Elevate Unit

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not allow water and/or ice to build up in base pan.

Elevate unit per local climate and code requirements to provide

clearance above estimated snowfall level and ensure adequate

drainage of unit.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Locate the unit in such a way that it is stable in all

circumstances including adverse weather conditions.

In Long--Line Applications, Install Liquid--Line

Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths greater

than 80 ft. (24.38 m) and/or when elevation difference between
indoor and outdoor unit is greater than

±20

ft. (

±

6.10 m), follow

all requirements of the Residential Piping and Long--Line
Guideline. If required by the Residential Piping and Long--Line

Guideline, install LSV kit, part no. KHALS0401LLS, specifically

designed for Puron

R

refrigerant heat pumps. LSV should be

installed within 2 ft. (0.61 m) of outdoor unit with flow arrow

pointing toward outdoor unit. Follow the Installation Instructions
included with accessory kit.

IMPORTANT

: Flow arrow must point toward outdoor unit.

Make Piping Connections

!

WARNING

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or

death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal. Use all service ports and open all

flow--control devices, including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Do not leave system open to atmosphere any longer than

minimum required for installation. POE oil in compressor is

extremely susceptible to moisture absorption. Always keep

ends of tubing sealed during installation.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. vertical

rise at service valve. Refrigerant tubing lengths up to 36 in.

(914.4 mm) may be buried without further special

consideration. Do not bury lines longer than 36 in. (914.4

mm).

Outdoor units may be connected to indoor section using accessory

tubing package or field--supplied refrigerant grade tubing of correct

size and condition. For tubing requirements beyond 80 ft. (24.38
m), substantial capacity and performance losses can occur.

Following the recommendations in the Residential Piping and
Long--Line Guideline will reduce these losses. Refer to Table 1 for

field tubing diameters. Refer to Table 2 for accessory requirements.

Outdoor Unit Connected to Factory--Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for

operation with factory--approved, AHRI--rated indoor unit with
highest sales volume when connected by 15 ft. (4.57 m) of

field--supplied or factory--accessory tubing, and factory--supplied
filter drier. Check refrigerant charge for maximum efficiency.

NOTE

: If the indoor furnace coil width is more than the furnace

casing width, refer to the indoor coil Installation Instructions for
transition requirements.

Table 1 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (in.)

UNIT SIZE

LIQUID

RATED VAPOR*

Connection

& Max. Tube

Diameter

Connection

Diameter

Tube

Diameter

624, 924

3/8

3/4

3/4

636, 936

3/8

7/8

7/8

648, 948

3/8

7/8

1-1/8

660, 960

3/8

7/8

1-1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for

performance data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)

horizontal or 20 ft. (6.1 m) vertical differential 250 ft. (76.2 m) Total

Equivalent Length), refer to the Residential Piping and Longline Guide

line--- Air Conditioners and Heat Pumps using Puron refrigerant.

25H

N

B

6

/25H

N

B

9

Summary of Contents for Infinity 25HNB6

Page 1: ...kout tag There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may...

Page 2: ...Engineer Certification if required On rooftop applications mount on level platform or frame Place unit above a load bearing wall and isolate unit and tubing set from structure Arrange supporting memb...

Page 3: ...ring installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in vertical rise at ser...

Page 4: ...required A05227 Fig 4 Liquid Line Filter Drier Refrigerant Tubing connection Outdoor Connect vapor tube to fitting on outdoor unit vapor service valves see Table 1 Install Adapter Tube 1 Remove plast...

Page 5: ...TACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Power Connections Connect Control Wiring Route low voltage control wires through control wiring grommet and connect leads to...

Page 6: ...igest Install Accessories Refer to the individual instructions packaged with kits or accessories when installing When using a communicating control with the fan coil or the furnace dip switch adjustme...

Page 7: ...oor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 25HNB924 8 72 9 35 11 90 25HNB936 9 06 10 23 11 90 25HNB948 9...

Page 8: ...re not used AUTO defrost adjusts the defrost interval time based on the last defrost time as follows S When defrost time 3 minutes the next defrost interval 120 minutes S When defrost time 3 5 minutes...

Page 9: ...lenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the...

Page 10: ...riate error code will flash temporarily An RCD replacement board contains no model and serial information If the factory control board fails the model plug must be transferred from the original board...

Page 11: ...d when energized in high stage should measure 24vac across pin numbers PL5 2 HI and PL5 5 C When the compressor is operating in low stage the 24v DC compressor solenoid coil is de energized When the c...

Page 12: ...r must be locked in place with spheri cal nib end facing towards the front of the control box NO USE A12263 Fig 9 Outdoor Air Thermistor OAT Attachment OCT Thermistor must be secured tight on stub tub...

Page 13: ...f range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Thermal Cutout 71 Compressor operation detected then disappears while low stage d...

Page 14: ...p O RVS Cooling O B W2 W2 Heat Stage 3 furnace W W1 W W1 W1 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2...

Page 15: ...charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating...

Page 16: ...0 W Morris St S Indianapolis IN 46231 Edition Date 06 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HNB6 9 4SI...

Reviews: