background image

42

NOTE: Locate the 3-way valve as close as possible to the

chiller to minimize head pressure control response time.

 

FOR ALL UNITS
Dual Chiller Control Option — If the dual chiller algorithm is

used, and the machines are installed in parallel, an additional

chilled water sensor must be installed for each module. For

30RB315-390, a factory-supplied thermistor and well are

shipped in the control box of each module. Install the wells in

the common leaving water header. See Fig. 34.

Parallel chiller control with dedicated pumps is recom-

mended. Chiller must start and stop its own water pump locat-

ed in its own piping. If pumps are not dedicated for each

chiller, then isolation valves are required. Each chiller must

open and close its own isolation valve through the unit control

(the valve must be connected to the pump outputs).

See Dual Chiller Control Option section on page 58 for

more dual chiller leaving water sensor information.
Minimum Loop Volume — The preferred minimum loop vol-

ume is dependent on the type of application. In order to obtain

leaving water temperature stability for comfort cooling appli-

cations, a minimum of 3 gallons per ton (3.25 liters per kW) is

required on all unit sizes. For process cooling applications, ap-

plications where high stability is critical, or operation at

ambient temperatures below 32 F (0° C) is expected, the loop

volume should be increased to 6 to 10 gallons per ton (6.46 to

10.76 liters per kW) of cooling.

In order to achieve this volume, it may be necessary to add a

water storage tank to the water loop. If a storage tank is added

to the system, it should be properly vented so that the tank can

be completely filled and all air eliminated. Failure to do so

could cause lack of pump stability and poor system operation.

Any storage tank that is placed in the water loop should

have internal baffles to allow thorough mixing of the fluid. See

Fig. 35. For units with heat reclaim option, a minimum con-

denser loop volume of 6 gallons per ton of heating (0.5 to 0.83

gallons [1.9 to 3.1 L] per 100 Btu/h of heating) capacity is nec-

essary. In come cases, this will require the installation of a hot-

water buffer tank.

System Piping — Proper system design and installation proce-

dures should be followed closely. The system must be

constructed with pressure tight components and thoroughly

tested for leaks.

Installation of water systems should follow sound engineer-

ing practice as well as applicable local and industry standards.

Improperly designed or installed systems may cause

unsatisfactory operation and/or system failure. Consult a water

treatment specialist or appropriate literature for information

regarding filtration, water treatment, and control devices.

Figure 29 shows a typical installation with components that

might be installed with the hydronic package of the 30RB unit.
NOTE: It is recommended for units with the hydronic package

that an inlet isolation (shutoff) valve be placed exterior to the

unit to allow removal and service of the entire pump assembly,

if necessary. The hydronic package is supplied from the factory

with a combination valve for isolation of leaving water. Also,

if the unit is isolated with valves, a properly sized pressure

relief valve is recommended and should be installed in the pip-

ing between the unit and the valves, following all applicable

local codes.
Air Separation — For proper system operation, it is essential

that water loops be installed with proper means to manage air

in the system. Free air in the system can cause noise, reduce

terminal output, stop flow, or even cause pump failure due to

pump cavitation. For closed systems, equipment should be

provided to eliminate all air from the system.

The amount of air that water can hold in solution depends

on the pressure and temperature of the water/air mixture. Air is

less soluble at higher temperatures and at lower pressures.

Therefore, separation can best be done at the point of highest

water temperature and lowest pressure. Typically, this point

would be on the suction side of the pump as the water is return-

ing from the system or terminals. This is generally the optimal

place to install an air separator, if possible.

1. Install automatic air vents at all high points in the system.

(If the 30RB unit is located at the high point of the system,

a vent can be installed on the piping leaving the heat ex-

changer on the 

1

/

4

 in. NPT female port.)

2. Install an air separator in the water loop, at the place

where the water is at higher temperatures and lower pres-

sures — usually in the chilled water return piping. On a

primary-secondary system, the highest temperature water

is normally in the secondary loop, close to the decoupler.

Preference should be given to that point on the system

(see Fig. 36). In-line or centrifugal air separators are read-

ily available in the field.

It may not be possible to install air separators at the place of

the highest temperature and lowest pressure. In such cases,

preference should be given to the points of highest temperature.

It is important that the pipe be sized correctly so that free air

can be moved to the point of separation. Generally, a water

velocity of at least 2 feet per second (0.6 m per second) will

keep free air entrained and prevent it from forming air pockets.

Automatic vents should be installed at all physically elevat-

ed points in the system so that air can be eliminated during sys-

tem operation. Provisions should also be made for manual

venting during the water loop fill. 

S

UPPLY

RETURN

CON

S

TANT 

S

PEED

CIRCULATING PUMP

S

HEAT RECLAIM
CONDEN

S

ER

MODULATING 

3

-WAY

CONTROL VALVE

40 FT MAX

Fig. 33A — Three-Way Head Pressure Control 

Valve Location (Preferred)

a30-4825

MODULATING 

3

-WAY CONTROL

VALVE (A

S

 CLO

S

E TO CONDEN

S

ER

A

S

 PO

SS

IBLE)

HEAT RECLAIM
CONDEN

S

ER

CON

S

TANT 

S

PEED

CIRCULATING PUMP

S

RETURN

S

UPPLY

Fig. 33B — Three-Way Head Pressure Control 

Valve Location (Alternate)

a30-4824

IMPORTANT: Automatic vents should be located in

accessible locations for maintenance purposes and

protected from freezing.

Summary of Contents for MINIMUM LOAD CONTROL ACCESSORY 30RB060-390

Page 1: ...71 SAFETY CONSIDERATIONS Installing starting up and servicing air conditioning equipment can be hazardous due to system pressures electrical components and equipment location Only trained qualified in...

Page 2: ...unit may be mounted on a level pad directly on the base rails on rails along the long axis of the machine or on vibration isolation springs For all units ensure placement area is strong enough to sup...

Page 3: ...s shipped with a shipping bag the bag must be removed to gain access to the rigging holes in the base rail On export units with a full crate the crate sides must be removed to aid in rigging If overhe...

Page 4: ...tegral Cooler Microchannel MCHX CRN Canada 5 Integral Cooler Cooler Heater Microchannel MCHX CRN Canada G Integral Cooler no CRN H Integral Cooler Cooler Heater no CRN K Integral Cooler Microchannel M...

Page 5: ...L Terminal Block Cmpr Blankets Cmpr Enclosures High SCCR V Single Point Power Connections XL Non Fused Disconnect Cmpr Blankets Cmpr Enclosures W Single Point Power Connections XL Non Fused Disconnect...

Page 6: ...4 COIL SERVICE AREA NO PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE NOTE 4 COOLER VENT 1 4 PUMP PACKAGE LEAVING WATER 4 VICTAULIC COOLER DRAIN 3 4 NPT PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE DETAIL...

Page 7: ...TER 4 VICTAULIC SEE NOTE 4 COOLER VENT 1 4 NTP PUMP PACKAGE LEAVING WATER 4 VICTAULIC COOLER DRAIN 3 4 NPT PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE DETAIL A COOLER TUBE SERVICE AREA DETAIL A SCALE...

Page 8: ...8 KNOCKOUT TO BE USED FOR LOCATING FIELD POWER WIRING BACnet COMMUNICATION OPTION KNOCKOUT FOR 1 2 CONDUIT COOLER VENT 1 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE U...

Page 9: ...ne and filter drier of each circuit and have 1 4 flare connection 4 Units without a pump package have the same leaving water connection Y and Z dimensions entering water and Pump Discharge X dimen sio...

Page 10: ...RVICE AREA COIL SERVICE AREA COOLER VENT 1 4 NTP COOLER DRAIN 3 4 NPT PUMP PACKAGE LEAVING WATER 6 VICTAULIC NO PUMP PACKAGE ENTERING WATER 6 VICTAULIC SEE NOTE 4 SEE DETAIL B PUMP PACKAGE ENTERING WA...

Page 11: ...SER TUBE SERVICE AREA COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT SEE DETAIL B CONDENSER DRAIN 3 8 NPT AIR FLOW POWER BOX 230V CONTROL POWER BOX 380V 460V 575V 7 8 KNOCKOUT TO BE USED FOR LOCATING FIELD...

Page 12: ...te for draining 3 Temperature relief devices located on suction line liquid line and filter drier of each circuit and have 1 4 flare connection 4 No pump package leaving water connection is same size...

Page 13: ...CTAULIC SEE DETAIL B CONDENSER DRAIN 3 8 NPT AIR FLOW 7 8 KNOCKOUT TO BE USED FOR LOCATING FIELD POWER WIRING SCROLLING MARQUEE DISPLAY FIELD CONTROL WIRING FAN ELECTRICAL BOX 230V ONLY FEB POWER BOX...

Page 14: ...on suction line liquid line and fil ter drier of each circuit and have 1 4 flare connection 3 Dimensions are in mm inches 4 Allow 8 ft 2 4 m of service access on either side of unit for con denser co...

Page 15: ...quid line and filter drier of each circuit and have 1 4 flare connection 4 Units without a pump package have the same leaving water connection Y and Z dimensions entering water and Pump Discharge X di...

Page 16: ...d on suction line liquid line and filter drier of each circuit and have 1 4 flare connection 3 Dimensions are in mm inches 4 Allow 8 ft 2 4 m of service access on either side of unit for condenser coi...

Page 17: ...38 00 1 50 938 35 36 94 215 73 8 49 WEIGHT CU AL lb kg MAX WEIGHT CU AL PUMP lb kg WEIGHT CU CU lb kg MAX WEIGHT CU CU PUMP lb kg WEIGHT MCHX lb kg MAX WEIGHT MCHX PUMP lb kg CENTER OF GRAVITY PUMP S...

Page 18: ...RAIN 3 4 NPT COOLER ENTERING WATER 6 VICTAULIC COOLER LEAVING WATER 6 VICTAULIC CONDENSER DRAIN 3 8 NPT SCROLLING MARQUEE DISPLAY FIELD CONTROL WIRING FAN ELECTRICAL BOX FEB ALL VOLTAGES BACnet COMMUN...

Page 19: ...6 VICTAULIC NO PUMP PACKAGE ENTERING WATER 6 VICTAULIC SEE NOTE 4 PUMP PACKAGE ENTERING WATER 6 VICTAULIC COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT SEE DETAIL B VIE...

Page 20: ...TER 6 VICTAULIC COOLER ENTERING WATER 6 VICTAULIC CONDENSER DRAIN 3 8 NPT AIR FLOW FIELD CONTROL WIRING FAN ELECTRICAL BOX FEB ALL VOLTAGES POWER BOX 230V ONLY CKT A 7 8 KNOCKOUT TO BE USED FOR LOCATI...

Page 21: ...LER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A CIRCUIT A COMPRESSORS CIRCUIT B COMPRESSORS POWER BOX 1 230V CKT B 380V 460V 575V CKT A B C COIL SERV...

Page 22: ...T 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A CIRCUIT A COMPRESSORS CIRCUIT B COMPRESSORS CIRCUIT C COMPRESSORS POWER BOX 1 380V 460V...

Page 23: ...COIL SERVICE AREA LEAVING WATER 6 VICTAULIC ENTERING WATER 6 VICTAULIC COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A SEE DET...

Page 24: ...IRCUIT B COMPRESSORS CIRCUIT C COMPRESSORS COIL SERVICE AREA COIL SERVICE AREA LEAVING WATER 6 VICTAULIC ENTERING WATER 6 VICTAULIC COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA A...

Page 25: ...475 170 1055 2052 1024 1374 2809 1485 9 799 UNIT 30RB MOUNTING WEIGHT lb No Pump MCHX A B C D E F G H Total 190 1007 1278 1367 1014 1362 1846 1785 1405 11 064 210 852 1677 1989 793 1219 2831 2269 114...

Page 26: ...UNIT 30RB MOUNTING WEIGHT lb Single Pump Cu Cu A B C D E F G H Total 190 1257 1718 2095 1263 1638 2374 2084 1684 14 113 UNIT 30RB MOUNTING WEIGHT kg Single Pump Al Cu A B C D Total 060 493 512 559 538...

Page 27: ...9 8 166 UNIT 30RB MOUNTING WEIGHT lb Dual Pump Cu Cu A B C D E F Total 120 837 2498 1169 1054 2739 1161 9 457 130 850 2616 1193 1252 2953 1069 9 933 150 1015 3112 1270 1240 3411 1336 11 384 160 1481 3...

Page 28: ...11315 UNIT 30RB MOUNTING WEIGHT lb Heat Reclaim MCHX A B C D E F G H Total 190 962 1311 1461 937 1519 2620 2296 1474 12580 UNIT 30RB MOUNTING WEIGHT kg Heat Reclaim MCHX A B C D Total 060 538 533 529...

Page 29: ...ase Rail Cross Section 0 1 3 4 44 mm 1 50 DIA 38 mm RIGGING HOLE B B 0 5 127 mm 0 875 DIA 22 mm MOUNTING HOLE MOUNTING PLATE 0 3 15 16 100 mm 0 1 9 16 39 89 mm REF 0 7 7 8 200 mm VIEW B B BOTTOM VIEW...

Page 30: ...970 1518 Net Fluid Volume gal 28 2 28 2 31 3 31 3 31 3 45 8 45 8 45 8 73 5 Maximum Refrigerant Pressure psig 445 445 445 445 445 445 445 445 445 Maximum Water Side Pressure without Pumps psig 300 300...

Page 31: ...28 33 COOLER Direct Expansion Shell and Tube Type Weight empty lb 1518 1518 1518 2382 2382 2382 2382 2382 Net Fluid Volume gal 73 5 73 5 73 5 86 6 86 6 86 6 86 6 86 6 Maximum Refrigerant Pressure psig...

Page 32: ...388 440 440 440 689 Net Fluid Volume L 106 106 118 118 118 173 173 173 278 Maximum Refrigerant Pressure kPa 3068 3068 3068 3068 3068 3068 3068 3068 3068 Maximum Water Side Pressure without Pumps kPa 2...

Page 33: ...COOLER Direct Expansion Shell and Tube Type Weight empty kg 689 689 689 1080 1080 1080 1080 1080 Net Fluid Volume L 278 278 278 327 327 327 327 327 Maximum Refrigerant Pressure kPa 3068 3068 3068 306...

Page 34: ...52 5 No Capacity Steps Standard 14 14 14 15 16 Optional Maximum 16 16 16 17 18 Minimum Capacity Step Standard 6 6 7 7 6 Optional 5 4 6 5 5 Capacity Module A Ckt A 31 30 29 27 25 Module A Ckt B 19 22...

Page 35: ...8 No Capacity Steps Standard 14 14 14 15 16 Optional Maximum 16 16 16 17 18 Minimum Capacity Step Standard 6 6 7 7 6 Optional 5 4 6 5 5 Capacity Module A Ckt A 31 30 29 27 25 Module A Ckt B 19 22 21 2...

Page 36: ...36 Fig 24 Unit Rigging Label Detail 30RB060 150...

Page 37: ...37 Fig 25 Unit Rigging Label Detail 30RB160 300...

Page 38: ...inlet and outlet piping Locate valves in return and supply cooler water and heat reclaim lines as close to the chiller as possible In sound sensitive applications consider the installation of piping v...

Page 39: ...pump for connection to an expansion tank Install the tank in accordance with the manufacturer s instructions Figures 29 and 30 illustrate typical single and dual pump packages Two drain connections a...

Page 40: ...units can be equipped with a factory installed heat reclaim package consisting of a shell and tube condenser PT PT T1 T2 FS PP PP D D V D PT PT Chilled Water Out Heater Optional Heater E D PT Air Sep...

Page 41: ...rement a properly sized 3 way valve must be field installed This valve will facilitate cold water start up water temperatures below 68 F 20 C and it also will be able to maintain proper head pressure...

Page 42: ...let isolation shutoff valve be placed exterior to the unit to allow removal and service of the entire pump assembly if necessary The hydronic package is supplied from the factory with a combination va...

Page 43: ...Option Thermistor Location LWT Leaving Water Fluid Temperature Field Wiring Field Communication Wiring a30 3185ef Tank Installation BAD BAD GOOD GOOD Fig 35 Tank Baffling Distribution Pump Expansion...

Page 44: ...al of particulates from the chilled water loop Using the combination valve and the field installed isolation valve at the inlet the strainer can be isolated from the chilled water loop to be cleaned T...

Page 45: ...ry secondary systems If a diaphragm expansion tank is utilized a flexible diaphragm physically separates the water air interface it is not recommended to have any air in the water loop See the section...

Page 46: ...in 6 00 in 3 hp 5 hp 7 5 hp 2 hp 80 80 78 78 73 73 65 65 54 40 6 50 in 7 00 in 7 50 in NPSHr N P S H r 81 12 2 40 3 0 10 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30R...

Page 47: ...5 2 50 12 2 40 9 1 30 6 1 20 3 0 10 0 0 0 N P S H r NPSHr LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump...

Page 48: ...000 63 09 3450 RPM NPSHr N P S H r a30 5468 a30 5469 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump Impe...

Page 49: ...PM N P S H r 5 90 in 69 69 65 65 60 60 52 52 42 31 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 5 25 in LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomencl...

Page 50: ...24 4 80 18 3 60 12 2 40 6 1 20 0 0 0 500 31 55 3450 RPM N P S H r NPSHr LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Re...

Page 51: ...00 63 09 3450 RPM NPSHr N P S H r a30 5472 a30 5470 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump Impel...

Page 52: ...op It should be noted that these curves are for fresh water and clean heat exchangers they do not apply to heat exchangers with fouling To read the chart subtract the readings of the two pressure gage...

Page 53: ...l from the sensor Switch S2 01 must be set to Off default set ting for 0 10 vdc or On for 0 4 20 mA The switch is located behind the display The cover must be removed and the display will snap off to...

Page 54: ...protection of the chiller in case of power failure during subfreezing ambi ent temperatures or in other cases where water temperature falls below the freezing mark other methods must be used Ap propr...

Page 55: ...85 44 16 a30 4822 Fig 55 30RB060 110 Optional Heat Reclaim Pressure Drop Curves HEAT RECLAIM VESSEL PRESSURE DROP CURVES 30RB 120 190 TON 0 0 100 200 300 400 500 600 700 800 900 1000 GPM ft wg 120 15...

Page 56: ...r warranty does not cover damage due to freezing 5 Units with the heat reclaim option are supplied with a heater to protect the reclaim condenser down to 0 F 18 C If the unit controls the heat reclaim...

Page 57: ...onditioned space to the power box es be sealed to prevent airflow and moisture into the control box Duplex units require at least two separate power supplies at least one for each module depending on...

Page 58: ...S 1 Combination is identified as COMB1 in Fig 58 2 Power L is the same as COMB1 in Fig 58 3 PEB or Power Electrical Box is shown in Fig 58 30RB UNIT SIZE VOLTAGE ELECTRICAL OPTION CONNECTIONS MAIN POW...

Page 59: ...SHUTDOWN RELAY IS 10 VA SEALED 25 VA INRUSH AT 24V FIELD POWER SUPPLY IS NOT REQUIRED ICE DONE DEMAND LIMIT STEP 2 OCCUPANCY OVERRIDE DUAL SETPOINT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TB5 TB6 1 2 3 4...

Page 60: ...D 13 OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP1 PMP1 STARTER TERMINALS 13 AND 15 OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP2 PMP2 STARTER THE MAXIMUM LOAD ALLOWED FOR THE CHILLED WATER PUMP RELAY...

Page 61: ...and 15 of TB7 are for external connection of heat reclaim remote enable switch 5 Terminals 5 through 13 of TB7 are for the connection of factory installed solenoid valve control wiring LEGEND Field C...

Page 62: ...460 60 414 506 147 9 175 355 9 175 152 1 175 360 8 175 155 0 175 363 9 175 575 60 518 633 119 8 150 287 4 150 123 1 150 291 3 150 125 2 150 293 8 150 080 208 230 60 187 253 366 5 400 757 8 400 381 9...

Page 63: ...253 455 6 500 901 6 500 458 6 500 909 5 500 470 3 500 925 7 500 380 60 342 418 239 2 250 494 3 250 240 9 250 498 7 250 247 9 250 507 5 300 460 60 414 506 201 5 225 411 0 225 202 9 225 414 6 225 208 4...

Page 64: ...30 9 450 575 60 518 633 342 3 350 509 9 350 225 208 230 60 187 253 380 60 342 418 534 5 600 787 8 600 460 60 414 506 449 6 450 657 6 450 575 60 518 633 365 4 400 533 0 400 250 208 230 60 187 253 380 6...

Page 65: ...0 380 60 342 418 150 1 86 4 175 110 403 5 298 4 175 100 158 2 86 4 200 110 413 2 298 4 175 100 460 60 414 506 126 0 73 6 150 100 334 0 247 7 150 90 133 1 73 6 150 100 342 0 247 7 150 90 575 60 518 633...

Page 66: ...125 349 2 301 6 150 110 143 0 93 6 175 125 356 5 301 6 175 110 575 60 518 633 110 3 76 3 125 110 279 1 243 9 125 90 111 4 76 3 125 110 282 0 243 9 125 90 116 2 76 3 150 110 287 8 243 9 125 90 110 208...

Page 67: ...225 738 5 439 7 500 200 460 60 414 506 408 0 156 8 450 175 616 0 364 8 450 175 575 60 518 633 331 5 127 5 350 150 499 1 295 1 350 150 300 208 230 60 187 253 920 5 472 0 1000 500 1362 7 914 3 1000 500...

Page 68: ...A 345B 360B 208 230 60 6 11 9 4 11 9 380 60 6 6 5 4 6 5 460 60 6 5 4 4 5 4 575 60 6 4 3 4 4 3 190 360A 390A 390B 208 230 60 6 11 9 6 11 9 380 60 6 6 5 6 6 5 460 60 6 5 4 6 5 4 575 60 6 4 3 6 4 3 210 2...

Page 69: ...380 60 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 460 60 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 575 60 33 9 210 33 9 210 33 9 210 33 9 210 33 9 210 33 9 21...

Page 70: ...units offer several non CCN translators Refer to the separate instal lation instructions for additional wiring steps Step 7 Install Accessories A number of accessories are available to provide the fol...

Page 71: ...erican Wire Gage or 24 AWG low capacitance twisted stranded shielded copper wire The maximum length is 2000 ft Install a BT485 terminator on the first and last controller on a network segment to add b...

Page 72: ...7 6 5 4 32 1 0 9 8 7 6 5 4 32 1 0 9 BACNET BAUD RATE DIP SWITCHES ADDRESS ROTARY SWITCHES POWER LED RUN LED ERROR LED BACNET CONNECTION BAS PORT BT485 TERMINATOR Tx2 LED Rx2 LED Tx1 LED Rx1 LED EIA 48...

Page 73: ...perature Rating SmokeGard 167 F 75 C Halar 40 to 302 F 40 to 150 C Voltage 300 Vac power limited Listing UL NEC CL2P or better Fig 65 BT485 Terminator Installation AWG American Wire Gage CL2P Class 2...

Page 74: ......

Page 75: ......

Page 76: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300124 01 Printed in U S A Form 30RB 21SI Pg 76 318 12 13 Replaces 30RB...

Reviews: