1. Score groove in corner 1 in both directions as far as you can reach.
2. Starting in corner 1, tap-out all sides with a small hammer. Be careful
    not to damage any other part of unit.
3. If side from corner 3 to 4 is not accessible due to heat exchanger,
    pivot panel up and down by hand until remaining side breaks off.

INSTRUCTIONS FOR REMOVING DOWNSHOT PANELS

A09054

Fig. 9 -- Vertical (Downflow) Discharge Knockouts

TRAP
OUTLET

1-in. (25 mm) min.

2-in. (51 mm) min.

A09052

Fig. 10 -- Condensate Trap

Install Gas Piping

The gas supply pipe enters the unit through the access hole

provided. The gas connection to the unit is made to the 1/2--in.
FPT gas inlet on the gas valve.
Install a gas supply line that runs to the heating section. Refer to
Table 2 and the current edition of NFGC in the U.S. and the current

NSCNGPIC in Canada. Do not use cast--iron pipe. It is
recommended that a black iron pipe is used. Check the local utility

for recommendations concerning existing lines. Size gas supply

piping for 0.5 in. wc maximum pressure drop. Never use pipe
smaller than the 1/2--in. FPT gas inlet on the unit gas valve.
For natural gas applications, the gas pressure at unit gas connection
must not be less than 4.0 in. wc or greater than 13 in. wc while the

unit is operating. For propane applications, refer to propane

conversion kit instructions.
A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gauge

connection, must be installed immediately upstream of the gas
supply connection to the gas valve and downstream of manual

equipment shutoff valve.
When installing the gas supply line, observe local codes pertaining

to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1--2006

(in Canada, CAN/CGA B149.1).

NOTE

: In the state of Massachusetts:

1. Gas supply connections MUST be performed by a licensed

plumber or gas fitter.

2. When flexible connectors are used, the maximum length

shall not exceed 36 in. (915 mm).

3. When lever handle type manual equipment shutoff valves

are used, they shall be T--handle valves.

4. The use of copper tubing for gas piping is NOT approved

by the state of Massachusetts.

In the absence of local building codes, adhere to the following
pertinent recommendations:

1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.

for every 15 ft (4.6 m) of length to prevent traps. Grade all

horizontal runs downward to risers. Use risers to connect to
heating section and to meter.

2. Protect all segments of piping system against physical and

thermal damage. Support all piping with appropriate straps,
hangers, etc. Use a minimum of one hanger every 6 ft (1.8

m). For pipe sizes larger than 1/2 in., follow
recommendations of national codes.

OUT

TEE

NIPPLE

CAP

IN

C99020

Fig. 11 -- Sediment Trap

3. Apply joint compound (pipe dope) sparingly and only to

male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied
petroleum gases as specified by local and/or national codes.

Never use Teflon tape.

4. Install sediment trap in riser leading to heating section (See

Fig. 11). This drip leg functions as a trap for dirt and
condensate.

5. Install an accessible, external, manual main shutoff valve in

gas supply pipe within 6 ft (1.8 m) of heating section.

6. Install ground--joint union close to heating section between

unit manual shutoff and external manual main shut off
valve.

7. Pressure test all gas piping in accordance with local and

national plumbing and gas codes before connecting piping
to unit.

NOTE

: Pressure test the gas supply system after the gas supply

piping is connected to the gas valve. The supply piping must be
disconnected from the gas valve during the testing of the piping
systems when test pressure is in excess of 0.5 psig. Pressure test the
gas supply piping system at pressures equal to or less than 0.5 psig.
The unit heating section must be isolated from the gas piping
system by closing the external main manual shutoff valve and
slightly opening the ground--joint union.

48X

T

--

A

Summary of Contents for INFINITIR 15 SEER 48XT-A

Page 1: ...Ground Screw 12 Routing Control Power Wires 12 Accessory Installation 13 Special Procedures for 208 v Operation 13 PRE START UP 15 START UP 16 28 Unit Start Up and Troubleshooting 16 Sequence of Oper...

Page 2: ...ated for Puron R 410A WARNING CUT HAZARD Failure to follow this caution may result in personal injury When removing access panels or performing maintenance functions inside your unit be aware of sharp...

Page 3: ...taff should handle and install this equipment When working with this equipment observe precautions in the literature on tags stickers and labels attached to the equipment and any other safety precauti...

Page 4: ...set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of duct rest on curb 5 Insulate...

Page 5: ...5 A09150 Fig 5 48XT A24 30 Unit Dimensions 48XT A...

Page 6: ...6 A09151 Fig 6 48XT A36 60 Unit Dimensions 48XT A...

Page 7: ...2800 22 559 1 8 825 2800 22 559 1 8 825 2800 22 559 1 8 825 2800 22 559 1 8 825 INDOOR COIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nomin...

Page 8: ...ill Size Natural Gas 3 38 3 33 3 31 3 38 3 33 3 31 HIGH PRESSURE SWITCH psig Cut out Reset Auto 670 10 470 25 HIGH PRESSURE SWITCH 2 psig Compressor Solenoid Cut out Reset Auto 565 15 455 15 LOSS OF C...

Page 9: ...anvas or similar heat resistant material connector between ductwork and unit discharge connection If flexible duct is used insert a sheet metal sleeve inside duct Heat resistant duct connector or shee...

Page 10: ...tion requires draining the condensate water away from the unit install a field supplied 2 in 51 mm trap at the condensate connection to ensure proper drainage Condensate trap is available as an access...

Page 11: ...th shall not exceed 36 in 915 mm 3 When lever handle type manual equipment shutoff valves are used they shall be T handle valves 4 The use of copper tubing for gas piping is NOT approved by the state...

Page 12: ...ircuit breaker size and minimum circuit amps ampacity for wire sizing The field supplied disconnect may be mounted on the unit over the high voltage inlet hole See Fig 5 and 6 Operation of unit on imp...

Page 13: ...appear at UI Re wire thermistor correctly for normal operation B Humidifier Connections The furnace control board terminal marked HUM is provided for low voltage 24 vac control of a humidifier No hum...

Page 14: ...AD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 13 Line Power Connections FURNACE BOARD...

Page 15: ...NG CAUTION and INFORMATION labels attached to or shipped with unit 3 Make the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disconnected wires etc...

Page 16: ...ion Fault on amber STATUS LED No further troubleshooting information will be available at UI until communications are re established If either COMM LED does not light within proper time period and sta...

Page 17: ...0 VAC or 24 VAC Blower runs for 90 seconds if unit is powered up during a call for heat R W W1 closed or R W W1 opens during blower on delay period STATUS CODE 13 LIMIT CIRCUIT LOCKOUT Lockout occurs...

Page 18: ...18 A09080 Fig 17 Wiring Schematic 48XT A Single Phase Gas Inputs 040 060 090 kBtu hr 48XT A...

Page 19: ...19 A09081 Fig 18 Wiring Schematic 48XT A Single Phase Gas Inputs 115 130 kBtu hr 48XT A...

Page 20: ...h fine steel wool proper flame sense microamps 5 microamps D C min 4 0 6 0 nominal manual valve shut off low inlet gas pressure control ground continuity gas valve defective or turned off flame sensor...

Page 21: ...satisfied NOTE Heat stages are not shortened due to a 5 degree or higher demand All stages are utilized for the full allotted time described above If the UI determines it is making sufficient progress...

Page 22: ...e Ther mal Cutout 72 Compressor voltage sensed then disappears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installed...

Page 23: ...O are selected by the Infinity Control User Interface the dip switches are not used AUTO defrost adjusts the defrost interval time based on the last defrost time as follows S When defrost time 3 minut...

Page 24: ...low of gas to the burners and de energizing the HUM terminal The inducer motor will remain on for a 4 second post purge period The indoor blower and air cleaner terminal EAC 1 will remain energized fo...

Page 25: ...s meter to complete one revolution d Divide number of seconds in step c into 3600 number of seconds in 1 hour e Multiply result of step d by the number of cubic feet shown for one revolution of test d...

Page 26: ...ssive restrictions causing static pressures in excess of 5 in wc d Make sure model plug is installed 8 Final Check a Turn off gas to unit b Remove manometer from pressure tap c Replace pipe plug on ma...

Page 27: ...e component test section or Status Code Label for explanation of status codes NOTE To repeat component test turn setup switch SW1 6 to OFF and then back ON Check for Refrigerant Leaks Locate and repai...

Page 28: ...se unavailable If communications cannot be established with the UI the Infinity furnace board will enable the standard thermostat input terminals to allow simple thermostatic control of the 48XT A uni...

Page 29: ...0 047 42 0 014 0 017 0 020 0 024 0 027 0 031 0 035 0 039 0 043 48 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 Table 8 Filter Pressure Drop Table...

Page 30: ...maintenance to the accessories as recommended in the accessory instructions Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the...

Page 31: ...the motor shaft when tightening 7 Replace grille Infinity Top A06035 UNIT SIZE A DIM IN MM 24 1 26 30 1 26 36 1 26 42 1 26 48 11 32 9 60 9 16 14 Fig 25 Outdoor Fan Blade Clearance Electrical Controls...

Page 32: ...efrigerant charging REFRIGERANT UNIT OPERATION SAFETY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or equipment damage This system uses Puron R 410A refriger...

Page 33: ...contactor and fan relay are de energized Compressor and fan operation are not allowed until voltage is a minimum of 190v The control will flash the appropriate fault code See Table 4 230V LINE POWER D...

Page 34: ...e thermistor comparison is not performed during low ambient cooling operation FAILED THERMISTOR DEFAULT OPERATION Factory defaults have been provided in the event of failure of outdoor air thermistor...

Page 35: ...0 psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oi...

Page 36: ...load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant evacuate system and re charge O...

Page 37: ...t 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace filter...

Page 38: ...I START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY...