67
Table 11B — 30RB210-390 Electrical Data — Dual Point Units
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2
%
; amps 10
%
.
2. Control power is derived from main power. No separate control power connection is
required.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
UNIT 30RB
UNIT VOLTAGE
NO HYDRONIC PACKAGE
3 HP PUMP, 1750 RPM
5 HP PUMP, 1750 RPM
V-Hz (3 Ph)
Supplied
MCA
MOCP
ICF
Rec Fuse
Size
MCA
MOCP
ICF
Rec
Fuse
Size
MCA
MOCP
ICF
Rec
Fuse
Size
Min
Max
XL
XL
XL
XL
XL
XL
XL
XL
XL
210
208/230-60
187
253
626.7/353.9
700/400
1068.9/796.2
700/400
—
—
—
—
—
—
—
—
380-60
342
418
327.7/186.4
350/225
581.1/439.7
350/200
—
—
—
—
—
—
—
—
460-60
414
506
233.3/200.0
250/225
441.3/408.0
250/225
—
—
—
—
—
—
—
—
575-60
518
633
188.8/162.0
200/175
356.4/329.6
200/175
—
—
—
—
—
—
—
—
225
208/230-60
187
253
684.3/353.9
700/400
1126.5/796.2
700/400
—
—
—
—
—
—
—
—
380-60
342
418
360.4/186.4
400/225
613.8/439.7
400/200
—
—
—
—
—
—
—
—
460-60
414
506
260.0/200.0
300/225
468.0/408.0
300/225
—
—
—
—
—
—
—
—
575-60
518
633
211.9/162.0
225/175
379.5/329.6
225/175
—
—
—
—
—
—
—
—
250
208/230-60
187
253
684.3/472.0
700/500
1126.5/914.3
700/500
—
—
—
—
—
—
—
—
380-60
342
418
360.4/248.7
400/250
613.8/502.1
400/250
—
—
—
—
—
—
—
—
460-60
414
506
303.2/209.2
350/250
511.2/417.2
350/225
—
—
—
—
—
—
—
—
575-60
518
633
246.4/170.0
250/200
414.1/337.6
250/200
—
—
—
—
—
—
—
—
275
208/230-60
187
253
920.5/353.9
1000/400
1362.7/796.2
1000/400
—
—
—
—
—
—
—
—
380-60
342
418
485.2/186.4
500/225
738.5/439.7
500/200
—
—
—
—
—
—
—
—
460-60
414
506
408.0/156.8
450/175
616.0/364.8
450/175
—
—
—
—
—
—
—
—
575-60
518
633
331.5/127.5
350/150
499.1/295.1
350/150
—
—
—
—
—
—
—
—
300
208/230-60
187
253
920.5/472.0
1000/500
1362.7/914.3
1000/500
—
—
—
—
—
—
—
—
380-60
342
418
485.2/248.7
500/250
738.5/502.1
500/250
—
—
—
—
—
—
—
—
460-60
414
506
408.0/209.2
450/250
616.0/417.2
450/225
—
—
—
—
—
—
—
—
575-60
518
633
331.5/170.0
350/200
499.1/337.6
350/200
—
—
—
—
—
—
—
—
315A
208/230-60
187
253
519.8/243.8
600/300
962.0/635.0
600/300
—
—
—
—
—
—
—
—
380-60
342
418
274.9/124.8
300/150
528.3/336.8
300/150
—
—
—
—
—
—
—
—
460-60
414
506
230.8/106.3
250/125
438.8/280.4
250/125
—
—
—
—
—
—
—
—
575-60
518
633
187.3/ 85.2
200/110
354.9/227.4
200/100
—
—
—
—
—
—
—
—
315B
208/230-60
187
253
519.8/243.8
600/300
962.0/635.0
600/300
—
—
—
—
—
—
—
—
460-60
414
506
230.8/106.3
250/125
438.8/280.4
250/125
—
—
—
—
—
—
—
—
575-60
518
633
187.3/ 85.2
200/110
354.9/227.4
200/100
—
—
—
—
—
—
—
—
380-60
342
418
274.9/124.8
300/150
528.3/336.8
300/150
—
—
—
—
—
—
—
—
330A
208/230-60
187
253
519.8/306.2
600/400
962.0/748.4
600/350
—
—
—
—
—
—
—
—
380-60
342
418
274.9/160.2
300/200
528.3/413.6
300/175
—
—
—
—
—
—
—
—
460-60
414
506
230.8/135.2
250/175
438.8/343.2
250/150
—
—
—
—
—
—
—
—
575-60
518
633
187.3/110.2
200/125
354.9/277.8
200/125
—
—
—
—
—
—
—
—
330B
208/230-60
187
253
519.8/243.8
600/300
962.0/635.0
600/300
—
—
—
—
—
—
—
—
380-60
342
418
274.9/124.8
300/150
528.3/336.8
300/150
—
—
—
—
—
—
—
—
460-60
414
506
230.8/106.3
250/125
438.8/280.4
250/125
—
—
—
—
—
—
—
—
575-60
518
633
187.3/ 85.2
200/110
354.9/227.4
200/100
—
—
—
—
—
—
—
—
345A
208/230-60
187
253
519.8/306.2
600/400
962.0/748.4
600/350
—
—
—
—
—
—
—
—
380-60
342
418
274.9/160.2
300/200
528.3/413.6
300/175
—
—
—
—
—
—
—
—
460-60
414
506
230.8/135.2
250/175
438.8/343.2
250/150
—
—
—
—
—
—
—
—
575-60
518
633
187.3/110.2
200/125
354.9/277.8
200/125
—
—
—
—
—
—
—
—
345B
208/230-60
187
253
519.8/306.2
600/400
962.0/748.4
600/350
—
—
—
—
—
—
—
—
380-60
342
418
274.9/160.2
300/200
528.3/413.6
300/175
—
—
—
—
—
—
—
—
460-60
414
506
230.8/135.2
250/175
438.8/343.2
250/150
—
—
—
—
—
—
—
—
575-60
518
633
187.3/110.2
200/125
354.9/277.8
200/125
—
—
—
—
—
—
—
—
360A
208/230-60
187
253
543.7/400.4
600/450
985.9/842.6
600/450
—
—
—
—
—
—
—
—
380-60
342
418
288.0/209.5
300/250
541.3/462.9
300/225
—
—
—
—
—
—
—
—
460-60
414
506
241.6/176.8
250/200
449.6/384.8
250/200
—
—
—
—
—
—
—
—
575-60
518
633
195.9/144.1
225/175
363.5/311.7
225/175
—
—
—
—
—
—
—
—
360B
208/230-60
187
253
519.8/306.2
600/400
962.0/748.4
600/350
—
—
—
—
—
—
—
—
380-60
342
418
274.9/160.2
300/200
528.3/413.6
300/175
—
—
—
—
—
—
—
—
460-60
414
506
230.8/135.2
250/175
438.8/343.2
250/150
—
—
—
—
—
—
—
—
575-60
518
633
187.3/110.2
200/125
354.9/277.8
200/125
—
—
—
—
—
—
—
—
390A
208/230-60
187
253
543.7/400.4
600/450
985.9/842.6
600/450
—
—
—
—
—
—
—
—
380-60
342
418
288.0/209.5
300/250
541.3/462.9
300/225
—
—
—
—
—
—
—
—
460-60
414
506
241.6/176.8
250/200
449.6/384.8
250/200
—
—
—
—
—
—
—
—
575-60
518
633
195.9/144.1
225/175
363.5/311.7
225/175
—
—
—
—
—
—
—
—
390B
208/230-60
187
253
543.7/400.4
600/450
985.9/842.6
600/450
—
—
—
—
—
—
—
—
380-60
342
418
288.0/209.5
300/250
541.3/462.9
300/225
—
—
—
—
—
—
—
—
460-60
414
506
241.6/176.8
250/200
449.6/384.8
250/200
—
—
—
—
—
—
—
—
575-60
518
633
195.9/144.1
225/175
363.5/311.7
225/175
—
—
—
—
—
—
—
—
AWG
—
American Wire Gage
ICF
—
Instantaneous Current Flow (Ckt1/Ckt2)
MCA
—
Minimum Circuit Amps (Ckt1/Ckt2)
MOCP —
Maximum Overcurrent Protection (Ckt1/Ckt2)
XL
—
Across-the-Line Start
208/230
460
575 v only