Table 10A — 30RB060-190 Electrical Data — Single Point Units
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2
%
; amps 10
%
.
2. All units or modules have single point primary power connection. (Each unit or module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
UNIT 30RB
UNIT VOLTAGE
NO HYDRONIC PACKAGE
3 HP PUMP, 1750 RPM
5 HP PUMP, 1750 RPM
V-Hz (3 Ph)
Supplied
MCA
MOCP
ICF
Rec Fuse
Size
MCA
MOCP
ICF
Rec Fuse
Size
MCA
MOCP
ICF
Rec Fuse
Size
Min
Max
XL
XL
XL
XL
XL
XL
XL
XL
XL
060
208/230-60
187
253
291.5
350
682.8
350
300.6
350
693.6
350
306.9
350
700.5
350
380-60
342
418
150.9
175
362.9
175
156.0
175
368.8
175
159.0
175
372.6
175
460-60
414
506
127.9
150
302.0
150
132.1
150
306.9
150
135.0
150
310.0
150
575-60
518
633
102.4
125
244.7
110
105.7
125
248.6
125
107.8
125
251.1
125
070
208/230-60
187
253
334.7
400
777.0
400
343.8
400
787.8
400
350.1
400
794.7
400
380-60
342
418
175.5
200
428.8
200
180.8
225
434.7
200
183.6
225
438.5
200
460-60
414
506
147.9
175
355.9
175
152.1
175
360.8
175
155.0
175
363.9
175
575-60
518
633
119.8
150
287.4
150
123.1
150
291.3
150
125.2
150
293.8
150
080
208/230-60
187
253
366.5
400
757.8
400
—
—
—
—
381.9
450
775.5
450
380-60
342
418
189.3
225
401.3
200
—
—
—
—
197.4
225
411.0
225
460-60
414
506
160.6
175
334.7
175
—
—
—
—
167.7
200
342.7
200
575-60
518
633
128.6
150
270.9
150
—
—
—
—
134.0
150
277.3
150
090
208/230-60
187
253
433.6
500
875.9
500
—
—
—
—
449.0
500
893.6
500
380-60
342
418
226.9
250
480.3
250
—
—
—
—
235.0
250
490.0
250
460-60
414
506
191.4
225
399.4
225
—
—
—
—
198.5
225
407.4
225
575-60
518
633
154.6
175
322.2
175
—
—
—
—
160.0
175
328.6
175
100
208/230-60
187
253
472.0
500
914.3
500
—
—
—
—
487.4
500
932.0
500
380-60
342
418
248.7
250
502.1
250
—
—
—
—
256.8
300
511.8
300
460-60
414
506
209.2
250
417.2
225
—
—
—
—
216.3
250
425.2
250
575-60
518
633
170.0
200
337.6
200
—
—
—
—
175.4
200
344.0
200
110
208/230-60
187
253
508.6
600
950.9
600
—
—
—
—
524.0
600
968.6
600
380-60
342
418
265.3
300
518.7
300
—
—
—
—
273.4
300
528.4
300
460-60
414
506
224.1
250
432.1
250
—
—
—
—
231.2
250
440.1
250
575-60
518
633
180.8
200
348.4
200
—
—
—
—
186.2
200
354.8
200
120
208/230-60
187
253
578.1
600
1020.4
600
—
—
—
—
593.5
600
1038.1
700
380-60
342
418
304.6
350
538.0
350
—
—
—
—
312.7
350
567.6
350
460-60
414
506
256.2
300
464.2
300
—
—
—
—
263.3
300
472.2
300
575-60
518
633
208.2
225
325.8
225
—
—
—
—
213.6
225
382.2
225
130
208/230-60
187
253
626.7
700
1068.9
700
—
—
—
—
642.1
700
1086.6
700
380-60
342
418
327.7
350
581.1
350
—
—
—
—
335.8
350
590.8
350
460-60
414
506
276.5
300
484.5
300
—
—
—
—
283.6
300
492.5
300
575-60
518
633
223.3
250
391.0
250
—
—
—
—
228.7
250
397.4
250
150
208/230-60
187
253
684.3
700
1126.5
700
—
—
—
—
699.7
700
1144.2
800
380-60
342
418
360.4
400
613.8
400
—
—
—
—
368.5
400
623.5
400
460-60
414
506
303.2
350
511.2
350
—
—
—
—
310.3
350
519.2
350
575-60
518
633
246.4
250
414.1
250
—
—
—
—
251.8
300
420.5
300
160
208/230-60
187
253
744.8
800
1187.0
800
—
—
—
—
760.2
800
1204.7
800
380-60
342
418
390.1
400
643.5
400
—
—
—
—
398.2
400
653.2
400
460-60
414
506
328.9
350
536.9
350
—
—
—
—
336.0
350
544.9
350
575-60
518
633
265.9
300
433.5
300
—
—
—
—
271.3
300
439.9
300
170
208/230-60
187
253
802.4
1000
1244.6
1000
—
—
—
—
817.8
1000
1262.3
1000
380-60
342
418
422.8
450
676.2
450
—
—
—
—
430.9
450
685.9
450
460-60
414
506
355.6
400
563.6
400
—
—
—
—
362.7
400
571.6
400
575-60
518
633
289.0
300
456.6
300
—
—
—
—
294.4
300
463.0
300
190
208/230-60
187
253
920.5
1000
1362.7
1000
—
—
—
—
935.9
1000
1380.4
1000
380-60
342
418
485.2
500
738.5
500
—
—
—
—
493.3
500
748.2
500
460-60
414
506
408.0
450
616.0
450
—
—
—
—
415.1
450
624.0
450
575-60
518
633
331.5
350
499.1
350
—
—
—
—
336.9
350
505.5
350
AWG —
American Wire Gage
MOCP —
Maximum Overcurrent Protection
ICF
—
Instantaneous Current Flow
XL
—
Across-the-Line Start
MCA —
Minimum Circuit Amps
208/230
460
575 v only