background image

10

MAJOR COMPONENTS

2--Stage Control Board

The HP control board controls the following functions:

S

High and low stage compressor contactor operation

S

Outdoor fan motor operation

S

Reversing valve operation

S

Defrost operation

S

Low ambient cooling

S

Crankcase heater operation

S

Compressor external protection

S

Pressure switch monitoring

S

Time Delays

Field Connections

On non--communicating (non--Infinity) system, the two--stage

control receives 24vac low--voltage control system inputs through
the Y1, Y2, and O connections located at the bottom of the control

board (see Fig. 7.) On a non--communicating system, output W1 is
connected to the control board for auxiliary heat.
For a communicating system, use the AB Infinity connections.

Two Stage Compressor

The two stage compressor contains motor windings that provide
2--pole (3500 RPM) operation.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into the compressor shell when
differential between suction and discharge pressure exceeds

550--625 psi. The compressor is also protected by an internal
overload attached to motor windings.

Compressor Control Contactor

The contactor has a 24volt coil. The electronic control board

controls the operation of the contactor.

TROUBLESHOOTING

If the compressor fails to operate with a cooling call, Table 4 can be

used to verify if there is any damage to the compressor windings
causing system malfunction.

Table 4 – Winding Resistance

Winding

Winding resistance at 70

_

F +/--- 20

_

F

(21.11

_

C +/--- 11.11

_

C)

024

036

048

060

Start

(S---C)

1.64

1.52

1.86

1.63

Run

(R---C)

1.30

0.88

0.52

0.39

Systems Communication Failure

If communication with the Infinity control is lost with the User
Interface, the control will flash the appropriate fault code. (See

Table 6.) Check the wiring to the User Interface and the indoor and
outdoor units.

Model Plug

Each control board contains a model plug. The correct model plug

must be installed for or the system to operate properly. (See Table
5.)

Table 5 – Model Plug Information

MODEL

NUMBER

MODEL PLUG

NUMBER

PIN RESISTANCE

(K---ohms)

Pins 1---4

Pins 2---3

25HNB624

HK70EZ041

18

91

25HNB636

HK70EZ043

18

150

25HNB648

HK70EZ045

18

220

25HNB660

HK70EZ047

18

360

25HNB924

HK70EZ010

5.1

120

25HNB936

HK70EZ012

5.1

180

25HNB948

HK70EZ014

5.1

270

25HNB960

HK70EZ016

11

5.1

The model plug is used to identify the type and size of unit to the
control.
On new units, the model and serial numbers are input into the
board’s memory at the factory. If a model plug is lost or missing at

initial installation, the unit will operate according to the

information input at the factory and the appropriate error code will
flash temporarily. An RCD replacement board contains no model

and serial information. If the factory control board fails, the model
plug must be transferred from the original board to the replacement

board for the unit to operate.

NOTE

:

The model plug takes priority over factory model

information input at the factory. If the model plug is removed after
initial power up, the unit will operate according to the last valid
model plug installed, and flash the appropriate fault code
temporarily.

Pressure Switch Protection

The outdoor unit is equipped with high-- and low--pressure

switches. If the control senses the opening of a high-- or

low--pressure switch, it will respond as follows:

1. De--energize the compressor contactor.
2. Keep the outdoor fan operating for 15 minutes.
3. Display the appropriate fault code (see Table 6).
4. After a 15 minute delay, if there is a call for cooling or heat-

ing and LPS or HPS is reset, the compressor contactor is
energized.

5. If LPS or HPS has not closed after a 15 minute delay, the

outdoor fan is turned off. If the open switch closes anytime

after the 15 minute delay, then resume operation with a call
for cooling or heating.

6. If LPS or HPS trips 3 consecutive cycles, the unit operation

is locked out for 4 hours.

7. In the event of a high--pressure switch trip or high--pressure

lockout, check the refrigerant charge, outdoor fan operation,
and outdoor coil (in cooling) for airflow restrictions, or in-
door airflow in heating.

8. In the event of a low--pressure switch trip or low--pressure

lockout, check the refrigerant charge and indoor airflow

(cooling) and outdoor fan operation and outdoor coil in
heating.

Control Fault

If the outdoor unit control board has failed, the control will flash
the appropriate fault code (see Table 6). The control board should

be replaced.

Brown--Out Protection

If the line voltage is less than 187v for at least 4 seconds, the

appropriate compressor contactor and fan relay are de--energized.
Compressor and fan operation are not allowed until voltage is a

minimum of 190v. The control will flash the appropriate fault code
(see Table 6).

230V Brown--Out Protection Defeated

The brownout feature can be defeated if needed for severe noisy

power conditions. This defeat should always be a last resort to
solving the problem. Defeat is available on the User Interface

setup screen (available with SYSTXBBUID01--C), or can be

initiated through the forced defrost pins for non--communicating
systems as follows:
The brownout toggle is accomplished by sorting the defrost pins
from power up with the OAT and OCT sensor connector removed.

After 3 seconds, the status of the force defrost short and the

OAT/OCT as open will be checked. If correct, then the brownout
will be toggled.
Status code 6 shows the brownout is disabled.
Status code 5 shows the brownout is active.

25H

N

B

6

/25H

N

B

9

Summary of Contents for Infinity 25HNB6

Page 1: ...kout tag There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may...

Page 2: ...Engineer Certification if required On rooftop applications mount on level platform or frame Place unit above a load bearing wall and isolate unit and tubing set from structure Arrange supporting memb...

Page 3: ...ring installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in vertical rise at ser...

Page 4: ...required A05227 Fig 4 Liquid Line Filter Drier Refrigerant Tubing connection Outdoor Connect vapor tube to fitting on outdoor unit vapor service valves see Table 1 Install Adapter Tube 1 Remove plast...

Page 5: ...TACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Power Connections Connect Control Wiring Route low voltage control wires through control wiring grommet and connect leads to...

Page 6: ...igest Install Accessories Refer to the individual instructions packaged with kits or accessories when installing When using a communicating control with the fan coil or the furnace dip switch adjustme...

Page 7: ...oor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 25HNB924 8 72 9 35 11 90 25HNB936 9 06 10 23 11 90 25HNB948 9...

Page 8: ...re not used AUTO defrost adjusts the defrost interval time based on the last defrost time as follows S When defrost time 3 minutes the next defrost interval 120 minutes S When defrost time 3 5 minutes...

Page 9: ...lenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the...

Page 10: ...riate error code will flash temporarily An RCD replacement board contains no model and serial information If the factory control board fails the model plug must be transferred from the original board...

Page 11: ...d when energized in high stage should measure 24vac across pin numbers PL5 2 HI and PL5 5 C When the compressor is operating in low stage the 24v DC compressor solenoid coil is de energized When the c...

Page 12: ...r must be locked in place with spheri cal nib end facing towards the front of the control box NO USE A12263 Fig 9 Outdoor Air Thermistor OAT Attachment OCT Thermistor must be secured tight on stub tub...

Page 13: ...f range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low Stage Thermal Cutout 71 Compressor operation detected then disappears while low stage d...

Page 14: ...p O RVS Cooling O B W2 W2 Heat Stage 3 furnace W W1 W W1 W1 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2...

Page 15: ...charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating...

Page 16: ...0 W Morris St S Indianapolis IN 46231 Edition Date 06 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HNB6 9 4SI...

Reviews: