background image

25HNB6 (2 to 5 Tons)

25HNB9 (2 to 5 Tons)

Infinity

r

2---Stage Heat Pump

with Puron

r

Refrigerant

Installation Instructions

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.

In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.

Recognize safety information. This is the safety--alert symbol

!

!

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand

these signal words; DANGER, WARNING, and CAUTION. These

words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe

practices which

would

result in minor personal injury or product

and property damage. NOTE is used to highlight suggestions
which

will

result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position and

install a lockout tag. There may be more than 1 disconnect

switch. Lock out and tag switch with a suitable warning label.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

Indoor Thermostat Control Options

Model

Infinity

Control

Standard

2---stage

Thermostat

25HNB6 / 25HNB9

Yes

Yes

INSTALLATION RECOMMENDATIONS

NOTE

: In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding un-

necessary turns and bends.

4. Leave some slack between structure and unit to absorb vi-

bration.

5. When passing refrigerant tubes through the wall, seal open-

ing with RTV or other pliable silicon--based caulk. (See Fig.
1.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 1.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

When outdoor unit is connected to factory--approved indoor unit,

outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of

field--supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information

located on control box cover and/or in the Check Charge section of

this instruction.

IMPORTANT

: Maximum liquid--line size is 3/8--in. OD for all

residential applications including long line applications.

IMPORTANT

: Always install the factory--supplied liquid--line

filter drier. Obtain replacement filter driers from your distributor or
branch.

Summary of Contents for Infinity 25HNB6

Page 1: ...kout tag There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may...

Page 2: ...Engineer Certification if required On rooftop applications mount on level platform or frame Place unit above a load bearing wall and isolate unit and tubing set from structure Arrange supporting memb...

Page 3: ...ring installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in vertical rise at ser...

Page 4: ...required A05227 Fig 4 Liquid Line Filter Drier Refrigerant Tubing connection Outdoor Connect vapor tube to fitting on outdoor unit vapor service valves see Table 1 Install Adapter Tube 1 Remove plast...

Page 5: ...TACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Power Connections Connect Control Wiring Route low voltage control wires through control wiring grommet and connect leads to...

Page 6: ...igest Install Accessories Refer to the individual instructions packaged with kits or accessories when installing When using a communicating control with the fan coil or the furnace dip switch adjustme...

Page 7: ...oor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 25HNB924 8 72 9 35 11 90 25HNB936 9 06 10 23 11 90 25HNB948 9...

Page 8: ...re not used AUTO defrost adjusts the defrost interval time based on the last defrost time as follows S When defrost time 3 minutes the next defrost interval 120 minutes S When defrost time 3 5 minutes...

Page 9: ...lenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the...

Page 10: ...riate error code will flash temporarily An RCD replacement board contains no model and serial information If the factory control board fails the model plug must be transferred from the original board...

Page 11: ...d when energized in high stage should measure 24vac across pin numbers PL5 2 HI and PL5 5 C When the compressor is operating in low stage the 24v DC compressor solenoid coil is de energized When the c...

Page 12: ...r must be locked in place with spheri cal nib end facing towards the front of the control box NO USE A12263 Fig 9 Outdoor Air Thermistor OAT Attachment OCT Thermistor must be secured tight on stub tub...

Page 13: ...f range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Thermal Cutout 71 Compressor operation detected then disappears while low stage d...

Page 14: ...p O RVS Cooling O B W2 W2 Heat Stage 3 furnace W W1 W W1 W1 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2...

Page 15: ...charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating...

Page 16: ...0 W Morris St S Indianapolis IN 46231 Edition Date 06 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HNB6 9 4SI...

Reviews: