MODULINE 37HS

Page 1: ...observe precautions in the literature tags and labels attached to the equipment and any other safety precautions that may apply See Fig 1 for Proposition 65 warning label Fig 1 Proposition 65 Warning...

Page 2: ...it Unit Size Airflow Nominal Cfm 1 100 2 200 4 400 Not used Plenum Size 1 5 x 7 2 7 x 7 3 9 x 9 4 11 x 11 5 13 x 13 X Special Quote Control Inlet Diameter 4 4 Round 6 6 Round 8 8 Round 0 10 Round 2 12...

Page 3: ...ons for dif fuser options are shown in Fig 8 and 9 See Fig 10 for acces sory return air diffuser dimensions and Fig 11 for accessory dummy diffuser dimensions Table 1 lists installation acces sories f...

Page 4: ...lable in inches A 46 92 47 00 47 38 48 00 58 92 59 00 59 38 60 00 F 1 25 1 25 1 25 1 25 7 25 7 25 7 25 7 25 NOTE Dimensions are in inches 37HS4 Plenum Dimensions PLENUM SIZE sq B C D E G H J 9 8 11 50...

Page 5: ...NARROW 9 16 T BAR 23 38 47 38 37HS2 200 cfm Diffuser Options CEILING T BAR STYLE AND WIDTH DIFFUSER LENGTH in STANDARD 15 16 T BAR 47 00 59 00 TEGULAR 15 16 T BAR 46 92 58 92 CONTINUOUS RUN 15 16 T B...

Page 6: ...LUMINUM 3 SLOT Available Lengths in of Accessory Return Air Diffusers 37HS1 37HS2 37HS4 23 00 47 00 47 00 47 00 47 38 47 38 59 00 59 00 NOTES 1 Dummy diffusers for other lengths can be field cut from...

Page 7: ...37HS4 Package No 2 Slot T Bar 37CN900002 2 Slot Tegular 1 2 in 37CN900042 7 16 in 37CN900052 3 8 in 37CN900062 5 16 in 37CN900072 1 4 in 37CN900082 3 Slot T Bar 37CN900012 3 Slot Tegular 1 2 in 37CN9...

Page 8: ...ckets can be used for ceiling alignment Fig 12 37HS Unit Installed in a T Bar Ceiling END TRIM Qty 50 T Bar Tegular Used on 37HS1 HS2 Color Package No 2 Slot T Bar White 37CM900132 2 Slot Tegular Whit...

Page 9: ...r on end of unit 9 If other units are to be connected to the first unit install T bar mounting brackets on each end of the adjoining units 10 Raise each unit above ceiling and lower into position Enga...

Page 10: ...e After alignment channel is installed filler trim piece can be snapped into place Fig 16 One Piece Mounting Bracket Installed on Diffuser End Fig 17 Installed Hanger Mounting Brackets Fig 18 Insertin...

Page 11: ...he unit is flush with the ceiling tile plane The recessed T bar may be painted usually black with white tiles to create an interesting grid pattern The 37HS unit cen ter diffuser when installed on the...

Page 12: ...is left to the discretion of the individual plasterer One typical method shown in Fig 21 shows 2 Model Moduline 37HS air termi nals installed Wire hangers with eyebolts for leveling and supporting the...

Page 13: ...h a special knife like tool to provide access to the ceiling cavity this ceiling also offers the kind of security re quired for such installations as classrooms and other institu tional applications T...

Page 14: ...14 Fig 23 37HS Moduline Units Installed in a Plaster Ceiling Fig 24 Typical Concealed Spline Ceiling Using 37HS Air Terminals Details...

Page 15: ...15 Fig 25 Typical Concealed Spline Ceiling Using 37HS Air Terminals...

Page 16: ...in Fig 27 NOTE Although 37A 37C and 37HS controls operate on simi lar principles the pressure relationships between the 3 models of units are different Therefore 37HS units cannot be operated with 37A...

Page 17: ...17 Fig 28 Control Arrangements Master Units with Slaves SINGLE MASTER UNIT INSTALLATION MASTER UNIT WITH ONE SLAVE MASTER UNIT WITH 3 SLAVES...

Page 18: ...ol air from the volume controller low side This causes the volume controller seat to move toward the bleed nozzle increasing the bellows output pressure thus closing the unit A minimum airflow can be...

Page 19: ...TANT VOLUME COOLING 37HS1 37HS900003 37HS2 37HS900003 37HS4 37HS900003 2 SYSTEM POWERED VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT 37HS1 37HS900001 37HS2 37HS900002 37HS4 37HS900004 3 SYSTEM POWERED...

Page 20: ...a diffuser thermostat in place of the wall thermostat replace constant volume package 37HS900003 and wall thermostat 37CM901012 with variable volume package 37HS900001 37HS1 37HS900002 37HS2 or 37HS9...

Page 21: ...VARIABLE VOLUME COOLING DIFFUSER THERMOSTAT ELECTRIC INTERLOCK TO FAN COIL OR BASEBOARD HEATING 37HS1 37HS900001 37CM900922 37HS2 37HS900002 37CM900922 37HS4 37HS900004 37CM900922 9 SYSTEM POWERED VAR...

Page 22: ...972 NO with 37HS900007 DA 37CM900982 NC with 37HS900008 RA 11 SYSTEM POWERED VARIABLE VOLUME COOLING WALL THERMOSTAT PNEUMATIC WARM UP FIRE SWITCH 37HS1 37HS900003 37CM901012 37HS900017 37HS2 37HS9000...

Page 23: ...the control side should be capped or plugged before installation Moisten the 2 O rings with water then push the filter into the unit end block until the standoffs rest on or close to the unit end plat...

Page 24: ...form around the legs of the diffuser spacer and lock onto the center diffuser See Fig 31 4 To prepare the control filter for installation be sure that the bellows chamber filter plug is pushed tightl...

Page 25: ...ume controller with water and push the controller directly into the filter extensions c Install the thermostat on the center diffuser then snap spring clip over thermostat and onto the side diffusers...

Page 26: ...0003 37HS4 37HS900003 SYSTEM POWERED WARM UP CONTROL QTY 1 Package No 37CM900152 37 A G4 00 45 2 C F M 110 100 80 40 HK 08ZZ016 FILTER MANIFOLD WITH FILTER EXTENSIONS DIFFUSER THERMOSTAT ASPIRATOR DIF...

Page 27: ...VALVE Voltage Package No 24 37CM900792 120 37CM900802 240 37CM900812 208 37CM900822 277 37CM900832 480 37CM900842 ELECTRIC INTERLOCK Used On Package No 37HS1 37CM900922 37HS2 37CM900922 37HS4 37CM9009...

Page 28: ...lenum size the model and the number of units in an air series on one controller See Tables 5 and 6 The 37HS1 unit with 5 x 7 size plenum is available with blank end only multiple units of this size wo...

Page 29: ...just maximum cfm lever to desired percent cfm FUNCTIONAL CHECKOUT With building temperature within Moduline thermostat set point limits 70 F to 80 F VAV supply air at design tem perature and VAV suppl...

Page 30: ...e fan static pressure control is operating properly so that starting the fan without airflow at terminals will not cause duct damage from overpressure 1 Check fan and system controls for proper hookup...

Page 31: ...o leak is detected the bellows are satisfactory 5 If unit appears satisfactory replace the thermostat vol ume controller assembly and connect it to the unit See Control Installation section page 23 6...

Page 32: ...efective Check thermostat operation replace thermostat if temperature at thermostat is below 75 F and airflow does not shut off when lever is at extreme red area Bellows Defective Check bellows remove...

Reviews: