![background image](http://html.mh-extra.com/html/carrier/hfc-134a/hfc-134a_installation-instructions-manual_2562209036.webp)
Legend
MWB —
Marine Waterbox
NIH —
Nozzle-In-Head Waterbox
*Based on 2 pass NIH waterboxes. If 2 pass MWB are used, add an additional 2,250 lb (1021 kg).
†Based on 2 pass NIH waterboxes. If 2 pass MWB are used, add an additional 2,100 lb (953 kg).
Table 1A — Rigging and Operating Weights — English (lb)
Heat Exchanger Combinations
6032
6032L
Condenser
22,000
28,000
Cooler
31,000
31,000
Economizer
1,900
1,900
Steel Base (includes Storage Tank)
11,000
11,000
Compressor
6,000
6,000
Motor
5,000
5,000
Pumpout
200
200
Suction Elbow
500
500
Miscellaneous Piping
750
750
Control Center
100
100
Total Rigging Weight
78,450
84,450
Refrigerant Charge (HFC-134a)
5,050
5,850
Cooler Water
4,250*
4,250*
Condenser Water
3,100†
4,300†
Total Operating Weight
90,850
98,850
Summary of Contents for HFC-134a
Page 40: ...Figure 1 Model Number Identification ...
Page 41: ...Figure 2 Typical 19FA Installation 1400 2200 Tons 4922 7735 kW ...
Page 42: ...Figure 3 Machine Rigging Guide 3 Indicates center of gravity ...
Page 44: ...Figure 5 Machine Footprint ...
Page 45: ...Figure 6 Machine Contact Surfaces with Anchor Bolts ...
Page 51: ...Figure 12 Water Piping Oil Cooler to Chilled Water Circuit Typical ...
Page 52: ...Figure 13 Pumpout Unit ...
Page 53: ...Figure 14 Typical 19FA Relief Valve Tree for Storage Vessel ...
Page 54: ...Figure 15 Compressor Terminal Arrangement 18 Lead Rear Inlet ...
Page 55: ...Figure 16 Compressor Terminal Arrangement 18 Lead Top Inlet ...
Page 56: ...Figure 17 Compressor Terminal Arrangement 18 Lead Side Inlet ...
Page 57: ...Figure 18 Oil Pump Wiring ...
Page 58: ...Figure 19 Oil Heater and Control Power Wiring ...
Page 59: ...Figure 20 Pumpout Unit Controls ...
Page 60: ...Figure 21 Pumpout Unit Wiring Schematic ...
Page 61: ...Figure 22 Carrier Comfort Network Communication Bus Wiring ...
Page 62: ...Figure 23 COMM1 CCN Communication Wiring For Multiple Chillers Typical ...
Page 63: ...Figure 24 Typical 19FA With Free Standing Starter ...
Page 65: ...Figure 26 19FA Insulation ...