background image

57

3. Replace the drain plug and add 2 gallons (7.6 liters) of a

suitable corrosion-inhibited anti-freeze solution such as

propylene glycol to the cooler to prevent freezing of any

remaining water in system. Antifreeze can be added

through the vent on top of cooler. If the unit has a hydron-

ic pump package, the pump must also be treated in the

same manner.

4. Open one of the thermistor connections to allow air to

escape the vessel and the anti-freeze to enter.

5. At the beginning of the next cooling season, be sure that

there is refrigerant pressure on each circuit before

refilling cooler, add recommended inhibitor, and reset the

CB-HT (circuit breaker heater) (if opened) or restore

power.

HEAT RECLAIM SYSTEM — At the end of each cooling

season the fluid should be drained from the system. However,

due to the heat reclaim condenser circuiting, some fluid will re-

main in the condenser after draining. To prevent freeze-up

damage to the condenser tubes perform the following

procedure.

1. If the heat reclaim condenser will not be drained do not

shut off power disconnect during off-season shutdown. If

the condenser will be drained, deenergize the heaters to

prevent damage and possible safety hazards when drain-

ing, or when there is no liquid in the system. Open the

condenser heater circuit breaker, CB-CDH7 to deenergize

the heaters. Drain the fluid from the system.

2. Isolate the condenser from the rest of the system with wa-

ter shut off valves.

3. Completely fill the condenser with an appropriate

amount of inhibited ethylene glycol solution (or other

suitable corrosion-inhibitive antifreeze) for 15 F

(8.3 C) below the expected low ambient conditions.

4. Leave the condenser filled with the antifreeze solution for

the winter, or drain if desired. Be sure to deenergize heat-

ers as explained in Step 1 to prevent damages. Use an ap-

proved method of disposal when removing the antifreeze

solution.

5. At the beginning of the next cooling season, be sure that

there is refrigerant pressure on each circuit before refill-

ing the condenser circuit, add recommended inhibitor and

reset the CB-CDHT (if opened) to restore power.

Step 6 — Make Electrical Connections

POWER SUPPLY — The  electrical  characteristics  of  the

available power supply must agree with the unit nameplate

rating. Supply voltage must be within the limits shown.

Some units have options for multiple power connections.

See Table 9 and Fig. 58 for elecrical connection information.

See Tables 10A-14 for electrical requirements.

POWER WIRING — All power wiring must comply with

applicable local and national codes. Install field-supplied

branch circuit fused disconnect per NEC of a type that can be

locked OFF or OPEN. Disconnect must be within sight and

readily accessible from the unit in compliance with NEC

Article 440-14. In the power box, 

7

/

8

 in. holes are provided for

power entry. The holes will need to be enlarged to accept the

appropriate conduit. NEC also requires all conduits from a

conditioned space to the power box(es) be sealed to prevent

airflow and moisture into the control box.

Duplex units require at least two separate power supplies, at

least one for each module, depending on the power supply

option ordered. 
General Wiring Notes:

1. The control circuit does NOT require a separate power

source. A step-down transformer from the main three-

phase power supply obtains control circuit power. Be sure

that the appropriate connection tap is connected on all

transformers for the supply voltage. Up to three terminal

blocks are provided for field-wired control devices.

2. Cooler heat reclaim condenser and pump heaters (if fac-

tory installed) are wired in the control circuit so they are

operable as long as the main power supply to the unit is

ON. A factory-installed and set overload device protects

them.

NOTE: The field-supplied disconnect should never be off

except when unit is being serviced or is to be down for a pro-

longed period, in which case the cooler and heat reclaim con-

denser should be drained if not properly protected.

3. Power entry depends on the size and power entry option

ordered.

4. Maximum field wire sizes allowed by lugs on terminal

block/non-fused disconnect are listed in Tables 10 and 11.

5. Terminals for field power supply are suitable for copper

conductors. Insulation must be rated 75 C minimum. 

CONTROL POWER — Control power is obtained from the

main power supply and does NOT require a separate source. A

toggle switch (marked SW2 on the unit label diagram and by

the switch) allows the control circuit to be manually

disconnected when necessary. Cooler heat reclaim condenser

and pump heaters (if installed) are in an inoperable state when

this switch is in the Off position.

FIELD CONTROL OPTION WIRING — Install  field  con-

trol wiring options. See Fig. 58 and 59. Some options, such as

4 to 20 mA demand limit that requires the energy management

module, may require that accessories be installed first if not

factory installed for terminal connections.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all discon-

nect locations to alert others not to restore power until work

is completed.

IMPORTANT: Operating unit on improper supply

voltage or with excessive phase imbalance constitutes

abuse and may adversely affect Carrier warranty.

IMPORTANT: To ensure power to the heaters, make

sure power to the unit is always on (except during ser-

vice or a prolonged shutdown).

CAUTION

Proper rotation of condenser fan(s) and pump(s) MUST be

verified before pumps or compressors are started. Consult

the Controls, Start-Up, Operation, Service and Trouble-

shooting guide provided with 30RB060-390 units for cor-

rect procedure. Improper pump rotation can cause

permanent damage to pump impeller and housing. If

pump(s) have been removed for trimming, verify wiring is

reconnected in the original manner.

IMPORTANT: For 208-v systems, the connection tap

for all transformers must be changed. The factory

default setting is for 230-v. Failure to connect to the

proper tap may result in unreliable operation.

Summary of Contents for MINIMUM LOAD CONTROL ACCESSORY 30RB060-390

Page 1: ...71 SAFETY CONSIDERATIONS Installing starting up and servicing air conditioning equipment can be hazardous due to system pressures electrical components and equipment location Only trained qualified in...

Page 2: ...unit may be mounted on a level pad directly on the base rails on rails along the long axis of the machine or on vibration isolation springs For all units ensure placement area is strong enough to sup...

Page 3: ...s shipped with a shipping bag the bag must be removed to gain access to the rigging holes in the base rail On export units with a full crate the crate sides must be removed to aid in rigging If overhe...

Page 4: ...tegral Cooler Microchannel MCHX CRN Canada 5 Integral Cooler Cooler Heater Microchannel MCHX CRN Canada G Integral Cooler no CRN H Integral Cooler Cooler Heater no CRN K Integral Cooler Microchannel M...

Page 5: ...L Terminal Block Cmpr Blankets Cmpr Enclosures High SCCR V Single Point Power Connections XL Non Fused Disconnect Cmpr Blankets Cmpr Enclosures W Single Point Power Connections XL Non Fused Disconnect...

Page 6: ...4 COIL SERVICE AREA NO PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE NOTE 4 COOLER VENT 1 4 PUMP PACKAGE LEAVING WATER 4 VICTAULIC COOLER DRAIN 3 4 NPT PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE DETAIL...

Page 7: ...TER 4 VICTAULIC SEE NOTE 4 COOLER VENT 1 4 NTP PUMP PACKAGE LEAVING WATER 4 VICTAULIC COOLER DRAIN 3 4 NPT PUMP PACKAGE ENTERING WATER 4 VICTAULIC SEE DETAIL A COOLER TUBE SERVICE AREA DETAIL A SCALE...

Page 8: ...8 KNOCKOUT TO BE USED FOR LOCATING FIELD POWER WIRING BACnet COMMUNICATION OPTION KNOCKOUT FOR 1 2 CONDUIT COOLER VENT 1 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE U...

Page 9: ...ne and filter drier of each circuit and have 1 4 flare connection 4 Units without a pump package have the same leaving water connection Y and Z dimensions entering water and Pump Discharge X dimen sio...

Page 10: ...RVICE AREA COIL SERVICE AREA COOLER VENT 1 4 NTP COOLER DRAIN 3 4 NPT PUMP PACKAGE LEAVING WATER 6 VICTAULIC NO PUMP PACKAGE ENTERING WATER 6 VICTAULIC SEE NOTE 4 SEE DETAIL B PUMP PACKAGE ENTERING WA...

Page 11: ...SER TUBE SERVICE AREA COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT SEE DETAIL B CONDENSER DRAIN 3 8 NPT AIR FLOW POWER BOX 230V CONTROL POWER BOX 380V 460V 575V 7 8 KNOCKOUT TO BE USED FOR LOCATING FIELD...

Page 12: ...te for draining 3 Temperature relief devices located on suction line liquid line and filter drier of each circuit and have 1 4 flare connection 4 No pump package leaving water connection is same size...

Page 13: ...CTAULIC SEE DETAIL B CONDENSER DRAIN 3 8 NPT AIR FLOW 7 8 KNOCKOUT TO BE USED FOR LOCATING FIELD POWER WIRING SCROLLING MARQUEE DISPLAY FIELD CONTROL WIRING FAN ELECTRICAL BOX 230V ONLY FEB POWER BOX...

Page 14: ...on suction line liquid line and fil ter drier of each circuit and have 1 4 flare connection 3 Dimensions are in mm inches 4 Allow 8 ft 2 4 m of service access on either side of unit for con denser co...

Page 15: ...quid line and filter drier of each circuit and have 1 4 flare connection 4 Units without a pump package have the same leaving water connection Y and Z dimensions entering water and Pump Discharge X di...

Page 16: ...d on suction line liquid line and filter drier of each circuit and have 1 4 flare connection 3 Dimensions are in mm inches 4 Allow 8 ft 2 4 m of service access on either side of unit for condenser coi...

Page 17: ...38 00 1 50 938 35 36 94 215 73 8 49 WEIGHT CU AL lb kg MAX WEIGHT CU AL PUMP lb kg WEIGHT CU CU lb kg MAX WEIGHT CU CU PUMP lb kg WEIGHT MCHX lb kg MAX WEIGHT MCHX PUMP lb kg CENTER OF GRAVITY PUMP S...

Page 18: ...RAIN 3 4 NPT COOLER ENTERING WATER 6 VICTAULIC COOLER LEAVING WATER 6 VICTAULIC CONDENSER DRAIN 3 8 NPT SCROLLING MARQUEE DISPLAY FIELD CONTROL WIRING FAN ELECTRICAL BOX FEB ALL VOLTAGES BACnet COMMUN...

Page 19: ...6 VICTAULIC NO PUMP PACKAGE ENTERING WATER 6 VICTAULIC SEE NOTE 4 PUMP PACKAGE ENTERING WATER 6 VICTAULIC COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT SEE DETAIL B VIE...

Page 20: ...TER 6 VICTAULIC COOLER ENTERING WATER 6 VICTAULIC CONDENSER DRAIN 3 8 NPT AIR FLOW FIELD CONTROL WIRING FAN ELECTRICAL BOX FEB ALL VOLTAGES POWER BOX 230V ONLY CKT A 7 8 KNOCKOUT TO BE USED FOR LOCATI...

Page 21: ...LER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A CIRCUIT A COMPRESSORS CIRCUIT B COMPRESSORS POWER BOX 1 230V CKT B 380V 460V 575V CKT A B C COIL SERV...

Page 22: ...T 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A CIRCUIT A COMPRESSORS CIRCUIT B COMPRESSORS CIRCUIT C COMPRESSORS POWER BOX 1 380V 460V...

Page 23: ...COIL SERVICE AREA LEAVING WATER 6 VICTAULIC ENTERING WATER 6 VICTAULIC COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA SERVICE AREA 1219 2 48 0 FROM EACH SIDE OF THE UNIT A A SEE DET...

Page 24: ...IRCUIT B COMPRESSORS CIRCUIT C COMPRESSORS COIL SERVICE AREA COIL SERVICE AREA LEAVING WATER 6 VICTAULIC ENTERING WATER 6 VICTAULIC COOLER VENT 1 4 NPT COOLER DRAIN 3 4 NPT COOLER TUBE SERVICE AREA A...

Page 25: ...475 170 1055 2052 1024 1374 2809 1485 9 799 UNIT 30RB MOUNTING WEIGHT lb No Pump MCHX A B C D E F G H Total 190 1007 1278 1367 1014 1362 1846 1785 1405 11 064 210 852 1677 1989 793 1219 2831 2269 114...

Page 26: ...UNIT 30RB MOUNTING WEIGHT lb Single Pump Cu Cu A B C D E F G H Total 190 1257 1718 2095 1263 1638 2374 2084 1684 14 113 UNIT 30RB MOUNTING WEIGHT kg Single Pump Al Cu A B C D Total 060 493 512 559 538...

Page 27: ...9 8 166 UNIT 30RB MOUNTING WEIGHT lb Dual Pump Cu Cu A B C D E F Total 120 837 2498 1169 1054 2739 1161 9 457 130 850 2616 1193 1252 2953 1069 9 933 150 1015 3112 1270 1240 3411 1336 11 384 160 1481 3...

Page 28: ...11315 UNIT 30RB MOUNTING WEIGHT lb Heat Reclaim MCHX A B C D E F G H Total 190 962 1311 1461 937 1519 2620 2296 1474 12580 UNIT 30RB MOUNTING WEIGHT kg Heat Reclaim MCHX A B C D Total 060 538 533 529...

Page 29: ...ase Rail Cross Section 0 1 3 4 44 mm 1 50 DIA 38 mm RIGGING HOLE B B 0 5 127 mm 0 875 DIA 22 mm MOUNTING HOLE MOUNTING PLATE 0 3 15 16 100 mm 0 1 9 16 39 89 mm REF 0 7 7 8 200 mm VIEW B B BOTTOM VIEW...

Page 30: ...970 1518 Net Fluid Volume gal 28 2 28 2 31 3 31 3 31 3 45 8 45 8 45 8 73 5 Maximum Refrigerant Pressure psig 445 445 445 445 445 445 445 445 445 Maximum Water Side Pressure without Pumps psig 300 300...

Page 31: ...28 33 COOLER Direct Expansion Shell and Tube Type Weight empty lb 1518 1518 1518 2382 2382 2382 2382 2382 Net Fluid Volume gal 73 5 73 5 73 5 86 6 86 6 86 6 86 6 86 6 Maximum Refrigerant Pressure psig...

Page 32: ...388 440 440 440 689 Net Fluid Volume L 106 106 118 118 118 173 173 173 278 Maximum Refrigerant Pressure kPa 3068 3068 3068 3068 3068 3068 3068 3068 3068 Maximum Water Side Pressure without Pumps kPa 2...

Page 33: ...COOLER Direct Expansion Shell and Tube Type Weight empty kg 689 689 689 1080 1080 1080 1080 1080 Net Fluid Volume L 278 278 278 327 327 327 327 327 Maximum Refrigerant Pressure kPa 3068 3068 3068 306...

Page 34: ...52 5 No Capacity Steps Standard 14 14 14 15 16 Optional Maximum 16 16 16 17 18 Minimum Capacity Step Standard 6 6 7 7 6 Optional 5 4 6 5 5 Capacity Module A Ckt A 31 30 29 27 25 Module A Ckt B 19 22...

Page 35: ...8 No Capacity Steps Standard 14 14 14 15 16 Optional Maximum 16 16 16 17 18 Minimum Capacity Step Standard 6 6 7 7 6 Optional 5 4 6 5 5 Capacity Module A Ckt A 31 30 29 27 25 Module A Ckt B 19 22 21 2...

Page 36: ...36 Fig 24 Unit Rigging Label Detail 30RB060 150...

Page 37: ...37 Fig 25 Unit Rigging Label Detail 30RB160 300...

Page 38: ...inlet and outlet piping Locate valves in return and supply cooler water and heat reclaim lines as close to the chiller as possible In sound sensitive applications consider the installation of piping v...

Page 39: ...pump for connection to an expansion tank Install the tank in accordance with the manufacturer s instructions Figures 29 and 30 illustrate typical single and dual pump packages Two drain connections a...

Page 40: ...units can be equipped with a factory installed heat reclaim package consisting of a shell and tube condenser PT PT T1 T2 FS PP PP D D V D PT PT Chilled Water Out Heater Optional Heater E D PT Air Sep...

Page 41: ...rement a properly sized 3 way valve must be field installed This valve will facilitate cold water start up water temperatures below 68 F 20 C and it also will be able to maintain proper head pressure...

Page 42: ...let isolation shutoff valve be placed exterior to the unit to allow removal and service of the entire pump assembly if necessary The hydronic package is supplied from the factory with a combination va...

Page 43: ...Option Thermistor Location LWT Leaving Water Fluid Temperature Field Wiring Field Communication Wiring a30 3185ef Tank Installation BAD BAD GOOD GOOD Fig 35 Tank Baffling Distribution Pump Expansion...

Page 44: ...al of particulates from the chilled water loop Using the combination valve and the field installed isolation valve at the inlet the strainer can be isolated from the chilled water loop to be cleaned T...

Page 45: ...ry secondary systems If a diaphragm expansion tank is utilized a flexible diaphragm physically separates the water air interface it is not recommended to have any air in the water loop See the section...

Page 46: ...in 6 00 in 3 hp 5 hp 7 5 hp 2 hp 80 80 78 78 73 73 65 65 54 40 6 50 in 7 00 in 7 50 in NPSHr N P S H r 81 12 2 40 3 0 10 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30R...

Page 47: ...5 2 50 12 2 40 9 1 30 6 1 20 3 0 10 0 0 0 N P S H r NPSHr LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump...

Page 48: ...000 63 09 3450 RPM NPSHr N P S H r a30 5468 a30 5469 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump Impe...

Page 49: ...PM N P S H r 5 90 in 69 69 65 65 60 60 52 52 42 31 NPSHr 3 hp 5 hp 7 5 hp 10 hp 15 hp 6 19 in 4 50 in 70 5 25 in LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomencl...

Page 50: ...24 4 80 18 3 60 12 2 40 6 1 20 0 0 0 500 31 55 3450 RPM N P S H r NPSHr LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Re...

Page 51: ...00 63 09 3450 RPM NPSHr N P S H r a30 5472 a30 5470 LEGEND NPSHr Net Positive Suction Head Pressure Required NOTE Refer to the 30RB nomenclature Fig 1 for option identification Refer to the Pump Impel...

Page 52: ...op It should be noted that these curves are for fresh water and clean heat exchangers they do not apply to heat exchangers with fouling To read the chart subtract the readings of the two pressure gage...

Page 53: ...l from the sensor Switch S2 01 must be set to Off default set ting for 0 10 vdc or On for 0 4 20 mA The switch is located behind the display The cover must be removed and the display will snap off to...

Page 54: ...protection of the chiller in case of power failure during subfreezing ambi ent temperatures or in other cases where water temperature falls below the freezing mark other methods must be used Ap propr...

Page 55: ...85 44 16 a30 4822 Fig 55 30RB060 110 Optional Heat Reclaim Pressure Drop Curves HEAT RECLAIM VESSEL PRESSURE DROP CURVES 30RB 120 190 TON 0 0 100 200 300 400 500 600 700 800 900 1000 GPM ft wg 120 15...

Page 56: ...r warranty does not cover damage due to freezing 5 Units with the heat reclaim option are supplied with a heater to protect the reclaim condenser down to 0 F 18 C If the unit controls the heat reclaim...

Page 57: ...onditioned space to the power box es be sealed to prevent airflow and moisture into the control box Duplex units require at least two separate power supplies at least one for each module depending on...

Page 58: ...S 1 Combination is identified as COMB1 in Fig 58 2 Power L is the same as COMB1 in Fig 58 3 PEB or Power Electrical Box is shown in Fig 58 30RB UNIT SIZE VOLTAGE ELECTRICAL OPTION CONNECTIONS MAIN POW...

Page 59: ...SHUTDOWN RELAY IS 10 VA SEALED 25 VA INRUSH AT 24V FIELD POWER SUPPLY IS NOT REQUIRED ICE DONE DEMAND LIMIT STEP 2 OCCUPANCY OVERRIDE DUAL SETPOINT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TB5 TB6 1 2 3 4...

Page 60: ...D 13 OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP1 PMP1 STARTER TERMINALS 13 AND 15 OF TB5 ARE FOR CONTROL OF CHILLED WATER PUMP2 PMP2 STARTER THE MAXIMUM LOAD ALLOWED FOR THE CHILLED WATER PUMP RELAY...

Page 61: ...and 15 of TB7 are for external connection of heat reclaim remote enable switch 5 Terminals 5 through 13 of TB7 are for the connection of factory installed solenoid valve control wiring LEGEND Field C...

Page 62: ...460 60 414 506 147 9 175 355 9 175 152 1 175 360 8 175 155 0 175 363 9 175 575 60 518 633 119 8 150 287 4 150 123 1 150 291 3 150 125 2 150 293 8 150 080 208 230 60 187 253 366 5 400 757 8 400 381 9...

Page 63: ...253 455 6 500 901 6 500 458 6 500 909 5 500 470 3 500 925 7 500 380 60 342 418 239 2 250 494 3 250 240 9 250 498 7 250 247 9 250 507 5 300 460 60 414 506 201 5 225 411 0 225 202 9 225 414 6 225 208 4...

Page 64: ...30 9 450 575 60 518 633 342 3 350 509 9 350 225 208 230 60 187 253 380 60 342 418 534 5 600 787 8 600 460 60 414 506 449 6 450 657 6 450 575 60 518 633 365 4 400 533 0 400 250 208 230 60 187 253 380 6...

Page 65: ...0 380 60 342 418 150 1 86 4 175 110 403 5 298 4 175 100 158 2 86 4 200 110 413 2 298 4 175 100 460 60 414 506 126 0 73 6 150 100 334 0 247 7 150 90 133 1 73 6 150 100 342 0 247 7 150 90 575 60 518 633...

Page 66: ...125 349 2 301 6 150 110 143 0 93 6 175 125 356 5 301 6 175 110 575 60 518 633 110 3 76 3 125 110 279 1 243 9 125 90 111 4 76 3 125 110 282 0 243 9 125 90 116 2 76 3 150 110 287 8 243 9 125 90 110 208...

Page 67: ...225 738 5 439 7 500 200 460 60 414 506 408 0 156 8 450 175 616 0 364 8 450 175 575 60 518 633 331 5 127 5 350 150 499 1 295 1 350 150 300 208 230 60 187 253 920 5 472 0 1000 500 1362 7 914 3 1000 500...

Page 68: ...A 345B 360B 208 230 60 6 11 9 4 11 9 380 60 6 6 5 4 6 5 460 60 6 5 4 4 5 4 575 60 6 4 3 4 4 3 190 360A 390A 390B 208 230 60 6 11 9 6 11 9 380 60 6 6 5 6 6 5 460 60 6 5 4 6 5 4 575 60 6 4 3 6 4 3 210 2...

Page 69: ...380 60 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 49 3 315 460 60 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 41 6 260 575 60 33 9 210 33 9 210 33 9 210 33 9 210 33 9 210 33 9 21...

Page 70: ...units offer several non CCN translators Refer to the separate instal lation instructions for additional wiring steps Step 7 Install Accessories A number of accessories are available to provide the fol...

Page 71: ...erican Wire Gage or 24 AWG low capacitance twisted stranded shielded copper wire The maximum length is 2000 ft Install a BT485 terminator on the first and last controller on a network segment to add b...

Page 72: ...7 6 5 4 32 1 0 9 8 7 6 5 4 32 1 0 9 BACNET BAUD RATE DIP SWITCHES ADDRESS ROTARY SWITCHES POWER LED RUN LED ERROR LED BACNET CONNECTION BAS PORT BT485 TERMINATOR Tx2 LED Rx2 LED Tx1 LED Rx1 LED EIA 48...

Page 73: ...perature Rating SmokeGard 167 F 75 C Halar 40 to 302 F 40 to 150 C Voltage 300 Vac power limited Listing UL NEC CL2P or better Fig 65 BT485 Terminator Installation AWG American Wire Gage CL2P Class 2...

Page 74: ......

Page 75: ......

Page 76: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300124 01 Printed in U S A Form 30RB 21SI Pg 76 318 12 13 Replaces 30RB...

Reviews: