Install Machine Supports
The 19FA machines are typically placed directly on a level floor and do not require isolation
equipment. Check job data for specific information. The standard contact surfaces for floor
mounting are shown in
Figure 5
and
Figure 6
.
When isolation pads are specified by the customer, 7 shear flex pads are shipped with the
machine and strapped to the cooler shell. These pads are placed under the machine base as
shown in
Figure 5
and
Figure 6
. If desired, the base may be anchored through four 1 1/2 in.
Click here for Figure 3 — Machine Rigging Guide
Click here for Table 1A — Rigging and Operating Weights — English (lb)
Click here for Table 1B — Rigging and Operating Weights — SI (kg)
Click here for Figure 4 — 19FA Dimensions
Summary of Contents for HFC-134a
Page 40: ...Figure 1 Model Number Identification ...
Page 41: ...Figure 2 Typical 19FA Installation 1400 2200 Tons 4922 7735 kW ...
Page 42: ...Figure 3 Machine Rigging Guide 3 Indicates center of gravity ...
Page 44: ...Figure 5 Machine Footprint ...
Page 45: ...Figure 6 Machine Contact Surfaces with Anchor Bolts ...
Page 51: ...Figure 12 Water Piping Oil Cooler to Chilled Water Circuit Typical ...
Page 52: ...Figure 13 Pumpout Unit ...
Page 53: ...Figure 14 Typical 19FA Relief Valve Tree for Storage Vessel ...
Page 54: ...Figure 15 Compressor Terminal Arrangement 18 Lead Rear Inlet ...
Page 55: ...Figure 16 Compressor Terminal Arrangement 18 Lead Top Inlet ...
Page 56: ...Figure 17 Compressor Terminal Arrangement 18 Lead Side Inlet ...
Page 57: ...Figure 18 Oil Pump Wiring ...
Page 58: ...Figure 19 Oil Heater and Control Power Wiring ...
Page 59: ...Figure 20 Pumpout Unit Controls ...
Page 60: ...Figure 21 Pumpout Unit Wiring Schematic ...
Page 61: ...Figure 22 Carrier Comfort Network Communication Bus Wiring ...
Page 62: ...Figure 23 COMM1 CCN Communication Wiring For Multiple Chillers Typical ...
Page 63: ...Figure 24 Typical 19FA With Free Standing Starter ...
Page 65: ...Figure 26 19FA Insulation ...