background image

8

UTILITY RELAY  

*

UTILITY SIGNAL

OPEN RELAY

* SUPPLIED BY UTILITY PROVIDER

A  B  C

A  B  C

A12260

LLS

Liquid Line Solenoid

A   B   C

A   B   C

A12261

Fig. 7 -- 2--Stage Control Board

GENERAL INFORMATION

Infinity Controlled low ambient cooling:

This unit is capable of low ambient cooling down to 0

°

F (--17.8

°

C)

without a kit ONLY when using an Infinity Control. A low
ambient kit is not required for Infinity controlled low ambient

operation. The Infinity Control provides an automatic evaporator
freeze thermostat. Low ambient cooling must be enabled in the

User Interface setup. Fan may not begin to cycle until about 40

°

F

(4.4

°

C) OAT. Fan will cycle based on coil and outdoor air

temperature.
Infinity controlled low ambient mode operates as follows:

S

Fan is OFF when outdoor coil temperature is less than outdoor air
temperature (+ 3

_

F/1.7

_

C) or outdoor fan has been ON for 30

minutes. (Fan is turned off to allow refrigerant system to stabilize.)

S

Fan is ON when outdoor coil temperature is less than outdoor air
temperature (+25

_

F/13.9

_

C) or outdoor coil temperature is more

than 80

_

F (26.7

_

C) or if outdoor fan has been OFF for 30 minutes.

(Fan is turned on to allow refrigerant system to stabilize.)

S

Low pressure switch is ignored for first 3 minutes during low
ambient start up. After 3 minutes, if LPS trips, then outdoor fan
motor is turned off for 10 minutes, with the compressor running. If

LPS closes within 10 minutes then cooling continues with the
outdoor fan cycling per the coil temperature routine listed above

for the remainder of the cooling cycle. If the LPS does not close
within 10 minutes, then the normal LPS trip response (shut down

cooling operation and generate LPS trip error) will occur.

Defrost

This control offers 5 possible defrost interval times: 30, 60, 90, 120
minutes, or AUTO.
Defrost intervals are selected by dip switches on the unit control
board or by the Infinity Control User Interface. The Infinity

Control selection overrides the control board dip switch settings.
Defrost interval times: 30, 60, 90, and 120 minutes or AUTO are
selected by the Infinity Control User Interface (the dip switches are

not used.)
AUTO defrost adjusts the defrost interval time based on the last

defrost time as follows:

S

When defrost time <3 minutes, the next defrost interval=120
minutes.

S

When defrost time 3--5 minutes, the next defrost interval=90
minutes.

S

When defrost time 5--7 minutes, the next defrost interval=60
minutes.

S

When defrost time >7 minutes, the next defrost interval=30

minutes.

The control board accumulates compressor run time. As the
accumulated run time approaches the selected defrost interval time,

the control board monitors the coil temperature sensor for a defrost
demand. If a defrost demand exists, a defrost cycle will be initiated

at the end of the selected time interval. A defrost demand exists

when the coil temperature is at or below 32

_

F (0

_

C) for 4 minutes

during the interval.
The defrost cycle is terminated when the coil temperature reaches
65

_

F (18.33

_

C)or 10 minutes has passed. When OAT is > 25

°

F

(--3.9

°

C), defrost will occur in low or high stage as demanded by

the thermostat or User Interface.
If OAT is

25

°

F (3.9

_

C), defrost will occur in high stage only,

regardless of thermostat or User Interface demand, and will
terminate at 50

_

F (10

_

C) coil temperature with a minimum of 2.5

minutes in defrost.
If the coil temperature does not reach 32

_

F (0

_

C) within the

interval, the interval timer will be reset and start over.

S

Upon initial power up the first defrost interval is defaulted to 30

minutes. Remaining intervals are at selected times.

S

Defrost is only allowed to occur below 50

_

F (10

_

C) outdoor

ambient temperature.

The outdoor fan output (ODF) will remain off for 20 seconds after

termination. This delay will allow time for the system to capture

the heat from the outdoor coil and reduce the “steam cloud” effect
that may occur on transition from defrost to heating cycle. The

outdoor fan output OFF delay of 20 seconds may be defeated to
enable the fan to energize immediately at the time of termination

and 12 seconds prior to the reversing valve de--energizing through
the

User

Interface

setup

screen

(available

with

SYSTXBBUID01--C), or forced defrost pins as follows:
The ODF fan delay defeat can be toggled by shorting the forced
defrost pins for >15 seconds while in the standby mode (status

LED on solid). The LED will start to flash when the toggle has
taken place.

25H

N

B

6

/25H

N

B

9

Summary of Contents for Infinity 25HNB6

Page 1: ...kout tag There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may...

Page 2: ...Engineer Certification if required On rooftop applications mount on level platform or frame Place unit above a load bearing wall and isolate unit and tubing set from structure Arrange supporting memb...

Page 3: ...ring installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in vertical rise at ser...

Page 4: ...required A05227 Fig 4 Liquid Line Filter Drier Refrigerant Tubing connection Outdoor Connect vapor tube to fitting on outdoor unit vapor service valves see Table 1 Install Adapter Tube 1 Remove plast...

Page 5: ...TACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Power Connections Connect Control Wiring Route low voltage control wires through control wiring grommet and connect leads to...

Page 6: ...igest Install Accessories Refer to the individual instructions packaged with kits or accessories when installing When using a communicating control with the fan coil or the furnace dip switch adjustme...

Page 7: ...oor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 25HNB924 8 72 9 35 11 90 25HNB936 9 06 10 23 11 90 25HNB948 9...

Page 8: ...re not used AUTO defrost adjusts the defrost interval time based on the last defrost time as follows S When defrost time 3 minutes the next defrost interval 120 minutes S When defrost time 3 5 minutes...

Page 9: ...lenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the...

Page 10: ...riate error code will flash temporarily An RCD replacement board contains no model and serial information If the factory control board fails the model plug must be transferred from the original board...

Page 11: ...d when energized in high stage should measure 24vac across pin numbers PL5 2 HI and PL5 5 C When the compressor is operating in low stage the 24v DC compressor solenoid coil is de energized When the c...

Page 12: ...r must be locked in place with spheri cal nib end facing towards the front of the control box NO USE A12263 Fig 9 Outdoor Air Thermistor OAT Attachment OCT Thermistor must be secured tight on stub tub...

Page 13: ...f range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Thermal Cutout 71 Compressor operation detected then disappears while low stage d...

Page 14: ...p O RVS Cooling O B W2 W2 Heat Stage 3 furnace W W1 W W1 W1 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2...

Page 15: ...charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating...

Page 16: ...0 W Morris St S Indianapolis IN 46231 Edition Date 06 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HNB6 9 4SI...

Reviews: